• 제목/요약/키워드: Smoke propagation

검색결과 58건 처리시간 0.02초

고층건물의 수직방향 연기거동에 미치는 발코니의 영향에 관한 실험적 연구 (An Experimental Study on the Effect of the Balcony on the Vertical Smoke Movement of the High Rise Building)

  • 양승신;김성찬;유홍선;심상훈
    • 한국안전학회지
    • /
    • 제20권1호
    • /
    • pp.42-48
    • /
    • 2005
  • The present study investigates the effect of balcony on external smoke movement of high rise building through the fire tests of the 1/10 reduced model scale using Froude scaling. A hexane pool fire is used to examine the smoke movement for various opening sizes of balcony and temperature distributions are measured by T-type thermocouples. Also, hydrogen bubble technique is applied to visualize the smoke movement near the balcony. Measured temperatures of the closed balcony is 2.5 times higher than those of the open balcony because the external smoke in case of the closed balcony rise along the vertical wall. The maximum vertical temperature of partially closed balcony is similar with fully closed balcony and mean temperature inside of balcony increases as opening size of balcony decreases. The experimental results show that the balcony space plays an important roles in preventing fire propagation and cooling of smoke layer. In order to ensure the fire safety in high rise building design, a series of systematic researches are required to examine the various type of balconies.

열가소성 수지(PP, PMMA, PVC)의 연기생성 및 발생에 관한 실험적 연구 (Experimental Study on Smoke Production and Smoke Generation in Thermoplastic Resins Based on PP, PMMA, and PVC)

  • 황의홍;최돈묵
    • 한국화재소방학회논문지
    • /
    • 제34권3호
    • /
    • pp.1-7
    • /
    • 2020
  • 건축물의 복잡화, 대형화로 인해 합성수지를 건축 재료로써 많이 활용되고 있다. 이에 따라 합성수지가 원인이 되는 화재의 발생이 증가하고 있다. 합성수지 화재의 특성으로는 연기 등 연소생성물로 인한 인명 및 재산피해가 크다는 점이고, 이는 연기생성과 발생과 관계된다. 이에 본 연구는 국내 건축 및 소방관계법령과 연기측정방법에 대해 검토하고, 연기관련 3가지 시험기준(ISO 5660-1, ISO 12136, ASTM E 662)을 바탕으로 실험을 실시하였다. 실험에 대한 결과로 연기생성 관련 데이터에서는 PP 43.27 ㎡, PVC 32.83 ㎡, PMMA 12.33 ㎡ 순으로 나타났고, 연기발생 관련 데이터에서는 PVC 27.855 g, PP 9.599 g, PMMA 6.975 g 순으로 나타났다.

도로터널의 화염전파해석에 관한 연구 (Study on the Analysis of Fire Propagation in Road Tunnels)

  • 권용일;유지오;이동호;권순석
    • 설비공학논문집
    • /
    • 제12권6호
    • /
    • pp.616-622
    • /
    • 2000
  • This paper concerns the application of smoke and fire spread to road tunnel fire problems. When a road tunnel is on fire. a fire protection system of road tunnel have to offer an adequate escape space to human. Therefore, this study carried out a simulation for predicting a spreading path of smoke and fire. The evolution of the flow field is simulated with the low Reynolds number k-$\varepsilon$ turbulent model and SIMPLE algorithm based on the finite volume method.

  • PDF

An Efficient Method to Obtain MCF in Millimeter Wave Systems

  • 이종길
    • 한국통신학회논문지
    • /
    • 제28권3A호
    • /
    • pp.151-156
    • /
    • 2003
  • Millimeter waves are potentially useful for high resolution ranging and imaging in low optical visibility conditions such as fog and smoke. Also, They can be used for wide band communications since the currently used spectrum bands are already crowded. However, it is necessary to develop a theoretical and experimental understanding of millimeter wave propagation to assess the performance of millimeter wave systems. The intensity fluctuations and mutual coherence function (MCF) describe atmospheric effects on the millimeter wave propagation. Using the quasi-optical method (QOM), a practical and efficient method is suggested to obtain MCF from the flux measurement in the antenna focal plane.

자동차 내장재의 연소 특성에 관한 연구 (A Study On Combustion Characteristics of Automobile Interior)

  • 김정훈;박형주;김홍
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 1996년도 학술발표회
    • /
    • pp.43-48
    • /
    • 1996
  • It is considered that automobile inner space is dangerous due to its combustion characteristics. (Automobile interior is largely made by plastic materials.) At last it is necessary to study on combustion characteristics of automobile interior. we could obtain its rapid combustion velocity and high smoke density by using ASTM D 2863 apparatus, DSC (Differential Scanning Calorimetry), Smoke density apparatus and so on. The study is summerized by following conditions and results. 1. Sample size was 150mm(length)$\times$60mmwidth). 2. Combustion velocity appeared peak point in the 2cm point. 3. PVC and foam layers are important factors in the face of smoke density. 4. Using DSC, we obtained the point that automobile interior was melted. 5. Automobile interior should be improved because of its low L.O.I value and rapid flame propagation velocity.

