• Title/Summary/Keyword: current(CT)

Search Result 467, Processing Time 0.031 seconds

The Optimization of Optical Current Transformer owing to Incident Polarization (입사편광에 따른 광섬유형 광 CT의 최적화)

  • Kim Duck-Lae;Kim Byung-Tai
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.54 no.9
    • /
    • pp.407-413
    • /
    • 2005
  • The optical current transformer was developed for 170 kV GIS using optical fiber. The sensor optimized on the optical CT was wound 3 turns and twisted 4 times per a turn at the pipe with a diameter of 130 m. To optimize the optical CT, the output signal was measured according to the setting angle of polarizer and analyzer, The asymmetry and distortion of the output signals were improved when the parallel polarized light was incident to the fiber sensor and under the angle of analyzer was $45^{o}$. The measurement error for the linearity was only $\pm{0.42}\;\%$ to 1,000 A in the case of reflection type.

Current differential relay for transformer protection combined with a CT compensating algorithm (보상 알고리즘을 적용한 변압기 보호용 전류차동 계전 방식)

  • Kang, Yong-Cheol;Lee, Byung-Eun;Jin, Enshu;Park, Jong-Min;So, Soon-Hong;Hwang, Tea-Keun;Kim, Yeon-Hee
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.444-446
    • /
    • 2005
  • This paper describes a current differential relaying algorithm for power transformers with an advanced compensation algorithm for the secondary current of CTs. The comparative study was conducted with and without the compensating algorithm. The algorithm can reduce the operating time of the relay in the case of an internal fault and improve security for external faults. The performance of the proposed algorithm was investigated when the C100 CT, a quarter of the rated CT(C400), is used.

  • PDF

An Algorithm for Detecting CT Saturation (변류기 2차 전류의 포화 여부 판단 알고리즘)

  • Kang, Y.C.;Ok, S.H.;Kang, S.H.
    • Proceedings of the KIEE Conference
    • /
    • 2000.11a
    • /
    • pp.64-66
    • /
    • 2000
  • This paper presents an algorithm for detecting current transformer (CT). At the instants of beginning and end of saturation, the increment of the secondary current is reduced significantly, depending on the residual flux and saturation time. Thus, the third difference of the current is used to detect saturation in this paper. If the third difference is less than threshold the CT is at the beginning/end of saturation. The proposed detection method is unaffected by the amount of residual flux. The results of various tests with residual flux from -80% to +80% indicate satisfactory performance of the method.

  • PDF

A Note on the Outflow Boundary Conditions in Modeling the East Sea Circulation

  • Seung, Young-Ho;Cho, Kyoung-Ho
    • Journal of the korean society of oceanography
    • /
    • v.33 no.4
    • /
    • pp.212-218
    • /
    • 1998
  • Three different outflow boundary conditions are considered in modeling the East Sea circulation. The first one is that of the conventional constant volume transport (CT). The second one is the Orlanski radiation boundary condition (OR). The third one is that of the constant sea level just outside the outflow boundary (SL). In the third condition, the outflow current is set to be driven by the sea level differences across the outflow open-boundary lines, based on the recent knowledge that the Tsushima Current is driven by the sea level differences across the inflow and outflow boundaries. In case of OR it takes too much time to reach the steady state, resulting in a large increase of Tsushima Current Water in the basin and low level of kinetic energy. Both CT and SL reach the steady state in a relatively short time. However, SL is more recommendable, because it is based on physical background and generates less numerical noises than CT.

  • PDF

Development of Rogowski-Coil Type CT for Application in 170kV GIS (170kV GIS용 Rogowski coil형 CT개발)

  • Chung, Y.H.;Kim, J.B.;Song, W.P.;Kim, D.S.
    • Proceedings of the KIEE Conference
    • /
    • 2001.07a
    • /
    • pp.479-481
    • /
    • 2001
  • Traditionally, instrument transformer of the ferromagnetic core type have been used for measuring current in GIS(Gas Insulated Switchgear). Recently, with the introduction of digital technology at the protection relay or measurement device level, the use of new current sensor can be foreseen. Current measurement by means of Rogowski coil is just one illustration of this. This paper describes the progress of development of Rogowski-coil type CT for application in 170kV GIS.

  • PDF

Design of a CT Saturation Detection Technique with the Countermeasure for a Spike Signal

  • Kang, Yong-Cheol;Yun, Jae-Sung
    • KIEE International Transactions on Power Engineering
    • /
    • v.3A no.2
    • /
    • pp.85-92
    • /
    • 2003
  • When a current transformer (CT) is saturated, the wave-shape of the secondary current is distorted and contains points of inflection, which correspond to the start or end of each saturation period. Discontinuity in the first-difference function of the current arises at points of inflection, where the second and third differences convert into pulses that can be used to detect saturation. This paper describes the design and evaluation of a CT saturation detection technique using the third-difference function and includes the countermeasure for a spike signal. Test results clearly demonstrate that the algorithm successfully detects the start and end of each saturation period irrespective of the remanent flux and magnetization inductance in the saturated region. This paper concludes by describing the results of hardware implementation of the algorithm using a DSP.

