물류창고 시설의 인명안전기준 개선 방안에 관한 연구 (A Study on the Improvement of Life Safety Code for Logistics Warehouse Facilities)

  • 김윤성;진승현;이병흔;권영진
    • 한국건축시공학회:학술대회논문집
    • /
    • 한국건축시공학회 2021년도 봄 학술논문 발표대회
    • /
    • pp.98-99
    • /
    • 2021
  • The number of fires in the Korean distribution warehouse increased by about 350 from 1,070 in 2014 to 1,416 in 2020. In addition, the fire load increases with the scale of the distribution warehouse, and even if the automatic sprinkler operates, there is a limit to the direct intrusion of the water source into the ignition source, and the detector is often installed on a high ceiling. The sensing time is often delayed. In order to improve the fire safety of such distribution warehouses, the US NFPA stipulates in detail the contents related to the facility, such as sprinkler water discharge standards, rack-type warehouse installation height restrictions, and regulations on collection and equipment. However, in Japan, the goods loaded inside the distribution warehouse are not classified in detail, and it is considered that the fire safety for the distribution warehouse is low due to the relaxation regulations of the fire prevention section. Therefore, in this study, common problems are classified into material, spatial, and safety management characteristics through the cases of distribution warehouse fires that occurred in Korea and abroad, and the problems related to distribution warehouses in Korea and abroad are compared and analyzed. And present basic materials for improving the life safety standards of future distribution warehouse facilities.

  • PDF

창고 모델 실물화재 특성에 대한 실험적 연구 (An Experimental Study on the Warehouse Mock-up Fire Test)

  • 권오상;유용호;김흥열
    • 한국화재소방학회논문지
    • /
    • 제24권4호
    • /
    • pp.47-54
    • /
    • 2010
  • 본 연구에서는 창고 화재 사고의 위험성을 파악하기 위해서 중규모 실물 화재 실험 장비인 룸코너 시험기(Room Corner Tester)를 통해 구축된 단위 구성품의 화재 특성 DB를 바탕으로 화재에 취약할 것으로 판단되는 의류 창고를 실험 모델로 구성하여 실물 화재실험 장비인 라지 스케일 칼로리미터(Large Scale Calorimeter)에서 실물 화재실험을 실시하였다. 창고 모델의($3m{\times}3m{\times}2.4m$) 벽체는 불연등급의 그라스울과 일반 스티로폼 샌드위치 패널로 구성하였다. 실험결과 최대 열방출률은 그라스울 샌드위치 패널 창고모델에서 5MW, 스티로폼 샌드위치 패널 창고모델에서 11MW를 나타내었다.

사례분석과 현장인터뷰를 통한 적층형 대형창고 소방활동 개선방안 연구 (A Improvement Plan for Fire Fighting Activity of Rack- Type Warehouse Based on Case Study and Field Interview)

  • 김운형;서동훈;함은구
    • 한국재난정보학회 논문집
    • /
    • 제15권1호
    • /
    • pp.67-75
    • /
    • 2019
  • 연구목적: 본 연구는 국내 적층형 창고건물의 소방대응력 강화를 위한 제도적 개선방안을 제시함을 목적으로 한다. 연구방법:경기도 소재 창고 화재사례 및 설계사례를 분석하고 11명의 현장대응 소방전문가 집단인터뷰를 수행하였다. 연구결과: 초기소화용 이동식 장비마련, 3면 이상 접근성확보, 내부진입창 설치, 옥외소화설비의 적정배치, 현장정보의 이미지처리, 현장지휘관 인센티브 강화 등을 통한 소방활동 개선방안이 필요하다. 결론: 창고의 규모별 구조별 화재특성 및 위험요인을 고려하여 출동단계 및 현장대응단계별로 효율적인 표준작전절차 및 안전기준을 수립 적용되어야 한다.

랙크식 자동창고의 화재위험성 및 개선방안에 대한 연구 (A Study on the Fire Hazard and Improvement Schemes of a Rack-type Automatic Warehouse)

  • 이유식;안영철;남유진;유동균;곽지현
    • 동력기계공학회지
    • /
    • 제21권3호
    • /
    • pp.19-29
    • /
    • 2017
  • Recently, there has been increased demand for automatic warehouses with racks which are installed inside the warehouses to allow vertical loading of products or goods for space efficiency. Therefore considerations about fire hazards are extremely necessary. In this study, the fire hazard of automatic warehouse with racks was analyzed in the view of fire prevention engineering. It appeared its fire hazard was extremely high because of the undefined fire zones, the windowless floor, the large volume, the difficulty of extinguishment and the smoke emission in the view of building itself, and because of the fire hazard of load itself, the high fire load, and the chimney effect in the view of fire.

