An Experimental Study on the Effect of Longitudinal Ventilation on the Variation of Burning Rate in Tunnel Fires

터널 화재시 종류식 환기가 연소율 변화에 미치는 영향에 관한 실험적 연구

  • 양승신 (중앙대학교 기계공학부) ;
  • 김성찬 (중앙대학교 미래신기술연구소) ;
  • 유홍선 (중앙대학교 기계공학부)
  • Published : 2005.02.01

Abstract

In this study, the 1/20 reduced-scale experiments using Froude scaling were conducted to investigate the effect of longitudinal ventilation on the variation of burning rate in tunnel fires. The methanol square pool fires with heat release rate ranging from 3.57 kW to 10.95 kW were used. The burning rate of fuel was obtained by measured mass using load cell and temperature distribution were measured by K-type theomocouples in order to investigate smoke movement. The wind tunnel was connected with one side of the tested tunnel, and logitudinal ventilation velocity in the tested tunnel was controlled by power of the wind tunnel. In methanol fire case, the increase in ventilation velocity decreased the turning rate due to the direct cooling of fire plume. For the same dimensionless velocity(V), homing rate decreased as the size of pool fire increased.

본 연구는 터널내 화재 발생시 종류식 환기가 연소율 변화에 미치는 영향을 파악하기 위하여 Froude scaling에 의해 1/20크기로 축소한 모형화재 실험을 수행하였다. 화원으로는 $8.5cm{\sim}14.5cm$의 메탄올을 사용하였으며 발열량은 $3.57{\sim}10.95kW$이다. 연소율은 로드셀을 이용하여 산출하였고, 연기거동을 파악하기 위하여 K형 열전대를 이용하여 온도분포를 측정하였다. 풍동은 터널의 한쪽부분과 연결하였고, 터널 공간의 배연속도를 제어하기 위하여 풍동의 전압을 조절하였다. 메탄올 화재인 경우 배연속도가 증가할수록 냉각효과로 인하여 연소율은 감소하였으며, 또한 같은 무차원속도(V)일때 화원 크기가 커짐에 따라 연소율은 감소하였다.

Keywords

References

  1. 이성룡, 2004, 종류식 배연 터널 화재시 임계속도에 대한종횡비의 영향에 관한 연구, 박사학위논문, 중앙대학교
  2. 차철헌, 김진국, 1999, 지하철 터널에서의 제연, 공기조화냉동공학, 제28권, 제6호
  3. Y. Oka and G. T. Atkinson, 1995, Control of Smoke Flow in Tunnel Fires, Fire Safety Journal, 25.4, 305-322 https://doi.org/10.1016/0379-7112(96)00007-0
  4. O. Vauquelin and O. Me'gret, 2002, Smoke Extraction Ex- periments in Case of Fire in a Tunnel, Fire Safety Journal, 37.5, 525-533 https://doi.org/10.1016/S0379-7112(02)00014-0
  5. G. T. Atkinson and Y. Wu, 1996, Smoke Control in Sloping Tunnels, Fire Safety Journal, 27.4, 335-341 https://doi.org/10.1016/S0379-7112(96)00061-6
  6. Y. Wu and M. Z. A. Baker, 2000, Control of Smoke Flow in Tunnel Fires Using Longitudina1 Ventilation Systerns-A Study of the Critical Velocity, Fire Safety Journal, 35.4, 363-390 https://doi.org/10.1016/S0379-7112(00)00031-X
  7. 김성찬, 유홍선, 김충익, 홍기배, 2002, 짧은 터널 내의 연기거동에 관한 연구, 터널과 지하공간, 제12권, 제1호, 31-36
  8. 이성룡, 김충익, 유홍선, 박현태, 2002, 터널화재시 연기제어에 관한 연구, 대한기계학회 춘계학술대회 논문집, 1894-1900
  9. 이성룡, 김충익, 유홍선, 김혁순, 전명배, 2004, 경사 터널내화재시 임계속도에 관한 실험적 연구, 한국화재, 소방학회논문집, 제18권, 제1호, 49-53
  10. 김성찬, 2003, 화염과 워터미스트의 상호작용에 관한 실험 및 수치해석 연구, 박사학위논문, 중앙대학교
  11. J. G. Quintiere, 1998, Principles of fire behavior, New york, Delmar Pub
  12. J. G. Quintiere, 1989, Scaling Applications in Fire Research, Fire Safety Journal, Vol. 15, 3-29 https://doi.org/10.1016/0379-7112(89)90045-3
  13. S. Sardqvist, 1993, RHR, Smoke Protection and CO Generation from Single Item and Room Fire Tests, Report, Department of fire Safety Engineering, Institute of Technology, Lund University