Comparison of Theoretical Resu Its and Measured Data Using Hemispherical Water Tank Model for Potential Rise of Structure Grounding (구조체 접지의 전위상승에 대한 반구형 수조에 의한 측정값과 계산값의 비교)

  • Gil, Hyoung-Jun;Choi, Chung-Seog;Kim, Hyang-Kon;Han, Woon-Ki;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2005.11a
    • /
    • pp.111-114
    • /
    • 2005
  • This paper presents a comparison of experimental value by hemispherical grounding simulation system and calculated value by CDEGS program for ground potential rise of structure. When a test current flowed through structure grounding electrodes, ground potential rise was measured and analyzed for types of structure using the hemispherical grounding simulation system in real time, and was computed by means of CDEGS program. The model structures were designed and fabricated with two types on a scale of one-one hundred sixty. When the experimental data were compared with the theoretical values, the similar profile was shown. Therefore, the confidence of measurement was obtained. The distributions of ground surface potential are dependent on the resistivity and absorption percentage in concrete attached to structure.

  • PDF

Analysis on the Method of Forward-Reverse Fault localization of Electric Railways for the Improvement of Accuracy (전기철도 정역방향 고장점표정 방법을 통한 정확도 향상을 위한 연구)

  • Kim, Myeong Su;Kim, Seong Cheol
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.67 no.12
    • /
    • pp.1735-1742
    • /
    • 2018
  • The number of electric railway failures will increase due to the external and internal effects of electric railroads. The grounding test with 25,000V is to artificially test the transmission voltage to ground, and it is possible to cause risks of electric shock and other equipment insulation damage in neighboring enclosure. In 2016, method of fault localization changed to low - voltage at 380V from artificially high- voltage in the grounding tests since opening of Seoul Metropolitan Express Railway; The method is more accurate and safer rather than the previous one because it gets more data from unlimited grounding tests. However, an electric current falls on the track section where the track branches and vehicle bases with many lines. To precisely detect a transitive phenomenon, it is necessary to continuously study and additionally install.

Study for the Grounding Resistance of the Mesh Grounding Electrode by Water Tank Model (수조모델을 이용한 메쉬접지극의 접지저항에 관한 연구)

  • Kim, Ju-Chan;Kim, Sung-Sam;Choi, Jong-Gyu;Lee, Chung-Sik;Koh, Hee-Seog
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.3
    • /
    • pp.28-35
    • /
    • 2006
  • Recently, a number of equipments related with electricity, electronics, and communication in the same building are needed to the grounding system for safety from unexpected accidents. When the faulted electric current flows into a certain grounding system, the potential rise in that system takes place and it might induce the potential rise to other grounding system. This potential interference was strongly affected by the surface potential, which was deeply related with the electrode shape. In this paper, the fundamental formula was deduced on the basis of surface potential of two grounding electrodes. Which corresponds to source of the potential interference and other grounding electrode, respectively. Therefore, the degree of potential interference in this mesh grounding electrode system was verified by the simple model simulation. In addition, in order to identify the difference between the grounding resistance in the realistic construction site and the expected value from the corresponding simulation, the experiment was performed with model on a reduced scale about the realistic grounding system. It consists of stainless steel hemisphere electrodes in a water tank. From this work, the grounding resistance in the mesh grounding electrode showed the good coincidence results between those. Consequently, it is confirmed that the grounding resistance in the mesh electrode is possible to be estimated by performing the experiment using the water tank model.

