• 제목/요약/키워드: fire load of underground space

검색결과 9건 처리시간 0.03초

지하상업공간의 환기계수 및 화재하중 분석 (An Analysis of the Fire Load and Ventilation Factor in Underground Commercial Space)

  • 추연희;이지희;홍원화
    • 한국주거학회논문집
    • /
    • 제17권2호
    • /
    • pp.135-142
    • /
    • 2006
  • The purpose of this study is to obtain the fire safety for underground commercial space with analysing fire loads and ventilation factors. It was adopted the investigation method of field survey with commercial uses for more confidential data. The results of this study can be summarized as follows; 1) The ventilation factor shows $0.04{\sim}0.24m^{1/2}$ and it may develop ventilation-controlled fires which have much fire hazard more than fuel-controlled fires. 2) The highest value of fire load is $158.48kg/m^2$ and appeared in footwear shop which has the value $137.35kg/m^2$ for unfixed combustibles and $21.13kg/m^2$ for fixed combustibles. 3) The average value of burning rates which mean the velocity of fire development and the fire damage range is 0.143. Therefore it is desired to decrease the combustibles of compartment and is needed the method of dispersion arrangement of goods and storage to steel cabinet and so on.

화재하중에 따른 지하생활공간의 화재성상 예측 (Prediction of the Fire Behavior According to the Fire Load in an Underground Life Space)

  • 채한식;석창목;김이성;이지희;김화중
    • 한국화재소방학회논문지
    • /
    • 제21권1호
    • /
    • pp.51-59
    • /
    • 2007
  • 본 연구에서는 대구에 위치한 G 지하생활공간을 대상으로 화재하중에 따른 화재성상을 분석하였다. 화재성상 예측시 화재온도나 화재지속시간을 좌우하는 인자인 화재하중 및 환기계수를 파악하기 위하여, 현장방문을 통하여 가연조건을 조사하고 실의 용도별 가연조건에 대하여 각 재료의 단위발열량을 이용하여 화재하중을 산정하였다. 또한, 산정된 실의 화재하중을 변수로 화재성상분석을 위한 6가지 모델의 축소실험을 행하고 화원의 시간에 따른 온도변화와 화원의 온도상승으로 인한 공간내부로의 열유동 분포를 중심으로 화재성상을 분석하였다.

지하공간의 화재하중을 고려한 슬래브 내화 가열 실험 (A Experimental Study on the slab of fire resistance considering the fire load in Underground space)

  • 강승구;김동준;이재영;原田和典;한병찬;권영진
    • 한국건축시공학회:학술대회논문집
    • /
    • 한국건축시공학회 2012년도 춘계 학술논문 발표대회
    • /
    • pp.327-329
    • /
    • 2012
  • The validity of the numerical model used in the program is established by comparing the prediction from the computer program with results from full-scale fire resistance tests. Details of fire resistance experiments carried out on reinforced concrete slab, together with results, are presented. The results obtained from experimental test indicated in that the proposed numerical model and the implemented codes are accurate and reliable.

  • PDF

지하도상가의 HVAC 구성방식에 따른 운전특성 연구 (An Experimental Study on the Operating Characteristics with HVAC Type of Shopping Center in Underground Passage)

  • 이홍철;황인주
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2007년도 동계학술발표대회 논문집
    • /
    • pp.76-81
    • /
    • 2007
  • The shopping center in underground passage increased for efficient space utilization in urban area. This study describes operation characteristics of all air type and hybrid type with local ventilation and fan coil unit fixed to ceiling. In order to compare energy saving, thermal environment and installation space, etc., integrated simulator with heat production and indoor distribution system is designed and constructed. Energy saving of the hybrid system is calculated as over 30% compared to conventional all air type. And also the results showed that humidity decreased about 6%, also indoor thermal distribution is improved as temperature variation of around $1^{\circ}C$.

  • PDF

화재하중을 고려한 대공간 제배연 용량 최적화 연구 (Optimization for Ventilation Capacity of Large Enclosure Considering Fire Load)

  • 안찬솔;김아람
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2011년도 추계학술논문발표회 논문집
    • /
    • pp.478-481
    • /
    • 2011
  • This study is intended to evaluate and optimize the characteristics of smoke spreading and the appropriateness of evacuation time extended by operation of smoke control system during fire within the underground space of the building structured in compliance with the smoke control system performance criteria from the local fire safety standard, which has been currently applied to the buildings in Korea. Using the heat release per unit weight of the combustibles, a numerical analysis both in case of smoke control system in operation and the system not in operation was carried out at the several different shopping malls. From the viewpoint of securing the evacuation time, the results were compared in an attempt to assess the appropriateness of the fire safety criteria.

