• Title/Summary/Keyword: flux-lock type SFCL

Search Result 96, Processing Time 0.03 seconds

Comparison of Characteristics on the Flux-Lock and the Transformer Type SFCLs with Three Superconducting Units (3개의 초전도 소자를 갖는 자속구속형 SFCL과 변압기형 SFCL의 특성 비교)

  • Lee, Ju-Hyoung;Choi, Hyo-Sang
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.58 no.1
    • /
    • pp.79-84
    • /
    • 2009
  • In order to increase the capacity of the superconducting fault current limiter(SFCL), the current and voltage grades of the SFCL must be increased. As a method for the increase of the current and voltage grades of the SFCL, we compared the various characteristics between the flux-lock type SFCL "With three superconducting units connected in series and the transformer type SFCL using the transformer with three secondary circuits. One of three superconducting units had not quenched in the flux-lock type SFCL. Therefore, the unbalanced power burden happened because of the voltage difference generated by unbalanced quenching between the superconducting units. In the meantime, the three superconducting units were all quenched in the transformer type SFCL using the transformer, and the voltage difference generated between the superconducting units was decreased. Therefore, the difference of critical characteristics was complemented by distribution of fault current in accordance with the turn's ratio between primary and secondary windings. The unbalanced power burden of the superconducting units was reduced due to flux-share between the superconducting units in the transformer. In conclusion, the capacity increment of the SFCL using a transformer was easier due to equal distribution of voltages generated by simultaneous quench of the superconducting units. We think that the characteristics is improved more because of the decrease of saturation in the iron core if the secondary winding is increased in the SFCL using the transformer.

Analysis of fault Current Limiting Characteristics due to Ratio of Inductances between Coil 1 and coil 2 in a Flux-lock Type SFCL (자속구속형 고온초전도 전류제한기의 인덕턴스 변화에 따른 전류제한 특성 분석)

  • Park, Chung-Ryul;Lim, Sung-Hun;Park, Hyoung-Min;Choi, Hyo-Sang;Han, Byoung-Sung
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.18 no.9
    • /
    • pp.856-862
    • /
    • 2005
  • A flux-lock type SFCL consists of two coils, which are wound in parallel each other through an iron core, and a HTSC thin film connected in series with coil 2. If the current of the HTSC thin film exceeds its critical current by the fault accident, the resistance generated of the HTSC thin film, and thereby the fault current can be limited by the impedance of the flux-lock type SFCL. The amplitude of fault current can be set by the impedance of the flux-lock type SFCL. In this paper, we investigated the variance of the limiting current due to the ratio of inductances between coil 1 and coil 2 in the flux-lock type SFCL through the computer simulations and short circuit tests. In addition, both the simulation results and experimental ones were compared each other. From the comparison of both the results, the simulation results agreed well with the experimental ones.

Transient Current Limiting Characteristics of Flux-Lock Type SFCL Using Double Quench (이중퀜치를 이용한 자속구속형 초전도한류기의 과도전류제한 특성)

  • Choi, Sang-Jae;Lim, Sung-Hun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.30 no.2
    • /
    • pp.96-100
    • /
    • 2017
  • In this paper, the flux-lock type superconducting fault current limiter (SFCL) using double quench was suggested and its transient current limiting characteristics were analyzed. The suggested flux-lock type SFCL using double quench consists of two magnetically coupled windings and two $high-T_{c}$ superconducting (HTSC) elements connected in series with each winding. To analyze the transient current limiting characteristics of the flux-lock type SFCL using double quench, the short-circuit tests according to the fault angles, which affect the transient component of the fault current right after the fault occurs, were executed. From the comparative analysis for the short-circuit tests at both $0^{\circ}$ and $90^{\circ}$ fault angles, the useful transient current limiting operations of the suggested flux-lock type SFCL through the double or the single quench occurrence were confirmed.

