• Title/Summary/Keyword: grounding resistance

Search Result 246, Processing Time 0.033 seconds

Measurement of Grounding Impedances in Large-scale Grounding Electrode Systems (대형접지전극시스템 접지임피던스의 측정)

  • Lee, Kyoung-Hoon;Choi, Jong-Hyuk;Choi, Young-Chul;Lee, Kyu-Sun;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.10a
    • /
    • pp.193-196
    • /
    • 2008
  • In these days, large structures are constructed and bonded with ground grid Because the distances between mesh and auxiliary electrodes are not enough in downtown areas, it is very difficult to measure the ground resistance of large scale grounding electrode systems. Actually the auxiliary electrodes for test are installed in grounding grid. This paper present the experimental results of ground resistance and impedance according to the location of auxiliary electrode. As a result, we get much lower resistances and impedances than real values the auxiliary electrodes are placed in the ground grid. In case that the auxiliary electrodes are located in the ground grid the resistances are very low and reactance only is inductive component.

  • PDF

Transient Grounding Impedance Characteristic Analysis of a Copper Rod-type Grounding Electrode Used for Electric Distribution Systems Using MATLAB Program (MATLAB 프로그램을 이용한 배전계통에 사용되는 동봉 접지전극의 과도 접지임피던스 특성 분석)

  • Kim, Kyung-Chul;Oh, Kyung-Hoon;Lee, Kyu-Jin;Shim, Keun-Bo;Choi, Jong-Kee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.9
    • /
    • pp.40-46
    • /
    • 2009
  • Although a ground resistance is a good index of grounding performance for grounding electrodes, it does not reflect the grounding performance during transient state. A copper rod electrode is the most commonly used grounding electrode in electric distribution systems. In this paper, the grounding impedance of copper rods has been measured in frequency raging from 60[Hz] up to 100[kHz] and an equivalent model of the grounding impedance is identified from the measured values. The grounding impedance under study when a typical lightning surge is injected into the grounding system was simulated numerically and graphically through the use of the MATLAB software program.

A Study on Transient Grounding Performance of Ground Rods

  • Yun Dong-Hyeon;Lee Hyeong-Su;Lee Gwan Hyeong
    • Proceedings of the Korean Institute of Industrial Safety Conference
    • /
    • 2002.11a
    • /
    • pp.281-285
    • /
    • 2002
  • Although DC ground resistance is a good index of performance for a grounding system, it does not reflect the grounding performance during the transient states. Besides, impulse ground impedance, which is defined by a ratio of the peak value of transient ground potential rise to the peak value of impulse current, cannot be an absolute performance index due to its dependence on impulse current shape. In this paper, a grounding performance of needle-typed ground rod has been compared with simple ground rod using HIFREQ[1], which is an engineering electro-magnetic code based on MoM (Method of Moment).

  • PDF

Research on Standards for Protection against Electric Shock in Global Technical Regulations of Fuel Cell Vehicle (연료전지 자동차 세계기술규정의 감전보호기준 연구)

  • HwangBo, Cheon;Lee, Kyu-Myong;You, Kyeong-Jun
    • Transactions of the Korean hydrogen and new energy society
    • /
    • v.21 no.3
    • /
    • pp.167-183
    • /
    • 2010
  • This paper analyzes the backgrounds of the standards for protection against electric shock in Global Technical Regulations (GTR) of Fuel Cell Vehicle (FCV). Targets on research were high voltage criteria, safety current, isolation and grounding resistance, time limitation, energy, adequate clearance, and test procedure. Based on human impedance and effect of current in IEC 60479-1, safety of human was examined. Then, isolation and grounding circuit model of FCV were analyzed theoretically. The results give several suggestions: touch voltage less than 25V, AC energy less than 0.0813J, separation considering middle finger length, grounding resistance less than $0.2\Omega$, maximum AC ground voltage of 1V (rms), and isolation resistance between earth and electrical chassis. In MATLAB/Simulink environment, error characteristics of isolation resistance measurement procedure using internal DC sources were analyzed under variations of internal resistance of voltmeter and isolation resistance.

The Measurement of the Grounding Resistance Using the Ground Current of the Distribution System (접지선 전류를 시험 전류원으로 활용한 접지저항 측정기법에 관한 연구)

  • Kang, Moon-Ho
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.11a
    • /
    • pp.293-295
    • /
    • 2004
  • Public utilities adopt the grounding rules ; class I, class II, class III and special class III, and install the grounding electrodes in distribution facilities. To keep the safety of the human and the facilities, Public utilities also manage the value of ground resistance in distribution system biennially. At present the Hook-On meter is normally used to measure the ground resistance although it has ${\pm}5[%]$ measuring error and it can not measure the exact value when the current is over 1[A]. In addition it is very difficult to use the fall-of-potential method in distribution system. In this paper we propose the new measurement method using ground current of distribution system as the current source.

