• 제목/요약/키워드: URD cables

검색결과 14건 처리시간 0.031초

지중 케이블의 외피 재질 및 구조에 따른 수분침투 특성 (Water Ingress of URD Power Cables with the Jacketing Materials and the Cable Structures)

  • 한재홍;김동명;이재봉
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2002년도 하계학술대회 논문집
    • /
    • pp.244-247
    • /
    • 2002
  • In order to evaluate the water ingress to URD power cables with the jacketing materials and the cable structures, water vapor transmission (WVT) tests were carried out by the ASTM and the TEPCO's specification. All polyolefin compounds showed the superior water suppression to conventional PVC. Especially, linear polyethylenes have very low WVT. In case of cable structures, Allaminate cables showed the significant water suppression due to the watertight structure. Accordingly, it can be concluded that jacketing material and cable structure play an important role in the water suppression of URD power cables.

  • PDF

배전케이블 진단결과와 교류절연파괴강도의 상관성 (Relation between Dielectric Diagnosis and ACBD Strength in URD Cables)

  • 한재홍;김주용;김동명;이병성;정년호
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 추계학술대회 논문집
    • /
    • pp.484-487
    • /
    • 2000
  • This study is for assessing a reliability of diagnostic device through comparing diagnostic results to ACDB strength. The dielectric diagnosis using IRC (isothermal relaxation current) measurement was carried on service-aged cables. From this study, there was little correlation between dielectric diagnosis and ACBD strength in long distance cables. But the correlation between them showed in short distance below 200 m. Therefore, it is desirable to diagnose the URD cables in short distance.

  • PDF

지중 케이블용 외피 컴파운드 개발 (Development of Jacket Compounds for URD Power Cables)

  • 한재홍;김주용;김동명;송일근
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2002년도 춘계학술대회 논문집 유기절연재료 전자세라믹 방전플라즈마 일렉트렛트 및 응용기술
    • /
    • pp.7-10
    • /
    • 2002
  • In this study, polyolefin compounds were developed and evaluated for replacing a jacket material of URD power cables. The characteristics of compounds were investigated by water vapor transmission (WVT) test and mechanical test. In WVT test, all polyolefin compounds showed the superior water resistance to conventional PVC. The molecular structure and density of polyolefin play an important role in WVT. Also, polyolefin compounds showed the suitable characteristics in mechanical test. Especially, polyolefin compounds having linear molecules showed the superior characteristics to LDPE ones. From this study, it can be considered that polyolefin compounds may be suitable to jacket material for URD power cables.

  • PDF

지중 배편케이블의 열화에 미치는 온수의 영향 (Effects of Hot Water on the Aging of URD Power Cables)

  • 한재홍;송일근;김주용;이병성;정종욱
    • 한국전기전자재료학회논문지
    • /
    • 제15권7호
    • /
    • pp.609-614
    • /
    • 2002
  • In this study, we investigated the effects of hot water on the aging of URD power cables due to the hot water ingress to power distribution lines. Hot water contacted and non-contacted cables extracted from 2 distribution lines were characterized by the measurement of oxidation induction time(OIT) and chemical structure. In OIT measurement, hot water contacted cables showed the shorter OIT than non-contacted ones. Especially, hot water contacted insulation layer near insulation shield showed the shortest OIT. In chemical structure analysis, the antioxidant content was decreased and the acid concentration was increased by hot water ingress. From this results, it can be concluded that the hot water ingress to power cable may be accelerate the aging by means of antioxidant consumption.

지중 배전케이블용 자켓 컴파운드의 특성평가 (Evaluation of Jacket Compounds for Underground Distribution Power Cables)

  • 한재홍;송일근;김동명;이재봉;정창수
    • 한국전기전자재료학회논문지
    • /
    • 제15권8호
    • /
    • pp.687-694
    • /
    • 2002
  • In order to replace the jacket material for URD power cables, the 6 kinds of polyethylene compounds were manufactured and evaluated. The characteristics of the compounds were investigated by water vapor transmission (WVT) test, thermal and mechanical test. In WVT test, all the polyethylene compounds showed the superior water resistance to conventional PVC. The molecular structure and density of polyethylene play an important role in WVT. Also, the polyethylene compounds showed the suitable characteristics in thermal and mechanical test. Especially, the linear polyethylene compounds showed the superior characteristics to LDPE ones. Due to the fillers in compounds, the abrasion resistance was decreased and the cut-through resistance was increased. From this study, it can be considered that the polyethylene compounds may be suitable to jacket material for URD power cables.

