• 제목/요약/키워드: grounding resistance

검색결과 246건 처리시간 0.029초

국제 표준(IEC)에 의한 접지 설계 및 이에 대한 안전성 분석·평가 (Design and A Safety Analysis and Assessment of a Grounding System according to International Standards)

  • 김두웅;조만형;김한수;신대성;류기환;김철환
    • 조명전기설비학회논문지
    • /
    • 제29권10호
    • /
    • pp.54-59
    • /
    • 2015
  • In this paper, we evaluate safety of grounding system which is designed according to IEC standards. Safety assessment of construction site and grounding system of building is needed before construction for the safety of human in building. Until now, in case of domestic field, design of grounding system is proceeded based on methods which are proposed in IEEE Std. 80. In other words, it is not in the situation that grounding system is designed based on IEC standards. Therefore, we propose a method which designs grounding system and evaluates safety of it according to IEC standards. We measure ground resistance of construction site using measuring equipment of ground resistance. Using this value, soil structure and ground resistivity are obtained through program analysis. CDEGS program of SES company is used for simulation analysis.

전위강하법에 의한 접지저항측정에 미치는 전위보조전극 위치의 영향 (Effects of the Position of Potential Probe on Ground Resistance Measurements Using the Fall-of-Potential Method)

  • 이복희;어주홍;김성원
    • 조명전기설비학회논문지
    • /
    • 제15권2호
    • /
    • pp.97-104
    • /
    • 2001
  • 본 논문에서는 전위강하법에 의한 접지저항 측정시 전위보조전극 위치의 영향에 대하여 기술하였다. 전위강하법에서 접지저항은 이론적으로 전위보조전극을 피측정 접지전극과 전류보조전극이 이루는 일직선상에 위치시킬때 61.8[%]법칙을 적용하여 측정한다. 하지만 측정현장의 사정상 전위보조전극의 위치를 피측정 접지전극과 전류 보조전극이 이루는 일직선과 어느 정도의 각도를 가지도록 시설하여 접지저항을 측정하게 될 경우에 측정오차가 발생하게 되고 보정이 필요하다. 본 연구에서의 측정대상 전극은 길이 2.4 [m]의 봉형 접지전극으로 하였으며, 피측정 접지전극, 전위보조전극, 전류보조전극이 일직선상에 놓이지 않은 상태에서 접지저항을 측정하면 측정값은 항상 (-)의 오차를 나타내었고, 이들 전극이 이루는 각도가 증가함에 따라 측정 오차도 증가하였다.

  • PDF

배전계통에서 낙뢰보호용 피뢰기의 접지저항 영향에 관한 연구 (A Study on the Grounding Resistance Effects of Lightning Arrester for Lightning Stroke Protection in Electric Distribution Systems)

  • 김경철;정지원;이규진
    • 조명전기설비학회논문지
    • /
    • 제24권6호
    • /
    • pp.107-114
    • /
    • 2010
  • 낙뢰는 구름이 가진 높은 전압이 대지로 방출되는 현상이다. 낙뢰 보호 접지는 낙뢰로부터 건물, 배전선로와 전기설비를 보호하는 중요한 역할을 한다. 기기 접지는 제한된 중성점 전위상승을 위한 목적으로 한다. 기기 접지는 제한된 중성점 전위상승을 위한 목적으로 한다. 본 논문에서는 낙뢰가 배전선로에 급습했을 때 중성점 전위와 피뢰기의 제한 전압을 분석하여 피뢰기 접지저항의 영향을 심도 있게 조사하였다. 사례연구는 EDSA 프로그램으로 수치와 그래프로 시뮬레이션하였다.

