• 제목/요약/키워드: SPS(Special Protection System)

검색결과 12건 처리시간 0.029초

Fast-valving과 Braking resistor 적용을 통한 지능형 SPS 알고리즘 구현 (Algorithm of intelligent SPS with applying fast-valving and braking resistor)

  • 김갑용;윤동희;장길수;문영환;김석주;서상수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2011년도 제42회 하계학술대회
    • /
    • pp.280-281
    • /
    • 2011
  • Special Protection Scheme(SPS) that operates scenarios about faults beyond the normally protective action is wide system protection technology for the purpose of wide areas protection. Therefore, the SPS focuses on the improvement of the power supply capability by protecting the system rather than protecting the system equipments. Since the SPS requires emergency operation, the operation schedule is set up in advance by analyzing various scenarios. Since the SPS's action scheme uses generator tripping and is a classical method it is presently the most powerful one. However, as the setting of SPS is set to the most severe disturbance, the scheme tends to trip more generators than required to prevent fault propagation. It is highly likely that tripping generator units to prevent fault propagation would result in difficulty of system management and possibility of load shedding. Accordingly, it is desirable that generators are connected to the system within the range that ensures system stability and intelligent SPS is currently under development to solve the problem being stated. In this paper, as a part of developing the intelligent SPS, application of the fast-valving and braking resistor scheme to the generators is being proposed and analysed to reduce the number of tripped generators.

  • PDF

발전기 가속에너지를 이용한 고장파급방지장치 운전조건 완화용 전기저장장치 적정용량 산정방안 (Required Capacity Assessment of Energy Storage System for Relieving Operation Condition of SPS Using Generator Acceleration Energy)

  • 송승헌;최우영;권한나;국경수
    • 전기학회논문지
    • /
    • 제68권1호
    • /
    • pp.1-7
    • /
    • 2019
  • Due to the highly concentrated power plants integrated through the limited transmission lines in Korea, a Special Protection System(SPS) has been applied to stabilize the power systems by instantly tripping the pre-determined generators in a large-scaled power plant when a fault occurs on the drawing transmission lines. Moreover, power outputs of those generators are constrained to avoid any activation of Under Frequency Load Shedding(UFLS) even after those generators are tripped by SPS action. For this, this paper proposes a method for calculating the required capacity of Energy Storage System(ESS) expected to relieve the operating constraints to generators using its fast response for controlling power system frequency. The proposed method uses the generator acceleration energy to derive the stable condition during the SPS action. In addition, its effectiveness is verified by the case studies adopting actual SPS operations in Korean power systems.

Application of Multi-step Undervoltage Load Shedding Schemes to the KEPCO System

  • Shin, Jeong-Hoon;Nam, Su-Chul;Lee, Jae-Gul;Choy, Young-Do;Kim, Tae-Kyun;Song, Hwa-Chang
    • Journal of Electrical Engineering and Technology
    • /
    • 제4권4호
    • /
    • pp.476-484
    • /
    • 2009
  • This paper deals with improvements to the special protection schemes (SPS) which have been applied to the low probability and high impact contingencies in the Korea Electric Power Corporation (KEPCO) system since 2004. Among them, the SPS for voltage instability in the Seoul metropolitan area is considered in this paper, and is a form of event-based undervoltage load shedding with a single-step scheme. Simulation results based upon a recent event that occurred on 765kV lines show that the current setting values of the SPS have to be revised and enhanced. In addition, by applying response-based multi-step undervoltage load shedding (UVLS) schemes to severe contingencies in the system, more effective results than those of the existing single-step SPS can be obtained. Centralized and distributed UVLS schemes are considered in the simulation. ULTC-based load recovery models and over excitation limiters (OXL) for the KEPCO system are also included in the long-term voltage instability studies.