냉동창고 화재 사례를 기반으로 하는 NFPA 921 CODE에 의한 과학적 화재조사 연구 (Scientific fire investigation by NFPA 921 CODE based on frozen warehouse fire case)

  • 박경진;이영기;차성식;정도영;김장오
    • 한국산학기술학회논문지
    • /
    • 제19권8호
    • /
    • pp.78-85
    • /
    • 2018
  • 본 연구에서는 2017년 20건의 화재가 발생한 냉동창고 화재사례중 발화원인의 판정에 다수의 의견이 존재하였던 사례에 대해 연구하였다. 연구 방법론은 NFPA 921 CODE에서 규정하고 있는 과학적 화재조사 방법이다. 과학적 화재조사 방법은 가설설정을 통한 논리적 추론에 의한 화재조사 방법으로 발화원인 판단에 오류를 최소화 시킨다. 반면에 비과학적 화재조사 방법은 발화원인의 판단에 주관적 추측, 추론적 판단 등의 비합리적 요소의 개입으로 많은 오류를 발생시킨다. 이는 결국 인적, 물적 책임의 문제 및 학문적 퇴보를 가져온다. 특히 목격된 화재(Sighted fire)에 비해 목격되지 않는 화재(Fire not seen)의 경우 원인조사에 있어서 더 많은 발화원인 의 오류를 만든다. 본 연구에서는 2017년 **시 **마트에서 발생한 냉동창고 정온전선의 화재사례에 대해 화재조사 보고서의 검토, 현장조사를 바탕으로한 가설A 와 가설B의 설정하였다. 설정된 가설은 NFPA 921 code 규정하고 있는 연역적 검정 방법중 실험으로 검정하였다. 이러한 분석방법은 향후 목격되지 않는 화재(Fire not seen) 및 원인 불명 화재의 발화원인 판단에 NEW Paradigm의 구축 할 것이다. 또한 본 연구의 실험 자료는 냉동창고 제조사 및 운영사에 통보, 화재 예방을 위한 기초 자료로 활용 될 것이다.

랙크식 창고 화재의 수직 확산 방지를 위한 수평차단막과 In-Rack 스프링클러 적용에 관한 실험연구 (An Experimental Study on the Application of Horizontal Barrier and In-Rack Sprinklers to Prevent Vertical Spread of Rack-type Warehouse Fires)

  • 박문우;홍성호;최기옥;최돈묵;김수진
    • 한국안전학회지
    • /
    • 제34권5호
    • /
    • pp.15-21
    • /
    • 2019
  • A rack-type warehouse has the advantage of storing a large amount in a small area by loading goods vertically. But in terms of fire risk, the fire load is very high, which can cause massive damage in the event of a fire. In the United States, research has been actively conducted to minimize the spread of vertical fires, and relevant standards have been established and operated. In Korea, research and related standards are insufficient to prevent the vertical spread of rack-type warehouse fires. In this study, an experimental study was conducted to prevent the vertical spread of a rack-type warehouse fire using a horizontal barrier and in-rack sprinklers. As a result of the test, the horizontal barrier considering the continuous flame prevented the vertical spread of the flame for a certain time. However, the horizontal barrier with continuous flame did not show the effect of preventing continuous flame. The combination of the horizontal barrier and the in-rack sprinkler prevented the vertical spread of fire effectively. In addition, the heat collecting effect through the horizontal barrier was shown and helped the early operation of the in-rack sprinklers.

화재시뮬레이션을 통한 물류창고 화재 속도와 위치에 따른 공기흡입형 감지기와 일반 연기 감지기 감지시간 비교에 관한 연구 (A Study on the Comparison of Aspirating Smoke Detector and General Smoke Detector Detection Time according to the Fire Speed and Location of Logistics Warehouse through FDS)

  • 이상범;김민석;민세홍
    • 한국재난정보학회 논문집
    • /
    • 제19권3호
    • /
    • pp.608-623
    • /
    • 2023
  • 연구목적: 최근 물류 창고 수의 증가 추세에 있다. 또한 이러한 물류 창고의 수가 늘어남에 따라 화재발생건수 또한 매년 증가 추세를 보여 대형 물류 창고에서 발생하는 화재 예방의 중요성이 커지고 있다. 연구방법: 물류 창고에 적응성 있는 화재감지기로 대두되고 있는 공기흡입형 감지기에 대해 조사하고 화재시뮬레이션(FDS)를 통해 물류 창고 모델링을 진행하여 물류창고 화재 성장 속도 4단계와 화원 위치 3가지에 따른 일반 연기감지기와 공기흡입형 감지기의 감지 속도를 비교 분석하였다. 연구결과: 성장속도 Slow급 화재와 Medium급 화재에서는 화원위치에 상관없이 공기흡입형 감지기의 감지속도가 더 빨랐다. 하지만 Fast급 화재와 Ultra Fast급 화재에서는 화원위치에 따라 일반연기감지기의 감지속도가 더 빠른 것을 확인할 수 있었다. 결론: 공기흡입형 감지기는 화재성장속도가 빨라질수록, 둘째 화원의 위치가 공기흡입형 감지기 수신부보다 멀어질수록 같은 위치에 있는 연기감지기보다 성능이 낮아지는 것을 확인할 수 있었다. 그렇기에 화재성장속도가 빠른 가연물을 적치하는 창고에서는 공기흡입 형 감지기를 설치하더라도 공기흡입형 감지기의 수신부와 멀리 떨어진 위치에는 연기감지기를 추가로 부착하는 것이 화재 안전성을 높이는 방법이라고 판단된다.

