• Title/Summary/Keyword: Underground subway fire

Search Result 66, Processing Time 0.033 seconds

THE COMPARISON ON THE CHARACTERISTIC OF THE FIRE DRIVEN SMOKE-FLOW FOR THE PLATFORM TYPES IN THE DEEPLY UNDERGROUND SUBWAY STATION (대심도 지하철 승강장의 종류별 연기전파특성 비교고찰)

  • Kim, H.B.;Jang, Y.J.;Lee, D.H.;Jung, W.S.;Whang, H.B.
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2010.05a
    • /
    • pp.505-507
    • /
    • 2010
  • In this paper, the comparison on the fire driven smoke flow for platform types was conducted in the Deeply Underground Subway Station. Soongsil-University station (47m depth) as a bank type platform and Mandeok Station as a island type platform were selected for fire numerical simulation. The characteristics of fire driven smoke-flows were analyzed from the simulation results. The proper plan of evacuation against fire for each type was considered through the results.

  • PDF

Numerical Study on the characteristics of fire driven flow for smoke ventilation system operating in the deeply underground subway station (대심도 지하역사에서의 화재시 급 배기 동작유무에 따른 열 연기 거동 분석)

  • Jang, Yong-Jun;Kim, Hag-Beom;Lee, Chang-Hyun;Jung, Woo-Sung
    • Proceedings of the KSR Conference
    • /
    • 2008.11b
    • /
    • pp.66-72
    • /
    • 2008
  • In this study, transient 3D numerical simulations were performed to analyze the characteristics of fire driven flow for smoke ventilation system operating conditions in the deeply underground subway station. The smoke flow patterns were compared and discussed under smoke fan operating mode and off mode in the platform. Soongsil Univ. station(line number 7)was chosen for simulation which was the one of the deepest underground subway stations in the each lines of Seoul. The geometry for model is 365m in length include railway, 23.5m for width, 47m for depth. Therefore 10,000,000 structured grids were used for fire simulation. The parallel computational method for fast calculation was employed to compute the heat and mass transfer eqn's with 6 CPUs(Intel 3.0GHz Dual CPU, 12Cores) of the linux clustering machine. The fire driven flow was simulated with using FDS code in which LES method was applied. The Heat release rate was 10MW and The Ultrafast model was applied for the growing model of the fire source.

  • PDF

Investigation for Fire Flow of the Deeply Underground Shin-Gum-Ho Subway Station (대심도 신금호역사의 화재 유동에 대한 고찰)

  • Jang, Yong-Jun;Park, Il-Soon;Kim, Jin-Ho;Jung, Woo-Sung;Kim, Hag-Beom;Lee, Chang-Hyun
    • Proceedings of the KSR Conference
    • /
    • 2010.06a
    • /
    • pp.110-115
    • /
    • 2010
  • Recently the deeply underground tunnels have been increased along the subway railroads of urban area compared to the past subway railroads. The Shin-Gum-Ho subway station (the Fifth lines, the depth : 46m) which is the third among the deep subway stations in the Korea was chosen as the model of deeply underground stations, and attempted to do simulation of fire. This station consists of three entrance, the basement first floor (B1), the basement second floor (B2), the basement eighth floor or platform (B8) and escalators and stairs from B2 to B8. The total number of grid was about 9,000,000 to make simulation of fire and smoke from the platform to entrance in this research, and the grid system was divided into 19 blocks to increase the efficiency of this simulation. The FDS (Fire Dynamics Simulation) was chosen to make the simulation of fire, and the model of turbulent flow was LES (Large Eddy Simulation). Each block is processed in a CPU using parallel processing of MPI (Message Passing Interface). The resource of CPU for this simulation is a ten of Intel 3.0 GHz Dual CPU (20 CPU).

  • PDF

A Study on the Risk Assessment of the Underground Space -The Estimation of Smoke Reservoir Screen for Smoke Control in Subway Station Platform (지하공간의 위험성평가에 관한 연구 -지하철 역사내의 연기제어를 위한 제연경계벽의 효용성 평가)

  • Roh Sam-Kew;Hur Jun-Ho
    • Fire Science and Engineering
    • /
    • v.18 no.4
    • /
    • pp.103-109
    • /
    • 2004
  • The risk of underground space become an important issue of life safety thought the Taeku subway line Accident. It is essential to study of smoke control screen to minimize the damage of human life because of smoke passage and passenger evacuation routes are on the same vertical and dispersion movement. The Fire modeling result shows the effect of fire control screen can save the evacuation time about 2-2.5 times compare to existing the system However, The designs of fire control screen need to be complied with smoke control ventilation system to present optimum design and the position of installation.

Experimental and Numerical Studies on Heat/Smoke Behavior due to a Fire on Underground Subway Platform (I) - Experimental Approach - (지하철 역사 승강장 화재발생시 열/연기 거동 분석을 위한 실험 및 수치 연구(I) - 실험적 접근 -)

  • Park, Won-Hee;Kim, Dong-Hyeon;Chang, Hee-Chul;Kim, Tae-Kuk
    • Fire Science and Engineering
    • /
    • v.20 no.3 s.63
    • /
    • pp.9-14
    • /
    • 2006
  • In this study boundary velocity which is one of the important boundary conditions for numerical simulation for subway station on fire are experimentally obtained. The tests were conducted according to its operating mode of the ventilation systems in the platform: smoke extraction ventilation mode in occurrence of fire and normal ventilation mode for air conditioning. Velocities are measured at various points on the platform. To examine smoke extraction and air supply capacity in the platform level, air velocities were checked on opening vents. Numerical analysis under normal ventilation mode without fire is conducted by using measured boundary conditions, and the numerical results are compared with the measured velocities on the platform.