전력계통 운영조건을 고려한 발전기차단용 SPS 동작설정에 관한 연구 (A Study on Setting SPS for Generator Tripping Action considering Operating Conditions of Power Systems)

  • 권한나;손혁진;국경수;양성채
    • 한국산학기술학회논문지
    • /
    • 제15권1호
    • /
    • pp.411-417
    • /
    • 2014
  • 발전기차단용 고장파급방지장치(SPS; Special Protection Scheme)는 대규모 발전단지의 인출 송전선로 고장시 발전단지 내의 발전기 과속을 방지하기 위해 사전에 계획된 대수만큼 해당 발전기를 즉시 차단하여 전력계통 전체의 안정도를 유지하는 비상 장치이다. 그러나 기존의 국내 발전기차단용 SPS 동작은 첨두부하를 기준으로 산정된 값을 일률적으로 적용하여 운영 되고 있어 경부하시에 발전기차단용 SPS가 동작을 하게 되면 발전기 과차단으로 인한 발전력 부족을 초래할 가능성이 있는 등 SPS 운영의 비효율성이 잠재되어있다. 이를 위해 본 논문에서는 수시로 변화하는 전력계통 운영조건을 주기적으로 취득하고 정확도와 속도가 우수한 COA기반의 안정도평가를 통해 발전기 차단용 SPS 동작을 설정함으로써 경부하시에는 SPS 발전기 탈락대수가 첨두수요 기준의 설정치보다 감소되어 계통 고장에 의한 SPS 동작 시 발전비용 증가를 경감 할 수 있다.

Planning of HVDC System Applied to Korea Electric Power Grid

  • Choi, DongHee;Lee, Soo Hyoung;Son, Gum Tae;Park, Jung-Wook;Baek, Seung-Mook
    • Journal of Electrical Engineering and Technology
    • /
    • 제13권1호
    • /
    • pp.105-113
    • /
    • 2018
  • This paper proposes pre-analysis on planning of high-voltage direct current (HVDC) transmission system applied to Korea electric power grid. HVDC transmission system for interface lines has been considered as alternative solution for high-voltage AC transmission line in South Korea since constructing new high-voltage AC transmission lines is challenging due to political, environmental and social acceptance problems. However, the installation of HVDC transmission system as interface line in AC grid must be examined carefully. Thus, this paper suggests three scenarios to examine the influences of the installation of HVDC transmission system in AC grid. The power flow and contingency analyses are carried out for the proposed scenarios. Power reserves in metro area are also evaluated. And then the transient stability analysis focusing on special protection scheme (SPS) operations is analyzed when critical lines, which are HVDC lines or high voltage AC lines, are tripped. The latest generic model of HVDC system is considered for evaluating the impacts of the SPS operations for introducing HVDC system in the AC grid. The analyses of proposed scenarios are evaluated by electromechanical simulation.

전력계통 신뢰도 기준 분석을 통한 765kV 선로사고에 대한 부하차단 적정량 산정에 관한 연구 (Determination of Reasonable Amounts of Under-Voltage Load Shedding for 765kV T/L According to the Power System Reliability Standards)

  • 유제호;허진;차준민;김태균;강부일;조수환
    • 전기학회논문지
    • /
    • 제64권6호
    • /
    • pp.845-851
    • /
    • 2015
  • Load shedding is a last measure to avoid nationwide cascading collapses of power system by removing the pre-determined amount of loads from the main grid. In Korea, SPS(Special Protection System) is prepared to keep the power system stability from the extreme contingency of the critical transmission line losses. Among them, we need to pay attention to 765kV T/L’s because they have great influence on the total system stability. According to the present SPS operating guide, the total loads of 1,500MW should be removed through 2 step under-voltage load shedding(UVLS) scheme in case of 765kV T/L’s contingencies. However, it is not clear to defined how to determine the typical load reduction amounts for each case. This paper proposes a method to estimate appropriate amounts of load shed for 765kV T/L’s contingencies by analyzing the relevant national and international standards.

