Abstract

The ZnO surge arrester is the protective device for limiting surge voltages on equipment by diverting surge current and returning the device to its original status. The occurrence of overvoltage appears in any phase to AC power supply system and it appears in mixing AC and impulse voltages, moreover because HVDC power supply system uses converter in semiconductor, it makes mixed DC and high harmonics voltages. In this study, the various mixed AC and DC voltages was made for investigating the degradation effect of ZnO arrester according to mixed voltage. As a result, the increase of DC component to mixed voltages causes the increase of resistive component of total leakage current to ZnO block. In changing V-I curve for mixed voltages, the cross-over point acts a factor as making the proper capacitor size of an equivalent circuit for ZnO block.