배전전주용 스테인리스강판 접지전극의 접지 특성분석 (Grounding Characteristics Analysis of the Stainless-steel Plate Grounding Electrode for Distribution Poles)

  • 김경철;이규진;김민성;정지원
    • 조명전기설비학회논문지
    • /
    • 제24권8호
    • /
    • pp.94-100
    • /
    • 2010
  • 접지시스템은 전기설비의 기준 전위점을 확보할뿐만 아니라 낮은 대지저항으로 고장전류나 과도 전류를 흐르게 한다. 접지임피던스는 주파수에 대한 함수로 고장이나 과도전류가 넓은 범위의 주파수 성분을 포함하기 때문에 접지성능을 평가하는데 중요한 역할을 한다. 본 논문에서는 스테인리스강판 접지전극의 접지특성을 파악하기 위하여 3점 전위강하법으로 접지저항, 접지임피던스와 과도접지임피던스를 측정하였다. 측정된 데이터를 이용하여 접지임피던스와 과도접지임피던스의 등가 전달함수 모델은 ARMA 기법으로 모델링 되었고, 규약접지임피던스로 비교하여 평가하였다.

봉상접지극의 과도임피던스 특성 (Transient Impedance Characteristics of Grounding Rods)

  • 김일권;송재용;길경석;권장우
    • 한국정보통신학회논문지
    • /
    • 제5권1호
    • /
    • pp.133-143
    • /
    • 2001
  • 본 논문은 직각파 및 뇌충격진류에 대한 봉상접지각의 과도임피던스 특성을 정상접지지항과 비교.분석하였다. 접지계는 단일$(\Psi10[mm], 1[m])$과 5[m]의 간격을 두고 서로 연접한 3연접 봉상접지극으로 구성하였으며, 과도 임피던스 특성을 분석하기 위하여 상승시간 30[ns], 펄스폭 $20[\mus]$의 직각파전류 발생장치를 설계 제작하였다. 실제 낙뢰에 의한 접지임피던스의 변화를 관찰하기 위하여, 국제규격 ANSI/IEEE, IEC에 규정되어 있는 뇌충격전류를 인가하여 이에 따른 특성변화를 측정.분석하였다. 접지계로 유입된 과도전류는 접지계의 전위를 상승시키며, 이 때의 전위상승과 유입전류의 비로써 접지임피던스를 산출하며, 뇌격전류에 대한 경제적인 보호 수준을 평가.예측하기 위하여 임피던스 파라미터를 측정결과로부터 산출하였다. 또한 연접에 따른 접지임피던스의 감소와 접지리드선이 미치는 영향도 분석하였다.

  • PDF

반구형 전극계에서 물의 저항률을 이용한 접지시스템의 등가회로 구성 (Make-up of Equivalent Circuit of Grounding System using Water Resistivity in Hemispherical Electrode System)

  • 이복희;최종혁;배성배
    • 조명전기설비학회논문지
    • /
    • 제22권8호
    • /
    • pp.109-115
    • /
    • 2008
  • 현재 우리나라의 접지시스템의 설계기준은 낮은 주파수에서 측정된 저항값을 기반으로 한다. 고주파 성분을 포함하는 뇌서지가 접지시스템에 인가되면, 접지임피던스는 정상상태의 저항과 매우 다르게 된다. 이 논문은 접지시스템의 고주파 성능에 대한 물의 저항률의 영향을 파악하기 위하여 대지를 모의하는 수조를 이용하여 물의 저항률에 따른 어드미턴스의 주파수 의존성을 기술하였다. 500[${\Omega}{\cdot}m$] 이상의 높은 물의 저항률에서 용량성 효과에 의해 주파수가 증가함에 따라 어드미턴스와 컨덕턴스가 증가하는 것으로 나타났다. 반면에, 500[${\Omega}{\cdot}m$] 미만의 낮은 저항률에서는 유도성 효과에 의해 주파수가 증가함에 따라 어드미턴스와 컨덕턴스가 감소하는 것으로 나타났다. 또한 200[kHz]에서 5[MHz]에 이르는 주파수 범위에서 전류와 전압의 위상차가 증가하는 것으로 나타났다. 결론적으로, 접지시스템의 주파수 의존성은 대지의 저항률과 밀접한 관계가 있으며, 주파수와 대지저항률이 접지시스템의 성능에 미치는 영향에 대한 고려가 필요하다.

