• 제목/요약/키워드: Surge arrestor

검색결과 19건 처리시간 0.02초

혼합 배전계통에서 피뢰기적용과 접지시스템 변경을 고려한 서지 해석에 관한 연구 (A Study on the Surge Analysis considering Surge Arrester and Grounding System in the Combined Distribution System)

  • 윤창섭;이종범;김병숙
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 제37회 하계학술대회 논문집 A
    • /
    • pp.204-205
    • /
    • 2006
  • This paper describes the protective ability of lightning arrestor in combined distribution system with power cable. To evaluate the protective ability, change of arrestor and grounding location are considered. On the other hand, arrestor developed by Cooper Power Systems for underground power cable system, is considered to evaluate surge protective ability as in underground system, when arrestor occurs failure has overhead line. The result shows that lightning arrestor in combined distribution system with power cable protect effectively when failure at arrestor in overhead line. On the other hand, arrestor developed by Cooper Power Systems for underground power cable system, is considered to evaluate surge protective ability in underground distribution system, when arrestor of overhead line has failure. The result shows that lightning arrestor installed in underground cable can effectively protected cables from surge when arrestor of overhead line has failure. And also even though grounding locations are decreased, it is revealed that protective ability is nearly similar.

  • PDF

케이블 장력 및 피뢰기의 강성 변화를 고려한 애자형 피뢰기의 동특성 시험 연구 (Experimental Study on the Dynamic Characteristics of Porcelain Surge Arrestor Considering the Variation of Cable's Tension and Arrestor's Stiffness)

  • 장정범;황경민;연관희
    • 한국지진공학회논문집
    • /
    • 제18권5호
    • /
    • pp.253-259
    • /
    • 2014
  • Porcelain surge arrestor is very vulnerable to earthquake but there is very few information on its dynamic characteristics which are necessary to the seismic design. Therefore, the dynamic characteristics of the porcelain surge arrestor are evaluated considering the variation of its cable tension and stiffness by shaking table test. The test results show that the first natural frequencies are 5.3 Hz and 5.2 Hz in the horizontal x- and y-axis directions, respectively, and higher than 30 Hz in the vertical z-axis direction, respectively. The installation of cable on the surge arrestor reduces the horizontal natural frequencies due to the constraint effect of the cable but cable tension has no effect on the natural frequency. Also, the natural frequency is proportional to the stiffness of the surge arrestor. This test result will be used for the seismic design and seismic capacity assessment of domestic substations and contribute to the stability of the electric power supply under earthquake event.

세라믹 필터를 이용한 동축 서지어레스터의 잔류전압 저감 (Residual Voltage Reduction of Coaxial Surge Arrestor Using Ceramic Filler)

  • 엄주홍;조성철;이태형;이영철
    • 조명전기설비학회논문지
    • /
    • 제21권2호
    • /
    • pp.46-53
    • /
    • 2007
  • 현재 급속한 발전을 거듭하고 있는 이동통신 및 무선 멀티미디어 관련 서비스(W-CDMA, DMB, WiBro 등)의 확장은 이들 시스템을 구현하기 위한 수많은 기지국과 안테나 및 다수의 신호전송선로를 필요로 한다. 기지국 또는 중계시설의 안테나는 신호전송선로를 통하여 고가의 통신 네트워크 장비들과 결합되어 있으므로 주요 통신기기 시스템은 안테나를 통해 유입하는 직격뢰 및 유도뢰에 의한 순간적인 과전압의 위험에 항시 노출되어 있다. 현재 통신용 보호기로 사용되고 있는 가스방전튜브(GDT) 또는 협대역 스터브형 어레스터는 고속 광대역의 통신설비에 대한 뇌서지 보호수단으로서는 한계점이 드러나고 있다. 따라서 본 연구에서는 안테나를 통해 입사하는 뇌서지를 효과적으로 저감시켜주는 서지어레스터의 성능향상을 위해 세라믹 필터를 적용하였으며, 잔류전압 저감에 효과적임을 성능실험을 통해 입증하였다.

4분의 1 파장 단락 스터브 방식 서지 어레스터의 잔여 전압 제거에 관한 연구 (Study on the Elimination of Residual Voltage in Quarter Wave Short Stub Surge Arrestor)

  • 김연태;원태영
    • 대한전자공학회논문지TC
    • /
    • 제37권8호
    • /
    • pp.33-44
    • /
    • 2000
  • 고전압 전류 특성의 낙뢰는 안테나를 통해 지상에 설치된 이동 통신 기지국으로 도입될 수 있으며, 이를 방지하기 위한 장치가 서지 어레스터이다. 본 논문에서는 서지 어레스터의 개념, 종류, 동작 원리, 설계 및 제작 등을 검토하고, 이를 기반으로 현재 국내외에서 이용되고 있는 이동 통신 서비스인 셀룰라, GSM 및 PCS 등과 차세대 이동 통신 서비스인 IMT-2000의 기지국에 적용 가능한 서지 어레스터들을 설계하였다. 초기 설계된 서지 어레스터들은 고주파 3차원 구조 시뮬레이터 상에서 특성 예측을 위한 컴퓨터 모의 실험과 서지 어레스터의 전자기적 특성 개선을 위한 내부 구조 최적화 작업이 수행되었다. 서지 어레스터의 최종 설계도를 기반으로 실제 IMT-2000 기지국용 4분의 1 파장 단락 스터브 방식의 서지 어레스터를 제작하였으며, 전자기적 전송 특성 측정과 낙뢰 전달 테스트를 수행하여 제작된 서지 어레스터의 성능을 측정하였다. 측정 결과, 전압 정재파 비는 1.05 이하, 삽입 손실은 -0.035 dB이하, 상호변조 특성은 -150 dBc 이하의 특성을 얻었으며, 잔여 전압 특성은 7∼ll V 정도의 특성을 보였다.

