• Title/Summary/Keyword: arcing faults

Search Result 26, Processing Time 0.028 seconds

A Study on the Classification of Arcing Faults in Power Systems using Phase Plane Trajectory Method (위상면궤적을 이용한 전력계통의 고장판별에 관한 연구)

  • Park, Nam-Ok;Sin, Yeong-Cheol;An, Sang-Pil;Yeo, Sang-Min;Kim, Cheol-Hwan
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.51 no.5
    • /
    • pp.209-216
    • /
    • 2002
  • Recently, there is greater demand for stable supply of electric power as higher level of our living. It becomes the important problem that the cause of fault in power system is found out in early stage, if once it occurs. In this respect, accurate classification of arcing faults in power systems is vitally important. This paper presents a new classification method for arcing faults in power system. To obtain data of various faults including high impedance fault(HIF) and low impedance fault(LIF), HIF model with the ZnO arrester is adopted and implemented within the overall transmission system model based on the electromagnetic transients program(EMTP). Results of phase plane trajectory if Clarke modal transformation using postfault current and voltage are utilized to classify types of arcing faults. The performance of the proposed method is tested on a typical 154 kV korean transmission system under various fault conditions. As can be seen from results, phase plane trajectory of postfault current should be combined with that of o component from Clarke modal transformation to give reliability of clear fault classification. Thus the proposed method can classify arcing faults including LIFs and HIFs accurately in power systems.

Discrimination of Arcing Faults from Normal Distribution Disturbances by Wave form Distortion Analysis

  • Kim, C. J.
    • Journal of Electrical Engineering and information Science
    • /
    • v.1 no.2
    • /
    • pp.52-57
    • /
    • 1996
  • Detection of arcing high impedance faults has been a perplexing in the power distribution protection. Transient analysis of distribution disturbances for fault discrimination from other normal events is important for a secure protection of the power system. A simple parameter of wave form distortion quantification is used to analyze the behaviors of arcing faults and normal distribution disturbances. Theoretical perspectives of the transients were studied and actual disturbances were examined. From this investigation, a discrimination guideline based on the revised crest factor is developed. The discrimination method has a high potential to enhance the reliability and security for the distribution system protection.

  • PDF

Mitigation of high energy arcing faults in nuclear power plant medium voltage switchgear

  • Chang, Choong-koo
    • Nuclear Engineering and Technology
    • /
    • v.51 no.1
    • /
    • pp.317-324
    • /
    • 2019
  • A high energy arcing fault event occurred in the medium-voltage (13.8 kV and 4.16 kV) metalclad switchgears in a nuclear power plant not only affecting switchgear but also connected equipment due to the arc energy. The high energy arcing fault also causes a fire that influences the safety function of the unit. Therefore, from the safety point of view, it is necessary to evaluate the influences of high energy arcing fault events on the safety functions of nuclear power plants. The purpose of this paper is to elaborate the characteristics of high energy arcing faults and propose a high energy arcing fault mitigation scheme for medium voltage networks in nuclear power plants.

A Study on the Defection of Arcing Faults in Transmission Lines and Development of Fault Distance Estimation Software using MATLAB (MATLAB을 이용한 송전선로의 아크사고 검출 및 고장거리 추정 소프트웨어 개발에 관한 연구)

  • Kim, Byeong-Cheon;Park, Nam-Ok;Kim, Dong-Su;Kim, Gil-Hwan
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.51 no.4
    • /
    • pp.163-168
    • /
    • 2002
  • This paper present a new verb efficient numerical algorithm for arcing faults detection and fault distance estimation in transmission line. It is based on the fundamental differential equations describing the transients on a transmission line before, during and alter the fault occurrence, and on the application of the "Least Error Squares Technique"for the unknown model parameter estimation. If the arc voltage estimated is a near zero, the fault is without arc, in other words the fault is permanent fault. If the arc voltage estimated has any high value, the faust is identified as an fault, or the transient fault. In permanent faults case, fault distance estimation is necessary. This paper uses the model of the arcing fault in transmission line using ZnO arrestor and resistance to be implemented within EMTP. One purpose of this study is to build a structure for modeling of arcing fault detection and fault distance estimation algorithm using Matlab programming. In this paper, This algorithm has been designed in Graphic user interface(GUI).

Analysis of Tripping Characteristics of Earth Leakage Circuit Breakers against Parallel Arcing (병렬아크에 대한 누전차단기의 트립특성 분석)

  • Kim, Il-Kwon;Park, Dae-Won;Choi, Su-Yeon;Cho, Young-Jin;Kil, Gyung-Suk
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2007.11a
    • /
    • pp.478-479
    • /
    • 2007
  • Many electrical fires are occurred by leakage currents and sparks generated by a short circuit. Earth leakage circuit breakers (ELCBs) should be tripped at the moment of the faults mentioned above. In this paper, we described the tripping characteristics of ELCBs against parallel arcing faults. A diesel engine generator with the capacity of 375 kVA source was adopted to provide enough large current when a parallel arcing occurred. The experimental results showed that most ELCBs we experimented were not tripped against short-duration pulse currents produced by parallel arcing because the ELCBs are designed to be tripped by a large current with long duration similar to power frequency.