대규모 발전단지 상시제약 감소를 위한 에너지 저장장치(ESS) 적용에 관한 연구 (A Study on Energy Storage System(ESS) Application for Dynamic Stability Improvement and Generation Constraint Reduction)

  • 이재걸;정솔영;최장흠;김용학;윤용범
    • 전기학회논문지
    • /
    • 제66권11호
    • /
    • pp.1554-1560
    • /
    • 2017
  • Prepare a lose of 765kV transmission route in power system operation condition, there are some Special Protection Scheme(SPS)s in Korean power system. These SPS can make some preselected generators are tripped to avoid generator overspeed. Because of many of the new large power plants are installed to existing power generation sites due to the siting problem, the number of generator tripped by SPS should be increased. But that can be a cause of system frequency change under the Under Frequency Relay(UFR) 1st pickup level 59.0Hz. Therefore generation constraint should be considered until new transmission lines are installed. In this paper, we propose the ESS application for generation constraint mitigation by frequency damping control of ESS. To analysis an effect of ESS application, we use PSS/E dynamic simulation tool, CBEST model and controller model. The proposed ESS application is applied to the empirical Korean power system.

SPS의 보호동작과 우리나라 계통보호설비 현황 (Protection Actions of SPS and SPS in Korea Power System)

  • 박종영;박종근;추진부;장병태;강계희;양정재
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 A
    • /
    • pp.274-276
    • /
    • 2002
  • 긴급보호제어시스템(SPS, Special Protection System)은 일반적인 보호동작 범위를 벗어난 외란에 대해서 계통 전지역의 보호를 목적으로 하는 광역시스템 보호기술이다. 따라서 SPS는 외란 시에 계통 장비의 보호보다는 계통을 보호함으로써 전력 공급능력 향상에 주안점을 두게 된다. SPS는 자주 동작하지 않고 평소에는 대기 상태로 있으며, 긴급한 동작이 요구되기 때문에 많은 경우에 그 동작이 미리 결정되어 있다. SPS는 입력변수나 전력계통에의 영향에 따라 분류할 수 있는데, 입력변수에 따라서는 계통 응답에 기초한 SPS와 사고에 기초한 SPS로 나눌 수 있다. 발전기 탈락, 부하 차단이 SPS의 주요 보호 동작이며 이 외에 가스터빈이나 양수발전기 기동, AGC 제어, HVDC 고속전력변환, 분로기기의 자동스위칭 등의 제어 동작이 있다. 우리나라의 경우에는 주로 동기탈조 방지를 위한 발전기 탈락의 동작을 하는 SPS가 설치, 운전되고 있다.

  • PDF

2010년 여름철 전력계통 최적 운영에 관한 연구 (A Study on the Optimal Operation of 2010 Summer Peak in Korea Power System)

  • 이성무;조종만;김규호
    • 전기학회논문지
    • /
    • 제59권10호
    • /
    • pp.1733-1740
    • /
    • 2010
  • KPX(Korea Power Exchange) predicts that summer peak load will be 70,700MW and system overload will be 150% from contingency analysis. This paper presents a method to operate power system at 2010 summer peak. about equipment variation, power system variation, analysis results of voltage stability, and the method to relief overload by comparing 2009 and 2010. Especially, transmission constraints to prevent global contingency in Korea power system and the role of SPS(Special Protection System) to prevent voltage collapse when fault occurs are introduced.

부하특성을 고려한 동계 강원지역 SPS 적용방안 (Application With Load Characteristic To Special Protection System For The District Of GangWon In Winter)

  • 김동현;김태옥;김준연;윤부현;곽은섭;이석창;이희찬
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.87-88
    • /
    • 2008
  • 현재 전국적으로 많은 곳에 SPS(고장파급방지장치)가 설치되어 운영중에 있으며 대부분은 345kV이상 대단위 전원단지 인근에 설치되어 있으나 강원지역의 경우는 154kV 계통에 다수가 설치되어 운전중에 있다. 강원지역은 지역적 특성으로 인해 장거리 송전선로가 많으며 전원단이 원거리에 위치하여 고장시 전압불안정에 의한 계통붕괴의 위험성이 타 지역보다 높다. 특히 하계에 비해 난방부하 및 심야전력의 영향으로 최대부하가 대폭 증가하는 동계의 경우 이러한 특성이 더욱 두드러지는데 2007년 동계피크시 부하실적 및 역률을 기준으로 부하특성 및 부하역율 변동에 따른 계통영향을 분석하여 기 설치 운영중인 SPS 적용의 타당성 및 유지여부에 대한 판단 및 SPS 적용 개선(안)을 제시하였다.

  • PDF