국내 랙크식 창고 수용물품 등급분류를 위한 현장조사 (A Field Survey of Rack-Type Warehouse for Commodity Classification System in Korea)

  • 김운형;이영재
    • 한국화재소방학회논문지
    • /
    • 제30권2호
    • /
    • pp.98-105
    • /
    • 2016
  • 물류창고 화재위험성은 보관물품, 포장재 및 파렛 등의 가연성과 화재하중 그리고 창고 내부 천장높이, 랙크 등의 저장높이와 배치, 통로 폭 등에 따라 결정된다. 물류창고의 소화 또는 진압대책은 이러한 주요 인자를 고려한 가연물 등급 분류기준을 마련하고 스프링클러설비 설계기준을 적용해야 한다. 본 연구는 국내 물류창고의 자동식스프링클러 적용을 위한 첫 단계로서 경기도 소재 5개 물류단지 내 28개 창고 동을 대상으로 수용물품의 분포 및 창고 공간특성을 현장 조사하였다. 아울러 미국 유럽 및 일본의 물품 분류기준을 분석하였으며 이를 통하여 물류창고 수용물품의 등급분류기준 마련을 위한 기초자료를 제시하고자 한다.

랙크식 물류창고 조기 화재감지를 위한 최적 화재감지기 설치방법에 관한 실험연구 (An Experimental Study on the Optimum Installation of Fire Detector for Early Stage Fire Detecting in Rack-Type Warehouses)

  • 최기옥;김동석;홍성호
    • 한국안전학회지
    • /
    • 제32권2호
    • /
    • pp.38-45
    • /
    • 2017
  • This paper is an experimental study to find an optimal detection method for detecting fire early in a rack-type warehouse stored with goods. In this study, we constructed rack-type structure with the fourth floor of 13.5 m high and conducted fire experiments which were to measure flow of heat/smoke in rack-type structure and response time of fire detectors. The detectors used at experiments were fixed temperature type detectors, rate of rise detectors, photoelectric smoke detectors, air sampling smoke detectors and flame detectors. The used ignition sources are n-heptane fire for response of heat detection and cotton fire for response of smoke detection. The fixed temperature type detectors, rate of rise detectors and photoelectric detectors were installed to every rack level respectively. The results show that the rate of rise detector should be installed every 2 levels and photoelectric smoke detector should be installed every 4 levels for the early stage fire detection. Air sampling smoke detectors can detect fire early in response to control of sensitivity, but there is a problem in false alarm. The fixed temperature detector is not suitable for early stage fire detection in warehouse and flame detector not worked if flame is not visible, so it need to install combination with other detector.

국내 랙크식 창고의 방화관련 규정 개선에 관한 연구 (An Improvement of Fire Safety Code for Rack-Type Warehouse in Korea)

  • 김운형;이영재
    • 한국화재소방학회논문지
    • /
    • 제28권6호
    • /
    • pp.69-75
    • /
    • 2014
  • 최근 발생한 아모레퍼시픽 창고화재는 국내 랙크식 창고의 자동식소화설비 및 감지기 설치기준의 보완 및 개선의 필요성을 제시하고 있다. 물류창고는 보관물품에 따라 화재 확산율 및 열 방출비율이 다르며 저장높이, 랙크 배치, 통로폭, 물품의 양 등에 따라서 화재위험성이 결정된다. 고천정화에 따른 화재하중의 증가로 인하여 자동식 스프링클러설비가 작동하여도 가연물에 직접적인 침투효과에 한계가 있으며 화재감지기의 작동시간이 지연되어 초기소화에 실패할 확률이 높아진다. 이를 위하여 본 연구에서는 화재사례 및 국내외 관련규정비교 그리고 현장조사 등을 수행하여 랙크식 창고의 초기소화 및 제어성능을 확보하기 위한 수용물품의 위험도 분류 및 스프링클러 설치기준 개선방향과 화재피해를 최소화하기 위한 제도적 도입을 제안한다.