Development of a High Pressure Turbine Bypass System Pressure Control Model for Power Plant Simulator (발전소 시뮬레이터를 위한 고압 터빈 바이패스 압력 제어 모델 개발)

  • Byun, Seung-Hyun;Lee, Joo-Hyun;Lim, Ick-Hun
    • Journal of the Korea Society for Simulation
    • /
    • v.20 no.4
    • /
    • pp.49-58
    • /
    • 2011
  • It is required that a developed control system should be verified using simulator in terms of functionality and reliability prior to application to a power plant that is a very critical facility in the industry. In this paper, the control model for turbine bypass system was developed for power plant simulator. In order to develop the control model for turbine bypass system, the tool that can be used to implement turbine bypass control logic was developed based on the turbine bypass control system manual. The developed tool was merged into the simulator development environment. The functionality of the developed tool was verified via the simulation based on the each function block specification. The HP turbine bypass pressure control logic was implemented using the developed tool and was integrated with process models and other control models such as boiler control model, turbine control model and boiler feed water pump turbine control model for 500 MW korean standard type fossil power plant. Finally, the validity of the developed control model was shown via simulation result under the integrated simulation environment.

A Study on Turbine Control and Turbine Bypass Control during Startup of Thermal Power Plants (화력발전소 기동시 터빈 바이패스 시스템과 터빈 제어에 관한 고찰)

  • Choi, In-Kyu;Park, Doo-Yong
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.1664_1665
    • /
    • 2009
  • Many years ago, most of thermal power plants built in this country were of subcritical pressure, of medium or small size, of constant pressure operations and of drum type steam generators with circulation type boilers. But, nowadays almost all of them were of high efficiency, of supercritical pressure, of big capacity, of sliding pressure operations, and of once through type steam generator. It has such advantage as the reduction of startup duration, but it control system and operation method are very complicated. It has a big difference in operation method of turbine and boiler. The feedforward control needs to be introduced to prevent such problems as thermal shock during the transit from normal operation into bypass operation. This paper introduces the turbine control and turbine bypass control during startup of thermal power plants.

  • PDF

Analysis of flow Field in a steam turbine LP/HP Bypass control Valve (증기터빈 Bypass Valve 의 유동장 해석)

  • Choi, Ji-Yong;Kim, Kwang-Yong
    • 유체기계공업학회:학술대회논문집
    • /
    • 2005.12a
    • /
    • pp.437-440
    • /
    • 2005
  • In the present work, characteristics of the flow in CAGE of a steam turbine LP/HP Bypass control valve for thermal power plant are investigated. The flow field is analyzed numerically by solving steady three-dimensional Reynolds-averaged Navier-Stokes equations. Shear stress transport (SST) model is used as turbulence closure.

  • PDF

Simulation for Pitch Angle Control Strategies of a Grid-Connected Wind Turbine System on MATLAB/Simulink

  • Ro, Kyoung-Soo;Choi, Joon-Ho
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.1
    • /
    • pp.91-97
    • /
    • 2007
  • This paper presents a pitch angle controller of a grid-connected wind turbine system for extracting maximum power from wind and implements a modeling and simulation of the wind turbine system on MATLAB/Simulink. It discusses the maximum power control algorithm for the wind turbine and presents, in a graphical form, the relationship of wind turbine output, rotor speed, and power coefficient with wind speed when the wind turbine is operated under the maximum power control algorithm. The objective of pitch angle control is to extract maximum power from wind and is achieved by regulating the blade pitch angle during above-rated wind speeds in order to bypass excessive energy in the wind. Case studies demonstrate that the pitch angle control is carried out to achieve maximum power extraction during above-rated wind speeds and effectiveness of the proposed controller would be satisfactory.