Simulation of Operational Characteristics in Integrated Three-Phase Flux-Lock Type SFCL (3상 일체화된 자속구속형 고온초전도 전류제한기의 동작특성 시뮬레이션)

  • Lim, Sung-Hun;Park, Chung-Ryul;Han, Byoung-Sung;Park, Hyoung-Min;Cho, Yong-Sun;Choi, Hyo-Sang
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2005.11a
    • /
    • pp.167-168
    • /
    • 2005
  • The operational characteristics of the integrated three-phase flux-lock type superconducting fault current limiter (SFCL) were analyzed. The suggested three-phase SFCL consisted of a three-phase flux-lock reactor and three high-Tc superconducting (HTSC) elements. The former has three windings wound on an iron core, each of which has the same turn's ratio between coil 1 and coil 2. The latter are connected in series with coil 2 of each phase. The integrated three-phase flux-lock type SFCL showed the operational characteristics that the fault phase could affect the sound phase, which resulted in quenching the HTSC element in the sound phase. Through the computer simulation applying numerical analysis for its three-phase equivalent circuit, the fault current limiting characteristics of the integrated three-phase flux-lock type SFCL according to the ground fault types were compared.

  • PDF

Operational Characteristics in Integrated Three-Phase Flux-Lock Type SFCL (3상 일체화된 자속구속형 고온초전도 전류제한기의 동작특성)

  • Lim, Sung-Hun;Han, Tae-Hee;Park, Hyoung-Min;Cho, Yong-Sun;Song, Jae-Joo;Choi, Myoung-Ho;Hwang, Jong-Sun;Choi, Hyo-Sang;Han, Byoung-Sung
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2006.12a
    • /
    • pp.112-113
    • /
    • 2006
  • The operational characteristics of the integrated three-phase flux-lock type superconducting fault current limiter (SFCL) were analyzed. The suggested three-phase SFCL consisted of a three-phase flux-lock reactor and three high-$T_c$ superconducting (HTSC) elements. The former has three windings wound on an iron core, each of which has the same turn's ratio between coil 1 and coil 2. The latter are connected in series with coil 2 of each phase. The integrated three-phase flux-lock type SFCL showed the operational characteristics that the fault phase could affect the sound phase, which resulted in quenching the HTSC element in the sound phase. Through the computer simulation applying numerical analysis for its three-phase equivalent circuit, the fault current limiting characteristics of the integrated three-phase flux-lock type SFCL according to the ground fault types were compared.

  • PDF

Recovery Characteristic of Flux-Lock Type SFCL (자속구속형 초전도 사고전류제한기의 회복특성)

  • Lim, Sung-Hun;Han, Tae-Hee;Park, Hyoung-Min;Cho, Yong-Sun;Song, Jae-Joo;Choi, Myoung-Ho;Hwang, Jong-Sun;Choi, Hyo-Sang;Han, Byoung-Sung
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2006.11a
    • /
    • pp.188-189
    • /
    • 2006
  • The flux-lock type superconducting fault current limiter (SFCL) has the attractive characteristics that can adjust the current limiting level by the turns ratio and the winding direction of two coils. To apply this type SFCL into power system, the analysis for the recovery characteristics of it together with the current limiting characteristic is needed. In this paper, the experiments of the current limiting and the recovery characteristics of the flux-lock type SFCL with YBCO thin film were performed. The recovery characteristics of the flux-lock type SFCL dependent on the winding direction of two coils were analyzed through the comparison with the resistive type SFCL.

  • PDF

Analysis on Fault Current Limiting Characteristics According to Peak Current Limiting Setting of a Flux-Lock Type SFCL with Peak Current Limiting Function (피크전류제한 설정에 따른 피크전류제한 기능을 갖는 자속구속형 초전도한류기의 고장전류제한 특성 분석)

  • Ko, Seok-Cheol
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.12
    • /
    • pp.68-73
    • /
    • 2012
  • In this paper, the fault current limiting characteristics of a flux-lock type superconducting fault current limiter (SFCL) with peak current limiting function were analyzed through its short-circuit tests. The setting condition for the peak current limiting operation was derived from its electrical equivalent circuit, which was dependent on the inductance ratio between the third coil and the first coil. Through the analysis on the short-circuit tests for the flux-lock type SFCLs with the different inductance ratio between the third coil and the first coil, the setting value for the peak current limiting operation of the flux-lock type SFCL with peak current limiting function could be confirmed to be adjusted with the variation of the inductance ratio between the third coil and the first coil.

