A Novel Sensitivity Verification Method for the UHF Partial Discharge Detection System in Gas Insulated Switchgear (GIS) (가스절연개폐장치용 UHF 부분방전검출장치의 새로운 감도 측정방법)

  • Gu, Seon-Geun;Park, Gi-Jun;Yun, Jin-Yeol
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.50 no.9
    • /
    • pp.450-455
    • /
    • 2001
  • We proposed a new sensitivity verification method for the UHF partial discharge(PD) detection system. Initially, we measure the UHF power induced by 5 pC PD which takes place near UHF sensor. Subsequently, we inject the swept UHF signal from a network analyzer into the GIS and measure the attenuation of the signal along the 71S Both the UHF power by 5 pC PD and the attenuation make it possible to verify the sensitivity and spatial coverage of the PD detection system. This method doesn\`t require the calibration of injected pulse type UHF signal into the GIS and makes us precisely measure the attenuation in frequency domain.

  • PDF

Performance Verification of Gas Insulated Switchgear using UHF Partial Discharge Diagnosis Method (UHF법 부분방전 진단기법에 의한 가스절연 개폐장치의 성능검증)

  • Kim, J.S.;Park, K.S.;Song, Y.P.;Kim, D.K.;Kim, J.H.
    • Proceedings of the KIEE Conference
    • /
    • 2002.11a
    • /
    • pp.37-39
    • /
    • 2002
  • UHF method is very effective to diagnosis for partial discharge of GIS. In generally, inner UHF sensor can be attached on sheath cover of GIS under construction for periodic inspection. However, there is no inner UHF sensor for GIS of the domestic substation. We used the outer UHF sensor attached on spacer for GIS of existing substation. In this paper, we report the diagnosis result of partial discharge on 800kV GIS in domestic substation. From these results, we can find the quantity, reason and location of PD and certificate the performance of UHF method for partial discharge diagnosis of GIS.

  • PDF

UHF & HF RFID Credit Card Size Tag Antenna Designs Using Silver-Ink and Jumper Structure (실버잉크와 점퍼구조를 사용한 신용카드 크기의 UHF & HF RFID 태그 안테나)

  • Nam, Sehyun;Chung, Youchung
    • The Journal of Korean Institute of Electromagnetic Engineering and Science
    • /
    • v.27 no.11
    • /
    • pp.972-977
    • /
    • 2016
  • This paper introduces development process and results of HF & UHF band(13.56 MHz, 920 MHz) tag antennas using a single-side printing method on a PE film. The size of tag antenna is designed in the area of $80mm{\times}50mm$, little bit smaller than a credit card. The UHF tag antenna, $76mm{\times}44mm$, is located at the outside of the card size tag antenna, and the HF tag antenna, $40 mm{\times}42 mm$, is located at the center of the UHF tag antenna. The UHF and HF tag antennas are designed with consideration of coupling effects. The single-side printing method with a jumper structure without using a via is used to make a loop antenna of HF tag antenna. The reading range of UHF tag antenna is about 6m, and the reading of HF tag antenna is about 5 cm. The designed tag antennas have long enough reading ranges for both bands. The tag is applicable to logistics and authentification.

Comparative analysis of PRPD method and UHF sensor method for Partial Discharge in air (공기중 부분방전에 대한 PRPD측정법과 UHF센서측정법의 비교분석)

  • Lee, K.W.;Lee, Y.H.;Park, S.H.;Jang, D.U.;Kang, S.H.;Lim, K.J.
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.07b
    • /
    • pp.882-885
    • /
    • 2002
  • Assessing the condition of air insulation by measuring electromagnetic wave generated in it by partial discharges gives warning of developing faults and breakdown which may give some bad effects to other thing concerned with it. Electromagnetic wave are taken from UHF antenna with 20k ~ 2GHz frequency range. The signal waveform and FFT(Fast Fourier Transform) results from UHF antenna for PD(partial discharge) generated from two different electrode(needle-plane, needle-needle) configurations are shown and it is processed by using PRPD($\Phi-q-n$ distribution) method. Cumulative pulse sequence during 100 period is compared with PRPD method. This also will show the possibility of making apparent distinction between two PD sources.

  • PDF

PD Monitoring of Transformer Using UHF Technique (UHF 기술을 응용한 전력용 변압기의 PD 모니터링)

  • Choi, Yong-Sung;Hwang, Jong-Sun;Lee, Kyung-Sup
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.2116-2117
    • /
    • 2008
  • This system has successfully captured long intermittent discharge signals that hadn't been detected through conventional techniques, and solved the problem successfully. The results demonstrate that UHF technique has great advantages for on-line PD monitoring of transformers. By adopting the peak detection technique, it becomes easy and effective for the transplantation of the phase-resolved pattern recognition technique from conventional method to UHF method, and then to realize continuous on-line monitoring, source characterization and trending analysis.