Analysis of Flow Field in a Steam Turbine Bypass Valve (증기터빈 바이패스밸브 케이지 유동장 해석관한 연구)

  • Choi Ji-Yong;Cho An-Tai;Kim Kwang-Yong
    • The KSFM Journal of Fluid Machinery
    • /
    • v.9 no.4 s.37
    • /
    • pp.36-42
    • /
    • 2006
  • In the present work, characteristics of the flow in the cage of a steam turbine bypass control valve for thermal power plant are investigated. Experimental measurement for wall static pressure has been carried out to validate numerical solutions. And, the flowfield is analyzed by solving steady three-dimensional Reynolds-averaged Navier-Stokes equations. Shear stress transport (SST) model is used as turbulence closure. The effects of the flow area between stages of the cage on the pressure drop are also found.

A comparison of steam turbine control systems according to adoption of turbine bypass system (바이패스 시스템 체용 유무에 따른 증기 터빈제어 비교)

  • Choi, I.K.;Kim, J.A.
    • Proceedings of the KIEE Conference
    • /
    • 2000.07d
    • /
    • pp.2342-2344
    • /
    • 2000
  • Many years ago, most of thermal power plants built in this country were of subcritical pressure, of medium or small size, of constant pressure operation, of drum type steam generator. But, nowadays, almost all of them were of high efficiency, of supercritical pressure, of great capacity(about 500MW), of sliding pressure operation, of once through type steam generator. Presently built once through boiler introduces turbine bypass systems to variable pressure operation which eliminates unexpected materials in boiler tube during startup, minimizes fuel loss by short startup period, eventually improves total efficiency and power system stability

  • PDF

Temperature Control of Ultrasupercritical Once-through Boiler-turbine System Using Multi-input Multi-output Dynamic Matrix Control

  • Moon, Un-Chul;Kim, Woo-Hun
    • Journal of Electrical Engineering and Technology
    • /
    • v.6 no.3
    • /
    • pp.423-430
    • /
    • 2011
  • Multi-input multi-output (MIMO) dynamic matrix control (DMC) technique is applied to control steam temperatures in a large-scale ultrasupercritical once-through boiler-turbine system. Specifically, four output variables (i.e., outlet temperatures of platen superheater, finish superheater, primary reheater, and finish reheater) are controlled using four input variables (i.e., two spray valves, bypass valve, and damper). The step-response matrix for the MIMO DMC is constructed using the four input and the four output variables. Online optimization is performed for the MIMO DMC using the model predictive control technique. The MIMO DMC controller is implemented in a full-scope power plant simulator with satisfactory performance.

Analysis of Flow through High Pressure Bypass Valve in Power Plant (발전소용 고압 바이패스 밸브의 유동해석)

  • Cho, An-Tae;Kim, Kwang-Yong
    • Proceedings of the KSME Conference
    • /
    • 2007.05b
    • /
    • pp.2558-2562
    • /
    • 2007
  • In the present work, flow characteristics analysis has been performed for steam turbine bypass control valve (single-path type). The numerical analysis is performed by solving three-dimensional Reynolds-averaged Navier-Stokes (RANS) equations. Shear stress transport (SST) model is used as turbulence closure. Symmetry condition is applied at the mid plane of the valve while adiabatic condition is used at the outer wall of the cage. Grid independency test is performed to find the optimal number of grid points. The pressure and temperature distributions on the outer wall of the cage are analyzed. Mass flow rate at maximum plug opening condition is compared with the designed mass flow rate.

  • PDF

Experimental and Numerical Analyses of flow field in a bypass valve (바이패스밸브 유동장에 관한 실험 및 수치해석)

  • Choi, Ji-Yong;Cho, An-Tae;Kim, Kwang-Yong
    • 유체기계공업학회:학술대회논문집
    • /
    • 2006.08a
    • /
    • pp.527-530
    • /
    • 2006
  • In the present work, characteristics of the flow in the cage of a steam turbine bypass control valve for thermal power plant are investigated. Experimental measurement for wall static pressure has been carried out to validate numerical solutions. And, the flowfield is analyzed by solving steady three-dimensional Reynolds-averaged Navier-Stokes equations. Shear stress transport (SST) model is used as turbulence closure. The effects of the flow area between stages of the cage on the pressure drop are also found.