Analysis for Magnetic field generated in the Flux-Lock Type Reactor using HTSC during a fault time (고온초전도체를 이용한 자속구속 리액터의 사고시 발생되는 자계 분석)

  • Lim, Sung-Hun;Choi, Hyo-Sang;Kang, Hyeong-Gon;Ko, Seok-Cheol;Lee, Jong-Hwa;Choi, Myung-Ho;Song, Jae-Joo;Han, Byoung-Sung
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.07a
    • /
    • pp.601-604
    • /
    • 2003
  • The magnetic field generated in the iron core, which is required for the magnetic field to link each coil of the flux-lock type reactor, affects the fault current limiting characteristics of the flux-lock type high-Tc superconducting fault current limiter(SFCL). By applying numerical analysis for equivalent circuit of flux-lock type SFCL, the magnetic field induced in the iron core including currents of each coil was investigated. Through the analysis of magnetic field, we have analyzed that the magnetic field linked the 3rd coil, which is wound in the iron core, prevents the saturation of the iron core, but decreases the impedance of the flux-lock type SFCL.

  • PDF

Current Limiting Characteristics of flux-lock Type High-lc Superconducting Fault Current Limiter According to fault Angles (사고각에 따른 자속구속형 전류제한기의 전류제한특성)

  • Park, Hyoung-Min;Choi, Hyo-Sang;Cho, Yong-Sun;Lim, Sung-Hun;Park, Chung-Ryul;Han, Byoung-Sung
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.18 no.8
    • /
    • pp.747-753
    • /
    • 2005
  • We Investigated the current limiting characteristics of the flux-lock type superconducting fault current limiter(SFCL) by fault angles. The flux-lock type SFCL consists of the primary and the secondary copper coils wound in parallel through the iron core and YBCO thin film. In this paper, the current limiting characteristics of the flux-lock type SFCL by fault angles in case of the subtractive and the additive polarity windings were compared and analyzed. The flux-lock type SFCL limited fault current more quickly as the fault angles increased. On the other hand, the initial power burden of the superconducting element during the fault increased as the fault angles increased. In addition, we found that the resistance of the flux-lock type SFCL in case of the subtractive polarity winding was more increased than that of the additive polarity winding. The peak current of the fault current in case of the subtractive polarity winding was larger than that of the additive polarity winding.

Quench Characteristics of Flux-Lock Type Superconducting Fault Current Limiter According to The Number of YBCO (YBCO의 직렬연결에 따른 자속구속형 초전도 한류기의 퀜치특성)

  • Lee Sang-Il;Park Hyoung-Min;Choi Hyo-Sang
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.55 no.8
    • /
    • pp.329-333
    • /
    • 2006
  • We investigated the quench characteristics of a flux-lock type superconducting fault current limiter (SFCL) depending on the number of the serial connection between the superconducting elements at the subtractive polarity winding of a transformer. The flux-lock type SFCL consists of two coils. The primary coil is wound in parallel to the secondary coil through an iron core, and the secondary coil is connected to the superconducting elements in series. The operation of the flux-lock type SFCL can be divided into the subtractive and the additive polarity windings depending on the winding directions between the primary and secondary coils. In this paper, the analyses of voltage, current, and resistance of superconducting elements in serial connection were performed to increase the power capacity of flux-lock type SFCL. The power burden was reduced through the simultaneous quenching between the superconducting elements. This enabled the flux-lock type SFCL to be easy to increase the capacity of power system.