파괴수명예측을 통한 지중배전용 전력케이블의 열화 진단 (Aging Diagnosis of Underground Distribution Power Cables Using Breakdown Lifetime Prediction)

  • 김충배;이정빈;임장섭;장영학;이진;김태성
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1999년도 춘계학술대회 논문집
    • /
    • pp.222-225
    • /
    • 1999
  • Degradation diagnosis of XLPE insulated URD cables was accomplished through out new method. which was to be analyzed non-electrical experiments and synthesized by degradation points. To supplement this method, it was also carried out using several electrical analyses. Breakdown voltages were measured and breakdown lifetimes were Predicted appling for Weibull distribution function. As a result, breakdown lifetime in failure cables was shorted up to 1/3 times than that in general cables. It was very available to estimate cable degradation using above method, but it needs further study on XLPE insulated URD cables in order to improve reliability.

  • PDF

전력케이블 열화진단기법의 현장적용 (Field Application of Power Cable Diagnosis System)

  • 김주용;한재홍;송일근;김상준;이재봉;오재형
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2002년도 춘계학술대회 논문집 유기절연재료 전자세라믹 방전플라즈마 일렉트렛트 및 응용기술
    • /
    • pp.148-151
    • /
    • 2002
  • In order to prevent the failures of underground distribution power cables we need to measure insulation condition in the field. Until now we used DC high voltage as a power source for the cable diagnosis but it was not proper method to the XLPE insulation cables because DC high voltage can affect sound insulation and can't diagnose exactly insulation degradation. For these reasons we imported isothermal relaxation current measurement system called by KDA-1 from germany but it's reliability did not proved in our URD cables. DC voltage decay measurement system was developed by domestic company but they don't have field experience. In this paper we tried to prove reliability of these two systems in the field. Through the field diagnosis and Ac breakdown test the two systems showed similar results.

  • PDF

22.9[kV] 지중배전용 전력케이블의 전기적 특성과 파괴수명 고찰 (The Consideration of Electrical Characteristics and Breakdown Lifetime in 22.9[kV] Underground Distribution Power Cables)

  • 김충배;홍경진;임장섭;정우성;김상준;김태성
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제48권9호
    • /
    • pp.628-633
    • /
    • 1999
  • Degradation diagnosis of XLPE insulated URD cables was accomplished through out new method, which was to be analyzed by non-electrical experiments and synthesized by degradation points. To supplement this method, It was also carried out using several electrical analyses. Tan$\delta$ had commonly a different tendency by means oftemperature and frequency and also appeared higher at the outer part rather than innerpart of insulator. PD-q increased generally in proportion to the applied voltage andshowed regular patterns in relation to the thickness of insulator. Breakdown voltageswere measured and breakdown lifetimes were predicted appling for Weibull distribution function. As a result, breakdown lifetime in failure cables was shorter up to$\fraction one-third$ times than that in general cables. It was very available to estimate cable degradation using above method, but it needs further study on XLPE insulated URD cables in order to improve reliability.

  • PDF

새로운 지중배전케이블용 절연재료의 공간전하 거동 (Space Charge Behaviors of New Insulating Materials for URD cables)

  • 고정우;서광석;김종은;남윤선;김덕주
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1998년도 추계학술대회 논문집
    • /
    • pp.207-210
    • /
    • 1998
  • Electrical properties such as space charge distribution and electrical conduction of XLPE/VLDPE blends were studied. When the VLDPE is blended, residual charge inside XLPE increases. In case of electrical conduction characteristics, there were no changes in electrical conduction mechanism, space charge limited conduction. XLPE/VLDPE blend including crosslinking coagent showed relatively small current density. It might be due to the carbonyl group in crosslinking coagent.

  • PDF

Development of Waterproof Jacket Materials for Power Cables

  • Han, Yong-Huei;Jung, Jong-Wook;Kwon, Tae-Ho;Song, Hyun-Seok;Koo, Kyo-Sun;Han, Byung-Sung
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • 제3C권4호
    • /
    • pp.146-154
    • /
    • 2003
  • This paper describes various characteristics of the new compounds for cable jackets and model cables advanced in waterproof performance in order to essentially solve the problems of underground (URD) distribution class power cable failures. Several compounds were manufactured by the inclusion of additives to base resins available in Korea and tested for basic property, mechanical and electrical characteristics. Two model cables were created by using the compounds determined in the test as being the most appropriate for new structured model cable jacket material. The waterproof performance and mechanical strength of the new cable jackets were verified by applicable tests. As a result, MDPE and LLDPE compounds were superior as cable jackets in both mechanical and electrical characteristic aspects when compared with conventional PVC. In addition, the model cables composed of the new compounds based on MDPE showed good quality results in the water permeability test.