  • PDF

4회선 인입철구 구조를 가진 154 kV 변전소의 뇌과전압 해석 (Lightning Surge Analysis in 154 kV S/S due to Flashover on the 4 Circuits Tower)

  • 우정욱;심응보;곽주식;최병준
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 C
    • /
    • pp.1888-1890
    • /
    • 2000
  • This paper describes the analysis results for the protection of lightning surge at 154 kV substation. We found that the surge arrester is needed at the inlet structure. The maximum overvoltage is about 1,500 kV at the circuit breaker without the surge arrester at the inlet structure. This value can be lower than 600 kV by installing the surge arrestor at the inlet structure. In addition to the incoming surge from transmission line, the shield wire should be considered to prevent the shielding failure by the direct lightning stroke.

  • PDF

154 kV 변전설비의 낙뢰사고 원인해석과 차폐검토 (A analysis result on the lightning outage and the lightning shield at 154 kV substation)

  • 우정욱;심응보;곽주식;구본묵;노영조;주준영
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 E
    • /
    • pp.2080-2082
    • /
    • 1999
  • This paper describes the analysis results for the protection of lightning surge at 154 kV substation. We found that the surge arrester is needed at the inlet structure. The maximum overvoltage is 975 kV at the circuit breaker without the surge arrester at the inlet structure. This value can be lower than 600 kV by installing the surge arrestor at the inlet structure. In addition to the incoming surge from transmission line, the shield wire should be considered to prevent the shielding failure by the direct lightning stroke.

  • PDF

ZnO 피뢰기의 경년변화 특성분석 (Aging Characteristics of ZnO Surge Arresters)

  • 김주용;김찬영;송일근;이병성;한용희
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1999년도 춘계학술대회 논문집
    • /
    • pp.383-386
    • /
    • 1999
  • Surge arrestor is used for protection of facilities and lines. Recently lots of arresters fatted prematurely In the distribution lines. It is important to know that what the cause of the failures is. This paper presents characteristics of the aged and new 18kV surge arrester. In order to analyse characteristics, we measured leakage current using specialty made leakage current measurement system and also investigated Tan $\delta$ of the arrester and microstructure of the elements. Through the investigation we found that the characteristics among the ZnO elements in an arrester were a little different, It means that the surge arreste can have non-uniform electric field due to the characteristic difference of The each element. Owing to this concentration of the electric field, the localized aging might be proceeded.

  • PDF

중첩전압(직류 +60Hz 교류)에서 18kV 배전용 피뢰기의 전기적 특성 (The electrical properties of in 18kV ZnO surge arrestor with mixed direct and 60Hz Alternating Voltage)

  • 이복희;이승주;이수봉;정동철;백영환
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2007년도 춘계학술대회 논문집
    • /
    • pp.291-294
    • /
    • 2007
  • This paper preserts the characteristics of leakage currents flowing through 18 kV zinc oxide (ZnO) surge arrester under the mixed DC and AC voltages. The I-V curves of ZnO surge arrester were measured as a function of the voltage ratio K The I-V curves under the mixed DC and AC voltages lay between the pure DC and AC characteristics, and the cross-over phenomenon in I-V curves was observed at the low current region As a result, the increase of DC component to mixed voltages causes the increase of resistive component of total leakage current th ZnO surge arrester.

  • PDF

중첩전압(직류+교류 60Hz)에서 산화아연 피뢰기 소자의 누설전류 특성 (The characteristic of leakage current in ZnO surge arrestor elements with mixed direct and 60Hz voltage)

  • 이복희;박건영;강성만;최휘성;오성균
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.186-188
    • /
    • 2003
  • The ZnO surge arrester is the protective device for limiting surge voltages on equipment by diverting surge current and returning the device to its original status. The occurrence of overvoltage appears in any phase to AC power supply system and it appears in mixing AC and impulse voltages, moreover because HVDC power supply system uses converter in semiconductor, it makes mixed DC and high harmonics voltages. In this study, the various mixed AC and DC voltages was made for investigating the degradation effect of ZnO arrester according to mixed voltage. As a result, the increase of DC component to mixed voltages causes the increase of resistive component of total leakage current to ZnO block. In changing V-I curve for mixed voltages, the cross-over point acts a factor as making the proper capacitor size of an equivalent circuit for ZnO block.

  • PDF

국제시험규격에 적합한 뇌서지 시험설비 구축 (Installation of Test Equipment for Lightning Surge Complying with International Standard)

  • 이태형;조성철;엄주홍;이복희
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2006년도 춘계학술대회 논문집
    • /
    • pp.360-364
    • /
    • 2006
  • Recently KS documents related to lightning protection were revised complying with the requirements of IEC standards. Lightning protection parts are divided three in IEC, those are arrestor(60099), SPD(61643), and protection facilities(62305). According as international standard is applicable in Korea, type tests, routine tests, and acceptance tests shall be made to demonstrate compliance with the relevant standards. KESRI have installed test equipment which is funded by Ministry of Commerce, Industry and Energy fit for lightning surge test form 2002, and we introduce the test equipments in detail.

  • PDF