  • PDF

UHF Narrow Band Type Partial Discharge Diagnosis Method for the Internal Insulation Performance Verification of the Gas Insulated Switchgear (가스절연 개폐장치의 내부절연 성능검증을 위한 UHF 협대역 부분방전 진단법)

  • Song Won-Pyo;Kim Jung-Bae;Kim Min-So;Jung Jae-Ryong;Park Seung-Jae;Ko Heui-Suk
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.54 no.9
    • /
    • pp.414-420
    • /
    • 2005
  • A method for partial discharge diagnosis based on UHF narrow band type for GIS has been developed and calibrated. In generally, PD cannot be directly measured under on-line condition, but we can indirectly measure the electromagnetic wave made by PD using the high-frequency antenna. Compared with VHF band, electromagnetic waves of UHF band have a low influence for external noise in high-voltage substation. Therefore, we can detect the real abnormality with several pC in GIS using UHF narrow-band type method. For the case of no internal VHF sensor for GIS of the domestic substation, it has applied to use the external UHF sensor attached in spacer in GIS of existing substation. In this paper, we firstly described the technique of partial discharge measurement using frequency analysis and phase analysis in UHF band. Secondly, we presented the results of sensitivity test, the relationship of dBm-pC and diagnosis result of the cause of PD source by phase analysis. And then, we report the diagnosis result of partial discharge on the real GIS in domestic substation. These results make above method applicable for measurement of quantity and cause of PD for real operation GIS in high-voltage substation.

On-line PD Monitoring Using UHF Technique (UHF 가술을 이용한 온라인 PD 모니터링)

  • Choi, Yong-Sung;Lee, Kyung-Sup
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2008.04c
    • /
    • pp.115-118
    • /
    • 2008
  • A field-oriented UHF system for on-line PD monitoring of transformers. is designed, which has been installed inside the oil tank of a transformer by two ways: on-line installing mode through the oil-valve and pre-installing mode through the man hole/hand hole cover. This system has successfully captured long intermittent discharge signals that hadn't been detected through conventional techniques, and solved the problem successfully. The results demonstrate that UHF technique has great advantages for on-line PD monitoring of transformers. By adopting the peak detection technique, it becomes easy and effective for the transplantation of the phase-resolved pattern recognition technique from conventional method to UHF method, and then to realize continuous on-line monitoring, source characterization and trending analysis.

  • PDF

On-line Insulation Diagnostic by PD Monitoring Field Practical of UHF Technique for On-line PD Monitoring (UHF 기술을 이용한 온라인 부분방전 모니터링)

  • Oh, Yong;Choi, Yong-Sung;Hwang, Jong-Sun;Lee, Kyung-Sup
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.57 no.2
    • /
    • pp.176-180
    • /
    • 2008
  • A field-oriented UHF system for on-line PD monitoring of transformers is designed, which has been installed inside the oil tank of transformer in a substation by two ways: on-line installing mode through the oil-valve and pre-installing mode through the man hole/hand hole cover. This system has successfully captured long intermittent discharge signals that hadn't been detected through conventional techniques, and solved the problem successfully. The results demonstrate that UHF technique has great advantages for on-line PD monitoring of transformers. By adopting the peak detection technique, it becomes easy and effective for the transplantation of the phase-resolved pattern recognition technique from conventional method to UHF method, and then to realize continuous on-line monitoring, source characterization and trending analysis.

A Study on Estimation of Breakdown Location using UHF Sensors for Gas Insulated Transmission Lines (UHF센서를 이용한 가스절연송전선로 절연파괴 위치 추정에 관한 연구)

  • Park, Hung-Sok;Han, Sang-Ok
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.4
    • /
    • pp.805-810
    • /
    • 2011
  • This paper deals with the method and algorithm used to find fault locations in gas insulated transmission line. The method uses UHF sensors and digital oscilloscope to detect discharge signals emitted to the outside through insulating spacer in the event of breakdown inside GIL. UHF sensors are the external type and installed at outside of insulating spacers of GIL. And we used wavelet signal processing to analyze the discharge signals and confirm the exact fault location findings in the GIL test line. This method can overcome demerit of TDR(Time Domain Reflectometer) method having been applied to detect fault location for conventional underground transmission lines, and Ground Fault Sensors used in conventional GIS systems. TDR method requires high level of specialty and experience in analyzing the measured signals. Ground fault sensors are installed inside GIL and can be destroyed by high transient voltage. This paper's method can simplify the fault location process and minimize the damage of sensors. In addition, this method can estimate the fault location only by the time difference when discharge signals are arrived to detecting sensors at the ends of GIL sections without reasons of breakdown. To test the performance of our method, we installed sensors at the ends of test line of GIL(84m) and sensed discharge signals occurred in GIL, energized with AC voltage generator up to 700kV.

Modelling Method for Removing Measurement Uncertainty in Chip Impedance Characterization of UHF RFID Tag IC (UHF RFID 태그 칩의 임피던스 산출 불확실성 제거를 위한 모델링 방법)

  • Yang, Jeenmo
    • The Journal of Korean Institute of Electromagnetic Engineering and Science
    • /
    • v.25 no.12
    • /
    • pp.1228-1235
    • /
    • 2014
  • Input impedance of UHF RFID tag chip is needed to design a tag. In determining the chip impedance, direct measurement method is adopted commonly. In this paper, problems generated from fixtures that interface between tag chip and coaxial-oriented measurement instrument are investigated and the result of the problems is shown, when the direct measurement method is applied. As an alternative to the method, a modeling method is proposed and its validity and accuracy are shown.