A transient CFD simulation of ventilation system operation for smoke control in a subway station equipped with a Platform Screen Door(PSD) when a train under fire is approaching the station (화재열차의 역사 접근 시 PSD가 설치된 역사 제연을 위한 환기장치 운전 비정상상태 해석)

  • Shin, Kyu-Ho;Hur, Nahm-Keon;Won, Chan-Shik
    • 유체기계공업학회:학술대회논문집
    • /
    • 2006.08a
    • /
    • pp.269-272
    • /
    • 2006
  • The heat and smoke which generated by subway under fire is one of the most harmful factor in air tighten underground station. To prevent this, Trackway Exhaust System(TES) can be used. The heat released from the train running in the tunnel raises the temperature at the platform and the trackway, and thus proper ventilation system is required for comfortable underground environment. When the fire is occurred, TES is operated as smoke exhaust mode from normal ventilation mode. In the present study, the subway station which is one of the line number 9 in Seoul subway is modeled, and fired situation is simulated with several ventilation mode of ventilation system in trackway. For this simulation whole station is modeled. Non steady state 3D simulation which considered train under fire is entering to the station is performed. Temperature and smoke distribution in platform and trackway are compared. To represent heat by fire, heat flux was given to the fired carriage, also to describe smoke by fire, concentration of CO is represented. As the result of present study, temperature and smoke distribution is different as the method of ventilation in trackway and platform is changed. In over side of trackway, the fan must be operated as exhaust mode for efficient elimination of heat and smoke, and supply mode of fan operation in under side shows better distribution of heat and smoke. The ventilation system which is changed from ventilation mode to exhaust mode can be applied to control heat and smoke under fire.

  • PDF

The Smoke Propagating Distance in the Reduced-scale Model for a Subway Railroad Tunnel (축소 모형을 이용한 지하철터널에서의 연기전파거리 측정)

  • Kim, Myung-Bae;Choi, Byung-Il;Oh, Chang-Bo;Han, Yong-Shik
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.7 no.4
    • /
    • pp.295-304
    • /
    • 2005
  • The smoke propagating distances are measured in case that a fire occurs within the subway railroad tunnel. The tunnel is 800m long and the dimension of the cross-section is. Three vertical shafts exist for smoke ventilation. The experiments are performed using the 1/50 reduced-scale model. The smoke propagating distances are measured by thermocouples and by visualization for the accuracy. In order to understand the effect of a fire size and ventilation capacity of the shafts on the smoke propagating distance, 9 test scenarios are chosen. Based on the results, the smoke propagating distance is shown to be important criteria for the ventilation design of the tunnel.

  • PDF

A study of comparative of evacuation time by platform type according to the propagation speed of smoke in subway platform fire (지하철 승강장 화재시 연기의 전파속도에 따른 승강장 형태별 피난시간 비교·분석 연구)

  • Kim, Jin-Su;Rie, Dong-Ho
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.19 no.4
    • /
    • pp.577-588
    • /
    • 2017
  • There are many constraints, both economically and ethically that experimenting human evacuation behavior in situations such as fire. Therefore, the evacuation behavior is simulated based on the existing studies. In recent years, the foundation has been established as computer performance advances, models closer to reality can be studied. In this study, the evacuation time in the subway platform was analyzed from modeling human behavior and smoke propagation in a fire. The evacuation efficiency was also examined by dividing the shape of the subway station platform by the stair position and comparing the evacuation times for each platform. As a result, it was found that the side platform was longer than the island platform by 36.82% more time to evacuation. The shape of the stairs is most advantageous in terms of evacuation form side type platform was 210 seconds and island type platform was 186 seconds, when a fire occurs in the center of the platform. And most favorable in location of evacuation stairs were located at 2/5 point and 4/5 from depending on the step location.

Experimental and Numerical Studies on Heat/Smoke Behavior due to a Fire on Underground Subway Platform (II) - Numerical Approach - (지하철 역사 승강장 화재발생시 열/연기 거동 분석을 위한 실험 및 수치 연구(II) - 수치적 접근 -)

  • Chang, Hee-Chul;Kim, Tae-Kuk;Park, Won-Hee;Kim, Dong-Hyeon
    • Fire Science and Engineering
    • /
    • v.20 no.3 s.63
    • /
    • pp.15-20
    • /
    • 2006
  • In this study the flow characteristics of smoke and heat on a bank type platform of the underground subway station are studied numerically by considering two different emergency operation modes. Effects of the natural flow through the tunnel and the stair ways are considered in the numerical simulations by using the measured velocities presented in Part I as the boundary condition. Distributions of heat, smoke, visible range and toxic gas on the platform are analysed for different smoke extraction flowrates corresponding to the two different emergency operation modes. The numerical results show that the extraction flowrate affects the smoke control performance significantly by improving the smoke removal performance as the extraction flowrate is increased.

A Study on the Risk Management Information System of the Underground Space - focused on Fire Growth Risk Assessment System- (지하공간의 위험관리정보시스템에 관한 연구 -화재확산평가시스템 중심으로-)

  • 박종근;노삼규
    • Fire Science and Engineering
    • /
    • v.16 no.4
    • /
    • pp.49-58
    • /
    • 2002
  • A large number of accidents at an underground place have been happening, including the gas explosion under construction of subway; the fires of underground utility and underground shopping malls, and other explosion, at home and abroad recently. These accidents make the function of a city ineffective due to the paralyses of electricity and communications net as well as the loss of property and cause people to feel unsecured with accompaniment of a heavy of toll of lives. This research will show evaluation methods of a numerical value of expected average loss space of combustion with the use of probability in order to present potential risk of combustion growth that underground space might cause, and how designer decides a system that enables us to compare and evaluate relatively the effectiveness of measures for preventing burning by calculating the expansion route and the damage size of burning in case of fire.