An Analysis of the Fire Load and Ventilation Factor in Underground Commercial Space

지하상업공간의 환기계수 및 화재하중 분석

  • Published : 2006.04.01

Abstract

The purpose of this study is to obtain the fire safety for underground commercial space with analysing fire loads and ventilation factors. It was adopted the investigation method of field survey with commercial uses for more confidential data. The results of this study can be summarized as follows; 1) The ventilation factor shows $0.04{\sim}0.24m^{1/2}$ and it may develop ventilation-controlled fires which have much fire hazard more than fuel-controlled fires. 2) The highest value of fire load is $158.48kg/m^2$ and appeared in footwear shop which has the value $137.35kg/m^2$ for unfixed combustibles and $21.13kg/m^2$ for fixed combustibles. 3) The average value of burning rates which mean the velocity of fire development and the fire damage range is 0.143. Therefore it is desired to decrease the combustibles of compartment and is needed the method of dispersion arrangement of goods and storage to steel cabinet and so on.

Keywords

References

  1. 일본건축센터(1997), 원저 건축방재계획지침, 한국화재보험협회
  2. 日本建築 センタ?(1993) 新.建築防災計劃指針
  3. 이강훈(2002), 건축방재계획론, 경남대학교 출판부
  4. 대한건축학회(1995.3), 강구조 건축물 내화설계기준 및 기법에 관한 연구, pp.83-86
  5. 田中哮義(1993), 建築火災安全工學入門, pp.49-52
  6. 이평강 외(2002.4), 건축물 화재안전을 위한 용도별 화재 하중 적용에 관한 연구, 대한건축학회 학술발표논문집 제 22권 1호
  7. 박종근 외(2003.9), 지하공간의 위험관리정보시스템 개발에 관한 연구, 대한건축학회논문집 계획계 19권 9호
  8. 김영하(1995.10), 지하공간의 실태 및 개선방안에 관한 고찰, 대한건축학회논문집 11권 10호
  9. 이원석 외(1989.4), 화재시 지하공간의 피난시설계획에 관한 연구, 대한건축학회 학술발표논문집 제 9권 1호