Analysis on the Protective Coordination with Hybrid Superconducting Fault Current Limiter (저항접지 시스템에서 지락사고시 CLR과열 소손방지를 위한 GPT 정격용량의 적정성 연구)

  • Shin, Ho-Jeon;Kim, Jin-Seok;Park, Yu-Hwan;Kim, Jae-Chul;Cho, Man-Young
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.4
    • /
    • pp.503-508
    • /
    • 2012
  • Among the high distribution voltage consumers, high-capacity consumers are often applying the grounding resistance method in order to overcome demerits such as erroneous operation of the ground reply or potential increase in the battery at the accident of the isolated neutral system. In this paper, to prevent damage to CLR and GPT in the delay to block the breakdown in the resistance grounded neutral system, this study aims to provide a proper suggestion for continuous rating capacity of GPT to check the appropriateness of CLR size and reduce GPT burden. Thereupon, this study comparatively analyzes CLR current applied in general GPT and the current gained when CLR demanded in the system is used and analyzes the simulated system through simulation using PSCAD/EMTDC in order to suggest GPT's proper continuous rating capacity.

Characteristics of Fault Current Division Factor & Groud Potential Rise of a Substation fed exclusively by Power Cables (지중케이블 변전소의 고장전류 분류율과 접지전위상승 특성)

  • Choi, Jong-Kee;Jung, Gil-Jo;Kim, Seon-Gu
    • Proceedings of the KIEE Conference
    • /
    • 1998.11a
    • /
    • pp.295-297
    • /
    • 1998
  • This paper shows characteristics of fault current division factor $S_f$, which is a ratio of earth- return current to total fault current, at a substation fed exclusively by power cables under unsymmetrical fault condition, such as single line-to-ground fault. In substation grounding system design, $S_f$ is a very important factor determining GPR, touch and step voltage at a substation under fault condition. In case of substations fed by overhead lines, 40-60% of $S_f$ has been typically used, although it is a very conservative value with no other network conditions considered. It is authors' hope that $S_f$ presented in this paper could hopefully be a basic reference in designing of substation grounding system, especially for a substation fed exclusively by power cables.

  • PDF

Numerical Calculation for Grounding Impedance of a Horizontal Ground Electrode Based on the Electromagnetic Field Theory (전자계 이론을 기반으로 한 수평접지전극의 접지임피던스 수치계산)

  • Lee, Bok-Hee;Cho, Sung-Chul
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.28 no.2
    • /
    • pp.76-83
    • /
    • 2014
  • This paper deals with the numerical method of calculating the frequency-dependent impedances of grounding electrodes. The proposed electromagnetic field approach is based on the solutions to Maxwell's equations obtained from the method of moment in the frequency domain. In order to evaluate the quality of the proposed simulation method, the frequency-dependent impedances of horizontally-buried ground electrodes were presented. The program for calculating the current distributions and impedances of grounding electrodes was implemented in MATLAB. The grounding impedances of two 10m and 50m long horizontal ground electrodes were measured and simulated in the frequency range from 100Hz to 10MHz for easy analysis and comparison. Also the simulated results were compared with those calculated from a sophisticated computer program CDEGS (HIFREQ module). As a result, the resultant results of frequency-dependent impedances obtained by using the numerical simulation method proposed in this work are in good agreement with experimental data. The validity of the approach techniques was confirmed.

A Study on Grounding Characteristic Analysis of Large-scaled Apartment Complex Based on PSCAD/EMTDC (PSCAD/EMTDC에 의한 대규모 아파트단지의 접지특성 해석에 관한 연구)

  • Lee, Hu-Dong;Shin, Myeong-Ki;Choi, Sung-Sik;Kang, Min-Kwan;Nam, Yang-Hyun;Rho, Dae-Seok
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.18 no.12
    • /
    • pp.650-658
    • /
    • 2017
  • A grounding system in a large-scale apartment complex consists of a TT grounding system when viewed in each building unit, but the characteristics of TN grounding system appears when viewed in the total ground system function. Therefore, this study examined the characteristics of a grounding system in a large-scale apartment complex using design draft, field measurements and PSCAD/EMTDC modeling. This paper proposes an algorithm for fault analysis depending on the grounding system structure in large-scale apartment complexes considering the connection of the underground culvert as well as a design algorithm for each grounding system considering the contact voltage and step voltage. The simulation results based on the proposed modeling and algorithm confirmed that it is useful for analyzing the characteristics of a grounding system in a large-scale apartment complex.