  • PDF

Analysis of Grounding resistance reduction effect of Transmission tower (가공송전선로의 철탑 접지저항 저감효과 분석)

  • Min, Byeong-Wook;Kim, Tai-Young;Park, Bong-Gyu;Choi, Jin-Sung;Kang, Yeon-Woog;Park, Kwang-Uk;Bae, Hyun-Kwon
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.453-454
    • /
    • 2011
  • With the transmission line the ratio of lightning breakdown the while whole breaking down is occupying a high share with average 72%, is a tendency which increases continuously. In order decreasing the back flashover faults from like this lightning breakdown, it is very important to maintain grounding resistance of tower below target. In this paper, we synthetically analyzed the grounding resistance reduction effect of tower foundation and standard ground connection from construction site, and investigated efficiency for ways to increase the length of counter poise and expand the size of conductivity concrete materials.

  • PDF

A Study On the Impulse Response Behavior of Ground Rods in Power Distribution System (22.9kV-Y 다중접지 배전계통 접지극의 임펄스 응답 특성 실증연구)

  • Kang, Moon-Ho;Jang, Sang-Ok;Park, Sang-Man;Ha, Dong-Hyuk;Lee, Heung-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1858-1860
    • /
    • 2003
  • Ground rods as the discharge path are commonly installed to ensure the safety of human beings and facilities from the surge. Accordingly, proper grounding resistance are specified by the grounding types, and the specified resistance are also required to install the lightning protective facilities. it is needed to analyze the difference between these two resistance through the field test. Therefore, in this paper, the impulse response behavior of the ground rods is analyzed by constructing the test facilities and by testing the ground rods in multi-ground power distribution systems. The impulse responses were analyzed, in transient state, by testing the concrete poles as well since the grounding wires are installed in the concrete poles.

  • PDF

Measurement and Analysis of the Dangerous Voltage Around Grounding Electrode for Safety in Substation Ground (변전소 접지설계를 위한 접지전극 주변의 위험전압 측정과 분석)

  • Son, Seok-Geum;Kim, Jae-Chul
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.60 no.4
    • /
    • pp.214-219
    • /
    • 2011
  • The substation grounding design,"IEEE Guide for Safety in AC Substation Grounding (ANSI / IEEE Std 80)"has been widely used. Substation grounding design and substation grounding resistance of grounding network site to predict the voltage at the risk of a very important task, which is a ground fault current due to the influx of the ground network and due to rise in the Earth's potential can be applied to human dangerous Voltage within safe tolerances be configured to be the ground because the network. IEEE Std. 80 for the substation construction safety equipment on the ground securing the ground electrode and the mesh around the boundary potential distribution in terms of risk analysis by the touch voltage and the reference was to clean up the definition and the basic steps of the voltage of the voltage limits the risk of peripheral grounding electrode Suppression by the simulator through a new secure from dangerous voltage design techniques were presented.

According to The changing of the grounding design source, The changes in the Diagonal mesh grounding (접지제원 변화에 따른 사선 메쉬접지의 특성변화)

  • Kim, Tae-Hoon;Choi, Hong-Kyoo;Hong, Soon-Suk;Song, Young-Joo;Shim, Yong-Sik
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2009.10a
    • /
    • pp.347-350
    • /
    • 2009
  • The latticed mesh grounding is compared with the diagonal mesh grounding. In the result, The latticed mesh grounding better than the diagonal mesh grounding at the maximum touch voltage, the grounding resistance and the total length of conductors.

  • PDF

Frequency Characteristics of Grounding Impedances of the Deeply-driven Ground Rods (심매설 접지전극에 대한 접지임피던스의 주파수특성)

  • Kang, Sung-Man;Kim, Tae-Ki;Kim, Han-Soo;Lee, Bok-Hee
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.1348-1349
    • /
    • 2008
  • Grounding impedance depends on the frequency of current flowing into a grounding system. Especially, the lightning gives a broad frequency spectrum from low frequency up to 1 MHz. So the grounding impedance related to high frequency current like lightning should be measured with high frequency source. In this paper, we described the grounding impedances of deeply-driven ground rods of 10 $\sim$ 48 m long with respect to the frequency of injected currents. For the experiments, we used the wideband power amplifier which can produce sinusoidal voltages with the frequency ranges of DC $\sim$ 250 MHz. As a result, the longer the ground rod is, the lower the ground resistance is. However the grounding impedance of deeply-driven ground rod in the range of higher frequency is significantly increased. As a consequence, it is important to evaluate the high frequency performance of grounding systems for lightning protection.

  • PDF