초록

Porcelain surge arrestor is very vulnerable to earthquake but there is very few information on its dynamic characteristics which are necessary to the seismic design. Therefore, the dynamic characteristics of the porcelain surge arrestor are evaluated considering the variation of its cable tension and stiffness by shaking table test. The test results show that the first natural frequencies are 5.3 Hz and 5.2 Hz in the horizontal x- and y-axis directions, respectively, and higher than 30 Hz in the vertical z-axis direction, respectively. The installation of cable on the surge arrestor reduces the horizontal natural frequencies due to the constraint effect of the cable but cable tension has no effect on the natural frequency. Also, the natural frequency is proportional to the stiffness of the surge arrestor. This test result will be used for the seismic design and seismic capacity assessment of domestic substations and contribute to the stability of the electric power supply under earthquake event.

키워드

참고문헌

  1. KEPCO Research Institute. Seismic design guidelines for transmission and substation facilities, c2001.
  2. EERI. Northridge reconnaissance report, Earthquake Spectra, Supplement C. Oakland. c1995.
  3. Shinozuka M, ed. The Hanshin-Awaji earthquake of January 17, 1995 : Performance of lifelines. Technical Report NCEER-95-0015 Buffalo. c1995.
  4. Jang JB et al. Experimental study of friction pendulum system to improve the seismic capacity of transformer. Journal of the Earthquake Engineering Society of Korea. 2008;12(2):1-8.
  5. Jang JB et al. Experimental study of a seismic reinforcing system without power breakdown and movement for electric panel on the access floor. Journal of the Earthquake Engineering Society of Korea. 2009;13(3):1-10.
  6. Gilani AS, Chavez JW, Fenves GL. Whittaker AS, Seismic Evaluation of 550kV Porcelain Transformer Bushings. PEER. c1999.
  7. Gilani AS, Chavez JW, Fenves GL, Whittaker AS. Seismic Evaluation of 196kV Porcelain Transformer Bushings. PEER. c1999.
  8. Wilcoski J. Demonstration of CERL Equipment Fragility and Protection Procedure by Fragility Testing of a Power Transformer Bushing. ATC-29-1. Seminar Technical Papers. c1997.
  9. Villaverde R, Pardoen G. Ground Motion Amplification at Base of Bushings Mounted on Electric Substation Transformer. A Technical Report of Research Supported by PEER/PG&E Under Award No. PGE-09566. Department of Civil Engineering, University of California, Irvine. c1999.

피인용 문헌

  1. The Experimental Study on Seismic Capacity of 154 kV & 345 kV Main Transformer Bushings vol.22, pp.2, 2018, https://doi.org/10.5000/EESK.2018.22.2.087