A Study on the Integrated Monitoring of a Leakage Current of the Grounding Wire of Neutral Point of the Low Voltage Side of Transformer (변압기 저압측 중성점 접지선의 누설전류 통합 감시에 관한 연구)

  • Hong, Soon-Seuk;Park, Joon-Yeol;Lee, Jung-Eun;Choi, Kyung-Han
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.5
    • /
    • pp.106-113
    • /
    • 2010
  • If leakage current is neglected, it can become a cause for disasters such as electric shock and fire, therefore a continuous monitoring is necessary. However in most cases, because management of substations is performed by unmanned systems, or walk-around inspections, continuous monitor is difficult. So when an accident occurs and the cause is not immediately resolved causing the emergency generator's OCGR getting activated by the leakage current that in turn cut off the ACB, the emergency generator may stop working. To prevent such a problem, a real-time integrated monitoring system for monitoring the leakage current returning to the grounding wire of neutral point of the low voltage side of transformer is proposed. Therefore in this paper, the effects of flow of leakage current, which is caused by insulation degradation phenomena or insulation destroy phenomena, were identified by simulation. And through cases studies; the excellence of integrated monitoring system was verified.

A Study on Improving of Grounding Systems for Railway Signalling Equipment (철도신호설비의 접지시스템 개선에 관한 연구)

  • Park, Ki-Bum;Lee, Tae-Hoon;Ryu, Young-Tae;Jeon, Yong-Joo
    • Proceedings of the KSR Conference
    • /
    • 2008.06a
    • /
    • pp.588-595
    • /
    • 2008
  • Recently, it is caused by environment change that is increased the number of lightning occurrence and the strength of lightning current is coming to be strong little by little. The performance of grounding system depends on how to construct. Specially the common grounding systems which uses the buried earth cable must be constructed by very well qualities because it is difficult to measure earth resistance and to manage the buried earth cable. Common grounding systems and independence grounding systems could be composed different. Against railway signalling equipment which like this is used from the environment lower part which is various it presents a standard grounding systems, and very it is hard job. We will present improvement through this paper that review grounding systems configuration condition of railway signalling equipment.

  • PDF

Modeling and Implementation of Safety Test Device for Grounding System Based on IEC 60364 (IEC 60364의 접지방식에 기반한 안전성 평가 시험장치의 모델링 및 구현에 관한 연구)

  • Kim, Soon-Sik;Han, Byeong-Gill;Lee, Hu-Dong;Ferreira, Marito;Rho, Dae-Seok
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.22 no.6
    • /
    • pp.599-609
    • /
    • 2021
  • A novel grounding system, which is presented in IEC 60364, has been adopted since 2021. A safety evaluation for the human body on the grounding system is required due to the various characteristics of the touch voltage and current passing when the human body experiences an electric shock. The Korea Electrical Safety Corporation (KESCO) and Korea Electric Association (KEA) have been conducting a safety technical education on the grounding system. On the other hand, it is difficult to instruct the electrical safety manager because of a lack of safety evaluations for the test equipment on the grounding system. Therefore, this paper modeled and implemented a test device for a safety evaluation depending on the grounding system of IEC 60364. Namely, this paper presents the modeling of the test device for a safety evaluation using PSCAD/EMTDC S/W, which is composed of an AC grid section, s test device section on the grounding system, and a sub-device section. This paper implemented a test device for safety evaluation, which consisted of an AC grid section, TT grounding system section, TN-S grounding system section, and monitoring section. From the simulation and test results with the safety characteristics of the human body in the TT and TN-S grounding system, when the fault impedances are 0[Ω], 10[Ω], and 100[Ω], the currents passing through the human body in the TT grounding system are 104[mA], 87.4[mA], and 35.5[mA], respectively. The corresponding currents in the TN-S grounding system are 54.9[mA], 4.1[mA], and 0.4[mA], respectively. Based on the results, the protection performance for an electric shock to the human body in the TN-S system is better than the TT system. This can be improved when the existing grounding system is changed from the TT system to the TN-S system.