  • PDF

Study on Testing Enclosed low-voltage switchgear and controlgear assemblies Under conditions of arcing due to internal faults (내부고장으로 인한 아크상태의 저압배전반 시험방법 동향 고찰)

  • Kim, Sun-Ho;Kim, Sun-Koo;Roh, Chang-Il;Jung, Heung-Soo;Kim, Won-Man;Lee, Dong-Jun
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.927-928
    • /
    • 2007
  • Recently IEC has made considerations on testing Enclosed low-voltage switchgear and controlgear assemblies under conditions of arcing due to internal faults. This paper will make a study on testing Enclosed low-voltage switchgear and controlgear assemblies under conditions of arcing due to internal faults that is suggested by IEC.

  • PDF

Analysis on the Effect of Arcing Fault and CT Saturation on Distance Algorithms (아크고장 및 CT포화가 거리계전 알고리즘에 미치는 영향분석)

  • Son, Chun-Myung;Kang, Sang-Hee;Kang, Yong-Choel;Rebizant, Waldemar
    • Proceedings of the KIEE Conference
    • /
    • 2002.11b
    • /
    • pp.50-52
    • /
    • 2002
  • Distance relays need accurate current and voltage for determining the trip ignition. Therefore we must analyze nonlinear phenomena which cause distortion in signals first of all. This paper presents the effect of some distortion(arcing fault and current transformer saturation) in power system. The saturation of a current transformer distorts input current of a distance relay and arcing faults make current and voltage to be changed. This paper describes modeling methods of a current transformer and arcing faults, and describes the simulation result of two distance relay algorithms (discrete fourier transform and modified differential equation methods)

  • PDF

Series Arcing Fault Detection Method Using Harmonics Analysis of Supply Current (전원 전류 고조파 해석에 의한 직렬 아크 고장 검출 방안)

  • Ahn, Jeongwoon;Oh, Yong-Taek
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.28 no.12
    • /
    • pp.30-37
    • /
    • 2014
  • Recently, Concerns of imbalance for power supply has been raised by the increase of electric power consumption, but the interest of electric safety is still lacking due to the incompleteness of regulations. Particularly, Arcing fault, direct cause of electric fire accidents, is difficult to detect, interrupt due to unformal signal behaviour in previous research and apply to real system. In this paper, Arcing fault simulator device was fabricated to investigate the characteristics of series arcing fault and simulated the faults in various real load. Also, this study are analysed arcing fault signal by using the harmonic analysis of the acquired data from the current of the power supply and proposed the methods to prevent the series arcing fault accidents in advance.

A Study on the Classification of High Impedance Faults using Clarke Transformation and Plane Trajectory Method (Clarke법과 위상면궤적을 이용한 고저항 지락사고의 판별에 관한 연구)

  • Kim, C.H.;Shin, Y.C.;Ahn, S.P.
    • Proceedings of the KIEE Conference
    • /
    • 2001.07a
    • /
    • pp.243-245
    • /
    • 2001
  • This paper presents a new classification method for high impedance faults in power systems. Results of phase plane trajectory with Clarke modal transformation using postfault current and voltage are utilized to classify types of arcing faults. The performance of the proposed method is tested on a typical 154 kV korean transmission system under various fault conditions using EMTP. As can be seen from results, phase plane trajectory of postfault current should be combined with that of o component from Clarke modal transformation to give reliability of clear fault classification. Thus the proposed method can classify arcing faults including LIFs and HIFs accurately in power systems.

  • PDF

A Numerical Algorithm for Fault Location Estimation and Arc Faults Detection for Auto-Reclosure (자동 재폐로기의 동작책무를 위한 아크전압 판정 및 사고거리 표정 알고리즘)

  • Kim, Byeong-Man;Chae, Myeong-Suk;Zheng, Tai-Ying;Kang, Yong-Cheol
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.7
    • /
    • pp.1294-1303
    • /
    • 2009
  • This paper presents a new numerical algorithm for fault discrimination and fault location estimation when occur to arcing ground and arcing line to line on transmission lines. The object of this paper is developed from new numerical algorithm to calculate the fault distance and simultaneously to make a distinction between transient and permanent faults. so the first of object for propose algorithm would be distinguish the permanent from the transient faults. This arcing fault discrimination algorithm is used if calculated value of arc voltage amplitude is greater than product of arc voltage gradient and the length of the arc path, which is equal or greater than the flashover length of a suspension insulator string[1-3]. Also, each algorithm is separated from short distance and long distance. This is difference to with/without capacitance between short to long distance. To test the validity of the proposed algorithms, the results of algorithm testing through various computer simulations are given. The test was simulated in EMTP/ATP simulator under a number of scenarios and calculate of algorithm was used to MATLAB.