This study is for assessing a reliability of diagnostic device through comparing diagnostic results to ACDB strength. The dielectric diagnosis using IRC (isothermal relaxation current) measurement was carried on service-aged cables. From this study, there was little correlation between dielectric diagnosis and ACBD strength in long distance cables. But the correlation between them showed in short distance below 200 m. Therefore, it is desirable to diagnose the URD cables in short distance.