Abstract

A rack-type warehouse has the advantage of storing a large amount in a small area by loading goods vertically. But in terms of fire risk, the fire load is very high, which can cause massive damage in the event of a fire. In the United States, research has been actively conducted to minimize the spread of vertical fires, and relevant standards have been established and operated. In Korea, research and related standards are insufficient to prevent the vertical spread of rack-type warehouse fires. In this study, an experimental study was conducted to prevent the vertical spread of a rack-type warehouse fire using a horizontal barrier and in-rack sprinklers. As a result of the test, the horizontal barrier considering the continuous flame prevented the vertical spread of the flame for a certain time. However, the horizontal barrier with continuous flame did not show the effect of preventing continuous flame. The combination of the horizontal barrier and the in-rack sprinkler prevented the vertical spread of fire effectively. In addition, the heat collecting effect through the horizontal barrier was shown and helped the early operation of the in-rack sprinklers.

Keywords

References

  1. S. H. Hong et al., "A Study on the Classification of Domestic Fire Detector Using Response Time Index", J. Korean Soc. Saf., Vol. 32, No. 2, pp. 46-51, 2017. https://doi.org/10.14346/JKOSOS.2017.32.2.46
  2. K. O. Choi et al., "An Experimental Study on the Optimum Installation of Fire Detector for Early Stage Fire Detecting in Rack-Type Warehouses", J Korean Soc. Saf., Vol. 32, No. 2, pp. 38-45, 2017. https://doi.org/10.14346/JKOSOS.2017.32.2.38
  3. I. H.Yeo and G.H. Cho, "Application of Horizontal Barrier on a Rack to Reduce Fire Spread", Fire Sci. Eng., Vol. 31, No. 4, pp. 71-79, 2017. https://doi.org/10.7731/KIFSE.2017.31.4.071
  4. Architectural Institute of Japan, "Handbook on Design Calculation Methods of Fire Behavior", p. 30, 2018.
  5. FM Global, "Property Loss Prevention Data Sheet 8-1, Commodity Classification", 2014.
  6. NFPA 13, "Standard for the Installation of Sprinkler Systems, 2010.