  • PDF

동굴 공간의 안전과 방재차단벽 (Embodiment of Firewall Block for Safety in the Cave)

  • 김보수;김강원;김태환;박정호;이영재;소대화
    • 동굴
    • /
    • 제87호
    • /
    • pp.8-13
    • /
    • 2008
  • The automatic firewall block and fire alarm system was embodied by using gas circuit and wireless communication equipment, using a smoke sensor (ST-QA1A) and RF Module. OR-CAD was also used for testing circuit system and experiment circuit after assembling circuit. As a result in experiment, the gas sensor detected well an imaginary smoke and worked reliably for driving action of firewall block motor and wireless warning alarm. Through the smoke sensitive perception from the fire, the warning alarm and the preventing fire propagation from the specific closed region were verified reliably. The gas sensor and RF module for firewall and fire alarm system were actually available.

스크린도어가 설치된 대심도 지하역사의 제연 실험 - 터널 송풍기에 의한 제연의 효과 분석 (Smoke Control Experiment of a Very Deep Underground Station Where Platform Screens Doors are Installed - Analysis on Smoke Control Performance by Fans equipped in Tunnel)

  • 박원희;김창용;조영민
    • 예술인문사회 융합 멀티미디어 논문지
    • /
    • 제9권9호
    • /
    • pp.721-736
    • /
    • 2019
  • 본 논문에서는 대심도에 위치한 지하역사(지하 6층) 및 터널에서 화재가 발생했을 경우 제연설비 작동에 따른 연기의 거동을 측정하였다. 열풍기를 이용하여 열부력 효과를 구현한 연기발생장치를 이용하여 화재연기를 생성하였다. 화재발생 위치는 승강장 위 및 스크린도어 외부에 위치한 터널부의 승강장 위의 2가지 위치를 선정하였다. 승강장 화재발생시 승강장에 설치된 환기구를 통하여 연기가 배출되도록 하는 제연모드가 일반적인데 본 연구에서는 승강장 양단에 위치한 터널부의 환기구를 통한 배기도 같이 동작되도록 설정하여 실험을 수행하였다. 다양한 위치에서 연기농도 및 풍향풍속을 측정하였고 화면을 취득하여 연기의 이동 및 제연을 분석하였다. 승강장 내부에서 화재가 발생하였을 경우와 선로부에서 화재가 발생하였을 경우 승강장의 송풍기의 제연모드 동작과 터널의 송풍기의 배연 동작으로 인하여 연기배출이 원활하였고 화재 발생 인근 구역으로의 연기전파가 억제되었다. 본 연구에서 제시한 승강장 및 승강장 양단부의 터널에 적용되는 송풍기를 같이 운전하는 제연모드를 통하여 승강장 화재 및 화재열차 정차시 화재 연기로부터 승객들에게 보다 안전한 대피환경을 제공할 수 있을 것이다.

PSD가 설치된 지하철 역사 내 화재 시 최적 배연시스템 연구 (A study on the optimal ventilation and smoke exhaust systems in case of fire in subway stations installed with PSD)

  • 김효규;유지오;김두영
    • 한국터널지하공간학회 논문집
    • /
    • 제20권2호
    • /
    • pp.527-539
    • /
    • 2018
  • 다수의 승객들이 이용하는 지하철은 안전과 공간의 쾌적한 환경관리가 필수적이며, 2003년 이후 기준 강화로 승강장 내에 스크린도어(PSD)를 반드시 설치해야 한다. 선행연구에 따르면 지하철 화재 시에 화재연기의 배연을 위해 배연설비의 설비용량 최적설계가 필요하다. 따라서 본 연구에서는 선행연구의 실험 결과를 바탕으로 3차원 수치해석기법을 이용하여 PSD가 설치된 승강장 내에서 화재발생 시 배연시스템 별로 CO가스와 Smoke의 유동을 분석하였다. 본 연구의 결과 비상시 상부 배연설비만 가동한 경우에는 CO 가스와 Smoke 농도는 653.8 ppm과 $768.4mg/m^3$로 피난 시 승객들의 위험이 큰 것으로 분석되었으며, 모든 배연설비를 가동하고 화재측 PSD만을 개방한 경우 CO 가스와 Smoke 농도 36.0 ppm 및 $26.2mg/m^3$를 보이며 화재연기의 전파범위가 줄어드는 것으로 분석되었다. 모든 배연설비를 가동하고 화재측 PSD를 미개방한 경우에는 화재연기 유입이 발생하지 않아서 대피환경에 있어 가장 효과적인 배연모드로 분석되었다.

실물터널 화재실험을 통한 터널화재 위험도 평가 (The Risk Assessment of Tunnel Fire Through Real Scale Fire Test)

  • 최준석;최병일;김명배;한용식;장용재;이유환;황낙순;김필영
    • 한국화재소방학회논문지
    • /
    • 제16권3호
    • /
    • pp.71-76
    • /
    • 2002
  • 실제 터널화재에서의 위험성을 평가하기 위하여, 국내에서 최초로 실물터널 화재실험이 수행되었다. 길이 465m의 터널에서 0.25MW에서 2.5MW까지의 가솔린 풀과 1500cc승용차를 화원으로 사용하였으며, 터널내의 유속을 조정하기 위하여 6대의 제트팬을 설치하였다. 터널내의 온도분포와 연기거동을 살펴보기 위하여 총 86곳의 온도를 측정하였다. 다양한 조건에서의 풀화재와 자동차 화재의 성상을 비교하였으며, 실험 결과 각종 화재 조건에서의 연기의 역류, 하강, 터널 내 온도분포 등과 같은 실제 터널 화재상황에서 피해에 영향을 미치는 각종 인자들을 파악하였다.