접지그리드의 접지임피던스 측정 기법 (Measurement method of ground impedance for the grounding grid)

  • 이복희;최종혁;최영철;유재덕;백영환;김동성;신희경;유양우
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2009년도 제40회 하계학술대회
    • /
    • pp.1487_1488
    • /
    • 2009
  • In these days, the common grounding systems are adapted in most large structures. In order to evaluate the performance of grounding system, it is needed to measure ground impedance. Measuring methods of ground impedance for a large scale grounding systems have not been yet presented in detail. In this paper, we analyze earth mutual resistance and mutual coupling of $15{\times}15m$ grounding grid in different arrangements of auxiliary electrode. As a results, the auxiliary electrodes are installed where the error rate due to earth mutual resistance is less than 5%. Also, the potential lead is installed at obtuse angle from the current lead and the overlapped length between potential lead and grounding grid are minimized.

  • PDF

각판상전극의 접지저항에 관한 연구 (Research on Grounding Resistance for the Grounding Plate Electrodes)

  • 고희석;신수한;김주찬;최종규
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2004년도 학술대회 논문집
    • /
    • pp.111-114
    • /
    • 2004
  • There are many electricity, electronics, and communication equipment which need to Grounding in the building. When electric current flows into a certain Grounding system in the same building, the potential of other Grounding system rises. This potential interference repuire surface potential of electrods by electrode shape. In this paper basic formula is deduced on the basis of both electrodes surface potential of Grounding electrode as a source of the potential interference and Grounding electrode which receive the potential interference. The degree of potential interference as multiple Grounding electrode is verified the simulated results by means of the simple model in advance.

  • PDF

매설지선의 임펄스임피던스의 해석 (Analysis for the impulsive impedance of counterpoise)

  • 조정현;김종호;백영환;김동성;이강수;김기복;이복희
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2009년도 춘계학술대회 논문집
    • /
    • pp.88-91
    • /
    • 2009
  • For lightning currents, a grounding system shows the transient grounding impedance characteristics. A grounding system for protection against lightning should be evaluated by the transient grounding impedance, not it's ground resistance. The transient grounding impedance varies with the shape of ground electrode and earth characteristics as well as the waveform of lightning surge current. For the analysis and practical use of transient grounding impedance, the characteristics of transient grounding impedance should be analyzed theoretically and this paper suggests the theoretical analysis for the transient grounding impedance of counterpoise by using the distributed parameter circuit model. EMTP and Matlab are used to simulate the distributed parameter circuit model of counterpoise and the adequacy of the distributed parameter model of counterpoise is examined by comparing the simulated results with the measured results.

  • PDF

접지그리드의 접지임피던스 측정의 정확도 평가 (Evaluation of the Accuracy of Grounding Impedance Measurement of Grounding Grid)

  • 최종혁;최영철;정동철;김동성;이복희
    • 조명전기설비학회논문지
    • /
    • 제23권12호
    • /
    • pp.146-153
    • /
    • 2009
  • 최근 대형 건축물들은 접지그리드를 기반으로 한 공통접지방식을 채택하고 있다. 이러한 접지시스템의 성능평가는 접지저항만으로 불충분하므로 접지임피던스의 측정이 요구된다. 대형 접지시스템의 접지임피던스에 대한 측정 방법은 IEEE standard 81.2에 기술되었으나 세부적인 평가방법들은 제시되지 못한 상태이다. 본 논문은 15[m]$\times$15[m] 접지그리드에 대하여 수정된 전위강하법에 기반한 접지임피던스의 정확한 측정방법과 보조전극의 위치에 따른 도전유도 및 전자유도에 의한 측정오차를 기술한다. 그 결과 도전유도에 의한 오차는 보조전극의 거리가 늘어날수록 감소하였다. 전자유도에 의한 오차를 배제하기 위해서 전위측정선은 전류측정선과 90도를 이루어야 한다. 전위측정선과 전류측정선이 예각 또는 둔각을 이루었을 때 전자유도전압은 각각 + 또는 -를 나타내었다. 일반적으로 전자유도에 의한 오차는 예각에 비해서 둔각의 경로가 작게 나타났다.