• Title/Summary/Keyword: flammable liquid fire

Search Result 67, Processing Time 0.026 seconds

A Study on Combustion Patterns of Flammable Liquids by Contained Oil Test (담유 실험에 의한 인화성 액체의 연소 패턴 해석에 관한 연구)

  • Joe, Hi-Su;Choi, Chung-Seog
    • Fire Science and Engineering
    • /
    • v.28 no.4
    • /
    • pp.14-20
    • /
    • 2014
  • The purpose of this study is to analyze combustion patterns by filling a specific container with a flammable liquid and performing combustion tests in a divided space. The container used for the test is made of plastic, 20 mm in depth and 150 mm in width. After the liquid was ignited, its combustion process was photographed using a digital camera and video camera. It was found that in the case of benzene, the flame reached its peak at the fastest speed about 60 s while in the case of alcohol, the flame reached its peak at the lowest speed about 360 s, which is approximately six times slower than the benzene. In most cases, when the flame reached its peak, smoke generated was dark as the plastic container and flammable liquid were combusted simultaneously. After completion of the combustion, it was possible to sample oil vapor from all flammable liquids excluding soybean oil as a result of the examination of oil vapor using a crime investigation tube. That is, it can be seen that there is significant difference in flame propagation speed, pattern, etc., depending on the combustible substances.

A Study on Flash Points and Fire Points of Acids Using Closed Cup and Open-cup Apparatus (밀폐식과 개방식 장치를 이용한 Acid류의 인화점과 연소점에 관한 연구)

  • Ha, Dong-Myeong;Han, Jong-Geun;Lee, Sung-Jin
    • Fire Science and Engineering
    • /
    • v.20 no.3 s.63
    • /
    • pp.29-34
    • /
    • 2006
  • The flash and fire point are the most important combustible properties used to determine the potential for the fire and explosion hazards of flammable material. The flash point is defined as the lowest temperature at which a flammable liquid gives off sufficient vapor to form an ignitable mixture with air near its surface or within a vessel. The fire point is the temperature of the flammable liquid at which there will be flaming combustion, sustained 5 seconds in response to the pilot flame. In this study, the flash points and fire points were measured to present raw data of the flammable risk assessment for acids, using Pensky-Martens Closed Cup(C.C.) apparatus (ASTM-D93) and Tag Open-cup (O.C.) apparatus(ASTM D 1310-86). The measured fire points were compared with the estimated values based on 1.11 times stoichiometric concentration. The values calculated by the proposed equation were in good agreement with measured values.

Optical Properties for Smoke Particles of Fire Sources According to UL 268 (UL 268 화원에 의한 연기입자의 광학적 특성)

  • Jee, Seung-Wook;Lee, Jong-Hwa
    • Fire Science and Engineering
    • /
    • v.28 no.2
    • /
    • pp.9-13
    • /
    • 2014
  • This paper is basic study for development of the photoelectric-type smoke detector that is able to distinguish fire source as well as fire detection. For this subject, Light source and sensor which is normally used for the conventional smoke detector are assembled for the optical chamber. Using 3 type of the test fires (the paper fire, the wood fire, the flammable liquid fire) this paper attempts to find optical properties of each fire. These 3 type of fire are used in the testing of smoke detector according to UL 268 standard. As the result, there are disambiguated between the paper fire and the wood fire in scattering and reason of extinction in the flammable liquid fire is different from that of the paper and the wood fire.

A Study on Prevention of Fire Accidents by Splash Filling in the Filtration Process of Pharmaceutical Companies (제약회사 여과 공정중 스플래쉬 필링에 의한 화재사고 예방대책에 관한 연구)

  • Kim, Sang Gil;Lee, Dae Joon;Yang, Seung Bok;Rhim, Jong Guk
    • Journal of the Korean Institute of Gas
    • /
    • v.25 no.6
    • /
    • pp.29-34
    • /
    • 2021
  • Flammable substances are often present in the raw materials of pharmaceutical products manufactured by pharmaceutical companies. In this case, an excessive amount of flammable substances is added to make an intermediate, and flammable substances that do not participate in the reaction are removed through filtration and drying steps. In addition, the flammable liquid separated in the filtration process is accumulated in the form of splash filling in the filtrate container. In this case, vapor and mist of flammable liquid are generated, which lowers the lower limit of explosion and minimum ignition energy, and increases the risk of fire and explosion due to complex charging. In this study, by analyzing fire accidents that occurred during the recent filtration process of pharmaceutical companies, it is proposed to prevent static electricity accumulation by measures of nitrogen supply facilities, capacity improvement, conductive filter fabric and so on.

Measurement of Fire Point and Flash Point for Alcohols Using Tag Open-Cup Apparatus (Tag식 개방계 장치를 이용한 알콜류의 인화점 및 연소점 측정)

  • Ha Dong-Myeong;Lee Sung-Jin;Song Young-Ho
    • Journal of the Korean Society of Safety
    • /
    • v.19 no.4 s.68
    • /
    • pp.69-73
    • /
    • 2004
  • The flash point is one of the most important combustible properties used to determine the potential for the fire and explosion hazards of industrial material and the fire point is the temperature of the flammable liquid at which there will be flaming combustion, sustained 5 seconds in response to the pilot flame. In this study, the flash point and fire point were measured to present raw data of the flammable risk assessment for alcohols, using Tag open-cup apparatus(ASTM D 1310-86). The measured values were compared with the calculated values based on 0.78 times stoichiometric concentration. The values calculated by the proposed equations were in good agreement with the measured values.

The Effect of the Change of Wind Velocity on the Classification of Explosion Hazardous Area (폭발위험장소 선정 시 풍속 변화에 관한 연구)

  • Kwon, Yong-Joong;Kim, Dong-Joon
    • Korean Journal of Hazardous Materials
    • /
    • v.6 no.2
    • /
    • pp.62-67
    • /
    • 2018
  • It is very important to classify explosion hazardous area in order to prevent an accident explosion. In order to prevent such a explosion, the Industrial Safety and Health Standards Rules stipulates the establishment and management of explosion hazards in accordance with the criteria set by the Korean Industrial Standards. This study has investigated the range of the explosion hazardous area according to various hole sizes, pressures, vapor densities, and wind velocities in the outdoor flammable liquid tank using KS C IEC-60079-10-1 $2^{nd}$ Ed.(=IEC CODE) and PHAST. The results show that the explosion hazardous areas by IEC CODE have circle shapes. However, the areas by PHAST show ellipse shapes. The different of the explosion hazardous areas increases with the increase of wind velocity.

Analysis of Risk Assessment Factors for Gas leakage and Dispersion in Underground Power Plant (지하복합발전플랜트 내의 가스 누출 및 확산에 의한 위험성 평가 인자 분석)

  • Choi, Jinwook;Li, Longnan;Park, Jaeyong;Sung, Kunhyuk;Lee, Seonghyuk;Kim, Daejoong
    • Journal of ILASS-Korea
    • /
    • v.20 no.2
    • /
    • pp.101-106
    • /
    • 2015
  • Gas leakage and dispersion in the underground LNG power plant can lead to serious fire and explosion accident. In this study, computational fluid dynamics simulation was applied to model the dynamic process of gas leakage and dispersion phenomena in a closed space. To analyze the risk assessment factor, such as the flammable volume ratio, transient simulations were carried out for different scenarios. The simulation results visualized the gas distribution with time in the closed space. The flammable volume ratio was introduced for quantitative analysis the fire/explosion probability.