Browse > Article
http://dx.doi.org/10.4313/JKEM.2002.15.7.609

Effects of Hot Water on the Aging of URD Power Cables  

한재홍 (한국전력공사 전력연구원)
송일근 (한국전력공사 전력연구원)
김주용 (한국전력공사 전력연구원)
이병성 (한국전력공사 전력연구원)
정종욱 (한국전력공사 전력연구원)
Publication Information
Journal of the Korean Institute of Electrical and Electronic Material Engineers / v.15, no.7, 2002 , pp. 609-614 More about this Journal
Abstract
In this study, we investigated the effects of hot water on the aging of URD power cables due to the hot water ingress to power distribution lines. Hot water contacted and non-contacted cables extracted from 2 distribution lines were characterized by the measurement of oxidation induction time(OIT) and chemical structure. In OIT measurement, hot water contacted cables showed the shorter OIT than non-contacted ones. Especially, hot water contacted insulation layer near insulation shield showed the shortest OIT. In chemical structure analysis, the antioxidant content was decreased and the acid concentration was increased by hot water ingress. From this results, it can be concluded that the hot water ingress to power cable may be accelerate the aging by means of antioxidant consumption.
Keywords
URD power cable; Aging; Hot water; Antioxidant;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 지중배전 설계편람(TM. 96EJ30. 1999.102) /
[ 김병숙;조성수 ] / 한국전력연구원 연구 과제 최종보고서
2 /
[ 설규환 ] / 2000년 지중고장 분석 및 대책
3 Contribution to the investigation of polyethylene by infrared techniques /
[ E. Cernia;C. Mancini;G. Montaudo ] / Polym. Lett.   DOI
4 Characterization of XLPE-Insulated Underground Residential Power Calbes /
[ K. S. Suh;C. H. Lee;M. K. Lee;J. H. Han;S. J. Kim ] / Trans. KIEE,
5 방사선조사에 따른 원전 저압케이블용 절연재료의 특성분석 /
[ 박정기;이우선;한재홍 ] / 전기전자재료학회논문지   과학기술학회마을
6 A technique for estimation of residual lifetime of underground distribution calbes by antioxidation of insulation /
[ J. E. Kim;K. S. Suh;H. G. Yoon;J. S. Lim;J. H. Han;S. J. Kim;G. J. Lee ] / Trans. on KIEE
7 Characterization of polyethylene for power cable insulation /
[ T. Niwa;S. Nakayama;K. Kobayashi;T. Nakatsuka;T. Takahashi ] / Trans. IEEJ
8 Effects of molecular structure on electrical conduction in low-density polyethylene above Its melting point /
[ K. Iida;J. S. Kim;S. Nakamura;G. Sawa ] / IEEE. Trans. Electr. Insul.
9 전력케이블용 반도전재료의 설계기술 /
[ 한재홍;송일근;임장섭;이동영 ] / B. of KIEEME   과학기술학회마을
10 지중 배전케이블의 고장원인 특성분석 /
[ 정창수;이우선;한재홍 ] / 전기전자재료학회논문지   과학기술학회마을
11 Oxidative Induction Time of Polyolefins by Thermal Analysis /
[] / ASTM. Std. D3895
12 지중 배전케이블의 절연성능 향상에 관한 연구(TM.OOPC02. M2001.451) /
[ 한재홍;김주용;김동명 ] / 한국전력연구원 연구 과제중간 보고서
13 배전케이블 수명예측 기준결정 및 열화진단 시스템 구축(TR.95YJ16.L. 199787) /
[ 김상준;한재홍;김주용;송일근 ] / 한국전력연구원 연구 과제 최종보고서