  • PDF

터널 화재시 배연속도가 연소율변화에 미치는 실험적 연구 - Heptane 풀화재 경우 (An Experimental Study on the Ventilation velocity of the Variation of Burning rate in Tunnel Fires - Heptane pool fire case)

  • 유홍선;양승신
    • 한국터널지하공간학회 논문집
    • /
    • 제7권2호
    • /
    • pp.109-117
    • /
    • 2005
  • 본 연구는 터널내 화재시 배연속도가 연소율 변화에 미치는 영향을 파악하기 위하여 Froude scaling에 의해 1/20 크기로 축소한 모형화재 실험을 수행하였다. 화원으로는 4.5cm~8.5cm의 헵탄을 사용하였으며 발열량은 3.71~15.6 kW이다. 연소율은 로드셀을 이용하여 산출하였고, 연기거동을 파악하기 위하여 K형 열전대를 이용하여 온도분포를 측정하였다. 풍동은 터널 상류 한쪽부분과 연결하였고, 터널 공간의 배연속도를 제어하기 위하여 풍동의 인버터를 조정하였다. 헵탄 풀화재인 경우 배연속도가 증가할수록 충분한 산소의 공급으로 연소율은 증가하였으며, 같은 무차원 속도($\bar{V}$) 일때 화원 크기가 작아짐에 따라 연소율은 증가하였다.

  • PDF

지하공간 재실자밀도 분석 연구 (The Occupant Load Density of Underground Space)

  • 김운형;김종훈;김종성
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2013년도 추계학술대회 초록집
    • /
    • pp.83-84
    • /
    • 2013
  • 본 연구는 국내 현실적인 기준 반영을 위하여 인구 유동에 있어 출퇴근 이용자가 집중되고 상업활동이 복합된 지하상가의 유동인구를 측정하여 재실자 밀도를 분석하였다. 실측 결과, 지하역사의 연결부분은 퇴근 시간을 기점으로 하여 인원이 편중되었으며 상업시설은 11시, 14시, 17시 등 다양한 시간에 이용자가 편중되는 특성을 나타냈다. 아울러 재실자 밀도는 1.52인/$m^2$로 현재 국내 기준과는 달리 다소 높은 분포를 보여주고 있다.

  • PDF

터널 화재시 종류식 환기가 연소율 변화에 미치는 영향에 관한 실험적 연구 (An Experimental Study on the Effect of Longitudinal Ventilation on the Variation of Burning Rate in Tunnel Fires)

  • 양승신;김성찬;유홍선
    • 터널과지하공간
    • /
    • 제15권1호
    • /
    • pp.55-60
    • /
    • 2005
  • 본 연구는 터널내 화재 발생시 종류식 환기가 연소율 변화에 미치는 영향을 파악하기 위하여 Froude scaling에 의해 1/20크기로 축소한 모형화재 실험을 수행하였다. 화원으로는 $8.5cm{\sim}14.5cm$의 메탄올을 사용하였으며 발열량은 $3.57{\sim}10.95kW$이다. 연소율은 로드셀을 이용하여 산출하였고, 연기거동을 파악하기 위하여 K형 열전대를 이용하여 온도분포를 측정하였다. 풍동은 터널의 한쪽부분과 연결하였고, 터널 공간의 배연속도를 제어하기 위하여 풍동의 전압을 조절하였다. 메탄올 화재인 경우 배연속도가 증가할수록 냉각효과로 인하여 연소율은 감소하였으며, 또한 같은 무차원속도(V)일때 화원 크기가 커짐에 따라 연소율은 감소하였다.

지하공간 화재에 따른 콘크리트 손상과 내화재 적용에 대한 연구 (Research on Concrete Damage and Fireproofing Applications in Underground Fires)

  • 최순욱;장수호;강태호;이철호
    • 터널과지하공간
    • /
    • 제33권3호
    • /
    • pp.169-188
    • /
    • 2023
  • 터널에서의 화재는 지상 화재에 비해 온도상승과 최대온도가 더 높게 나타난다. 이러한 이유로 네덜란드, 독일 등 여러 나라에서는 터널에서 사용하는 별도의 화재 시간이력곡선을 제시하였다. 터널 내 화재는 단면손실과 그 배면의 역학적 특성저하와 같은 터널 라이닝의 손상을 발생시킨다. 본 연구에서는 구조물의 화재안정성 설계 개념과 스폴링에 의한 단면손실, 터널 라이닝 재료의 물리화학적 및 역학적 특성 변화, 구조물 안전을 위한 내화재, 그리고 화재손상 예측모델에 대해 살펴보았다. 화재에 대한 구조물의 안정성을 확보하기 위해서는 설계 단계에서 구조물의 종류와 화재원인을 파악하고 예상되는 단면손실과 손상범위를 확인하여 내화재를 통해 이러한 손상에 대비하는 작업이 요구된다. 본 연구에서는 이러한 일련의 작업을 수행하는데 참고할 수 있는 사항들을 정리하고 이에 대한 의견을 제시하였다.