A Study on Dose Response of MAGAT (Methacrylic Acid, Gelatin Gel and THPC) Polymer Gel Dosimeter Using X-ray CT Scanner (X-ray CT Scanner를 이용한 MAGAT (Methacrylic Acid, Gelatin Gel and THPC) 중합체 겔 선량계의 선량 반응성 연구)

  • Jung, Jae-Yong;Lee, Choong-Il;Min, Jeong-Hwan;Kim, Yon-Lae;Lee, Seong-Yong;Suh, Tae-Suk
    • Progress in Medical Physics
    • /
    • v.21 no.1
    • /
    • pp.1-8
    • /
    • 2010
  • In this study, we evaluated the dose response of MAGAT (Methacrylic Acid Gelatin gel and THPC) normoxic polymer gel dosimeters based on the X-ray CT scanner. To perform this study, we determined the proper ratio of the gel composition and acquired X-ray scan parameters. MAGAT gel dosimeters were manufactured using MAA (MethacrylicAcid) and gelatin of various concentration, irradiated up to 20 Gy. We obtained the 20 CT images from the irradiated gel dosimeters by using on a Phillips Brilliance Big Bore CT scanner with the various scan parameters. This CT images were used to determine the $N_{CT}$-dose response, dose sensitivity and dose resolution As an amount of MAA and gelatin were increase, the slope and intercept were increase in each MAGAT gel dosimeter with various concentration of the $N_{CT}$-dose response curve. The dose sensitivity was $0.38{\pm}0.08$ to $0.859{\pm}0.1$ and increased were amount of the MAA was increased or the gelatin was decreased. However, the change of gelatin concentration was very small compare to MAA. The Dose resolution ($D_{\Delta}^{95%}$) varies considerably from 2.6 to 6 Gy, dependent on dose resolution and CT image noise. The slope and dose sensitivity was almost ident verywith the variation of the tube voltage, tube current and slice thickness in the dose response curve, but the noise (standard deviation of averamalg CT number) was decreased when the tube voltage, tube current and slice thickness are increase. The optimal MAGAT polymer gel dosimeter based on the CT were evaluated to determine the CT imaging scan parameters of the maximum tube voltage, tube current and slice thickness (commonly used in clinical) using the composition ratio of a 9% MAA, 8% gelatin and 83% water. This study could get proper composition ratio and scan parameter evaluating dose response of MAGAT normoxic polymer gel dosimeter using CT scanner.

Voltage Control of a Synchronous Generator for Ship using a Compound Type Digital AVR (혼합형 디지털 자동 전압 조정 장치를 이용한 선박용 동기발전기의 출력전압제어)

  • Park, Sang-Hoon;Lee, Sang-Seuk;Yu, Jae-Sung;Lee, Su-Won;Won, Chung-Yuen
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.58 no.4
    • /
    • pp.397-403
    • /
    • 2009
  • In this paper, an exciter current control of a synchronous generator for ships using a compound type digital automatic voltage regulator (DVAR) in order to provide a constant output voltage of the generator is presented. The compound type DAVR is composed of a controller part to adjust output voltage and an power source unit to supply power to the exciter. The controller part, which generates the PWM switching pattern via the PI controller, drives a power MOSFET for bypass to limit the SG's exciter current. The power source unit part is parallel connected to an output terminal of the generator through a reactor and a power CT. The residual magnetic flux of SG provides exciter current to the exciter through the reactor during the initial running or no load state and load current supplies field current to the exciter through the power CT during loading state. This paper confirmed an experiment to verify the validity of compound type DAVR system for controlling output voltage of synchronous generator.

Current-induced Phase Demodulation Using a PWM Sampling for a Fiber-optic CT

  • Park, Hyoung-Jun;Lee, June-Ho;Kim, Hyun-Jin;Song, Min-Ho
    • Journal of the Optical Society of Korea
    • /
    • v.14 no.3
    • /
    • pp.240-244
    • /
    • 2010
  • In this work, we used PWM sampling for demodulation of a fiber-optic interferometric current transformer. The interference signal from a fiber-optic CT is sampled with PWM triggers that produce a 90-degree phase difference between two consecutively sampled signals. The current-induced phase is extracted by applying an arctangent demodulation and a phase unwrapping algorithm to the sampled signals. From experiments using the proposed demodulation, we obtained phase measurement accuracy and a linearity error, in AC current measurements, of ~2.35 mrad and 0.18%, respectively. The accuracy of the proposed method was compared with that of a lock-in amplifier demodulation, which showed only 0.36% difference. To compare the birefringence effects of different fiber-optic sensor coils, a flint glass fiber and a standard single-mode fiber were used under the same conditions. The flint glass fiber coil with a Faraday rotator mirror showed the best performance. Because of the simple hardware structure and signal processing, the proposed demodulation would be suitable for low-cost over-current monitoring in high voltage power systems.

Setting Method of a Percentage Current Differential Relay for Transformer Protection (변압기 보호용 전류비율차동 계전기의 동작영역 설정방법)

  • Kim, Su-Hwan;Kang, Sang-Hee
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.1
    • /
    • pp.8-13
    • /
    • 2011
  • A percentage current differential relay is widely used for transformer protection. Because many percentage current differential relays recently use modified methods instead of conventional methods for deciding the operating characteristics of the large current region, in this paper, the operating region of a percentage current differential relay is analyzed in input-output current domain instead of operating-restraint current domain. An effective method to set the operating region when a CT is saturated is proposed with a series of investigations comparing a conventional method with the proposed modified method. The performance of the proposed method is evaluated for internal and external faults of a power transformer having the voltage rating of 345/154kV. EMTP-RV is used for the relaying data collection.