• Title/Summary/Keyword: dry chemical extinguisher

Search Result 7, Processing Time 0.016 seconds

Analysis of the Sedimentation Status Test for Type-3 Dry Chemical Powder with Changes in Internal Pressure of the Dry Chemical Extinguisher (분말소화기의 내부압력 변화에 따른 제3종 분말소화약제의 침강도 시험)

  • Ju-Dal Son;Seo-Young Kim;Ha-Sung Kong
    • Journal of the Korea Safety Management & Science
    • /
    • v.25 no.1
    • /
    • pp.67-74
    • /
    • 2023
  • This study aims to measure sedimentation status change with the changes in internal pressure for dry chemical extinguishers of various use periods and analyze the suitability of the fire extinguishers' performance criteria. When the internal pressure of the fire extinguisher is 0%, 2 out of 10 new dry chemical powders for the 5 elapsed years were noted to be suitable, including 3 recycled dry chemical powders with 5 elapsed years that were found eligible. One out of 10 new dry chemical powders for 10 elapsed years was shown as suitable. Also, one new dry chemical powder for 13 elapsed years was suitable. When the internal pressure of the fire extinguisher was 50%, all 10 out of 10 new dry chemical powders for 5 years, recycled one with 5 elapsed years, and a new one with 10 elapsed years were found to be suitable, while 9 new dry chemical powders for 13 years were shown as suitable. When the internal pressure of the fire extinguisher was normal, new ones with 5 elapsed years, recycled ones with 5 elapsed years, new ones with 10 elapsed years, and new ones with 13 elapsed years were all 10 out of 10 samples noted as suitable. In summarizing the experiment results, it was found that the sedimentation status, one of the fire extinguisher's physical properties experiments, affects the fire extinguisher's performance criteria rather than the change with use periods.

Analysis of the Apparent Specific Gravity for Type-3 Dry Chemical Powder with the Changes in the Internal Pressure of Dry Chemical Extinguisher (분말소화기의 내부압력 변화에 따른 제3종 분말소화약제의 겉보기비중 실험 분석)

  • Ju-Dal, Son;Seo-young, Kim;Ha-sung, Kong
    • The Journal of the Convergence on Culture Technology
    • /
    • v.9 no.3
    • /
    • pp.607-617
    • /
    • 2023
  • This study aims to analyze whether the performance of the fire extinguisher meets the criteria for the apparent specific gravity property test by calculating the change in internal pressure and the use period of the fire extinguisher as a new one with 5 years, recycled one with 5 years, a new one with 10 years, and a new one with 13 years, respectively. As a result of the experiment, when the internal pressure of the fire extinguisher was 0%, the first, second, and third arithmetic mean analysis of the dry chemical extinguisher according to the use period was found to be condemned. When the internal pressure of the fire extinguisher was 50%, it was measured as 130 ml in sample 12-08-new and analyzed as unsuitable. Also, sample 09-09-new of a new dry chemical extinguisher with 13 elapsed years measured 145ml, which was found inappropriate. All other dry chemical extinguishers were analyzed to be suitable. All were noted suitable when having normal internal pressure of the fire extinguisher, except for sample 09-06 of a new dry chemical extinguisher with 13 elapsed years, which was determined to be unsuitable caused by measuring as 131 ml for experimental value. As a result of experiments, some of the apparent specific gravity tests of dry chemical extinguishers from 10 years to 13 years have found that they are unsuitable for the performance of the fire extinguishers due to the massive phenomenon. Accordingly, it is necessary to reduce the endurance period of dry chemical extinguishers from 10 years to 7 years.

A Study on Improving Extinguishing Capacity of Mobile Water Mist Equipment (이동식 미분무수 소화장비의 소화능력 향상에 관한 연구)

  • Kong, Ha-Sung;Kim, Jong-Jin
    • Journal of the Korea Safety Management & Science
    • /
    • v.11 no.1
    • /
    • pp.15-26
    • /
    • 2009
  • This research has so far found out problems including the second damage of extinguishant and the short time of emission when using the existing dry chemical extinguisher and gas type extinguisher, and impossibility of constant extinguishing due to the inability of recharge at the field. To solve such problems, a mobile water mist system was developed and used. However, it is judged that more improved mobile water mist system is necessary because the force of the fire changed diversely and remote villages in mountains or islands where the force of fire extinguishing is short or delayed, require high capacity of fire extinguishing. Therefore a new equipment was developed and tested focusing on the improvement of extinguishing capacity and the performance of extinguishing was found out to be improved, compared to the existing mobile water mist system. It also showed a superior extinguishing capacity to dry chemical extinguisher or gas type extinguisher. Afterward an additional research is required of simplification of equipment, price cutting and the development of additive to enable high performance even with just small extinguishant.

Analysis of the Precautionary Measures and Causes on Explosion Accidents of a Old Dry Chemical Powder Extinguisher (노후 분말소화기의 폭발사고 원인과 예방대책에 관한 분석)

  • Lee, Eui-Pyeong
    • Fire Science and Engineering
    • /
    • v.26 no.3
    • /
    • pp.91-99
    • /
    • 2012
  • Fatal injuries and deaths have occurred resulting from the operation or disassembling of a powder extinguishers in Korea. If a rusted powder extinguisher is exploded during operation or disassembling, it rises to the air like a rocket and hits a head, chest, or neck part of an operator, resulting in his (her) death or injury. In this study examines the explosion accident cases of a powder fire extinguisher and analyzes their causes, reactions to explosion, and precautionary measures. And in this paper suggests 1) no using of old fire extinguishers in fire drill or education, 2) education and public information on danger of old fire extinguishers, 3) indication of explosion danger to cartridge-type dry chemical powder fire extinguishers had already placed to buildings etc., 4) obligatory indication of durable years on fire extinguishers, 5) examination for introduction of system that do hydraulic pressure test about fire extinguishers that given period past, 6) construction of system that reclaim old fire extinguishers, 7) construction of system that recycle or reuse old fire extinguishers, and 8) operation of help desk related to old fire extinguishers as precautionary measure of fire extinguisher explosion accidents.

A Study on the Effective Method of Fire Extinguisher Maintenance In the Underground Parking Lot of the Apartment (아파트 지하주차장 소화기의 유지관리 효율화 방안에 관한 연구)

  • Lee, Young-Sam
    • Journal of the Korea Safety Management & Science
    • /
    • v.18 no.3
    • /
    • pp.1-8
    • /
    • 2016
  • The definition of an apartment is a building more than 5 stories high and which is the standard law. Currently, the number of apartments is increasing much faster than detached houses. Owning an apartment is a normal trend these days. However, the increasing number of apartments has been increasing the number of apartment fires which also has been making social problems. Therefore, this study was conducted for the fire extinguisher among other fire facilities because it is important for initial fire suppression. The research subject is on the fire extinguisher that is in the underground parking lot of 40 apartment complexes which are more than 10 stories. Survey and analysis were conducted for 80 fire extinguishers. There are two fire extinguishers for each apartment. The result of this study is that all installed fire extinguishers are ABC dry chemical type, 92% of them is 3.3kg and that meet the legal height(less than 1.5m). However, the condition such as appearance, inspection, manufactured year, appearance of signs, material of signs, size of signs, etc. was insufficiency. So improvement of law and system that are fire facility construction, maintenance implementation and additional designation of type approval about sign will be needed in my opinion.

Smart Fire Fighting Appliances Monitoring System using GS1 based on Big Data Analytics Platform (GS1을 활용한 빅데이터 분석 플랫폼 기반의 스마트 소화기구 모니터링 시스템)

  • Park, Heum
    • Journal of Korea Society of Digital Industry and Information Management
    • /
    • v.14 no.4
    • /
    • pp.57-68
    • /
    • 2018
  • This paper presents a smart firefighting appliances monitoring system based on big data analytics platform using GS1 for Smart City. Typical firefighting appliances are fire hydrant, fire extinguisher, fire alarm, sprinkler, fire engine, etc. for the fire of classes A/B/C/D/E. Among them, the dry chemical fire extinguisher have been widely supplied and 6 millions ones were replaced for the aging ones over 10 years in the past year. However, only 5% of them have been collected for recycling of chemical materials included the heavy metals of environment pollution. Therefore, we considered the trace of firefighting appliances from production to disposal for the public open service. In the paper, we suggest 1) a smart firefighting appliances system using GS1, 2) a big data analytics platform and 3) a public open service and visualization with the analyzed information, for fire extinguishers from production to disposal. It can give the information and the visualized diagrams with the analyzed data through the public open service and the free Apps.

Policy Direction for Fire Products Life Expectancy Legislation (소방용품 내용연수 제도화 정책방안)

  • Baek, Chang Sun;Park, In-Seon
    • Fire Science and Engineering
    • /
    • v.30 no.1
    • /
    • pp.111-120
    • /
    • 2016
  • This study is intended to provide legislative direction for fire products life expectancy. Domestic and international laws relating to fire products life expectancy have been reviewed, and the results of a Fire Safety Manager Consciousness (FSMC) survey were analyzed. The FSMC survey has been designed in order to assist with the establishment of appropriate fire safety policy. A questionnaire survey was conducted with 660 fire safety administrators from 17 municipal and provincial districts, with the intention of gaining expertise on the extension of life-span for 32 fire products. The survey also asked for candidates opinions on future policy direction. Based on the survey results and the review of policies within other nations, we have devised a set of policy issues with the intention of extending the life-span of fire-safety items. The survey result revealed that 79.3% of Fire Safety Managers (FSMs) concurred with the establishment of legislation regarding the maintenance and correct care of fire-safety products. Overall, over 30% of FSMs were in favor of regulations regarding Ddry chemical fire extinguishers (77.3%), fire detectors (44.6%), fire hoses (44.4%), gaseous agent fire extinguisher (40.6%), automatic descending life lines (36.2%), exit lights (35.9%), air respirators (35.9%), extinguishing systems for residential cooking facilities (33.9%), automatic spray-type extinguishing units (33.9%), emergency lights (31.2%), and gas leakage detectors (30.7%). Especially, among these, dry chemical fire extinguishers (60.0%), detectors (20.0%), and fire hose (18.8%) were identified as the fire products primarily in need of maintenance legislation. The general consensus is that fire products older than 10 years need to be replaced. Based on the survey results, there was general agreement that fire product life expectancy is in need of legislation. This study recommends the introduction of fire product life expectancy legislation in phases.