Planning of HVDC System Applied to Korea Electric Power Grid

  • Choi, DongHee (School of Electrical and Electronic Engineering, Yonsei University) ;
  • Lee, Soo Hyoung (Korea Electrotechnology Research Institute (KERI)) ;
  • Son, Gum Tae (LS IS Co. Ltd) ;
  • Park, Jung-Wook (School of Electrical and Electronic Engineering, Yonsei University) ;
  • Baek, Seung-Mook (Division of Electrical, Electronic, and Control Engineering, Kongju National University)
  • 투고 : 2017.06.02
  • 심사 : 2017.08.28
  • 발행 : 2018.01.01

초록

This paper proposes pre-analysis on planning of high-voltage direct current (HVDC) transmission system applied to Korea electric power grid. HVDC transmission system for interface lines has been considered as alternative solution for high-voltage AC transmission line in South Korea since constructing new high-voltage AC transmission lines is challenging due to political, environmental and social acceptance problems. However, the installation of HVDC transmission system as interface line in AC grid must be examined carefully. Thus, this paper suggests three scenarios to examine the influences of the installation of HVDC transmission system in AC grid. The power flow and contingency analyses are carried out for the proposed scenarios. Power reserves in metro area are also evaluated. And then the transient stability analysis focusing on special protection scheme (SPS) operations is analyzed when critical lines, which are HVDC lines or high voltage AC lines, are tripped. The latest generic model of HVDC system is considered for evaluating the impacts of the SPS operations for introducing HVDC system in the AC grid. The analyses of proposed scenarios are evaluated by electromechanical simulation.

키워드

E1EEFQ_2018_v13n1_105_f0001.png 이미지

Fig. 1. Planned power plant in east-sea side and theproposed transmission for its installations in theKorea electric power grid

E1EEFQ_2018_v13n1_105_f0002.png 이미지

Fig. 2. Generator angle responses when two 765 kV T/L #3lines are tripped: (a) without generator trip; (b) with1 generator trip

E1EEFQ_2018_v13n1_105_f0003.png 이미지

Fig. 3. Bus voltage responses when two 765 kV T/L #3lines are tripped: (a) without generator trip; (b) with1 generator trip

E1EEFQ_2018_v13n1_105_f0004.png 이미지

Fig. 4. Transmitted power responses with 1 generator tripwhen two 765 kV T/L #3 lines are tripped

E1EEFQ_2018_v13n1_105_f0005.png 이미지

Fig. 5. Generator angle responses in SN 2 when 765 kVT/L #1 two-lines are tripped: (a) 2 generators trip;(b) 3 generators trip

E1EEFQ_2018_v13n1_105_f0006.png 이미지

Fig. 6. Bus voltage responses in SN 2 when 765 kV T/L #1two-lines are tripped: (a) 2 generators trip; (b) 3generators trip

E1EEFQ_2018_v13n1_105_f0007.png 이미지

Fig. 7. HVDC responses when 765 kV T/L #1 two-lines aretripped with 3 generators trip: (a) active power; (b)reactive power; (c) alpha; (d) gamma; (e) DCvoltage; (f) DC current

E1EEFQ_2018_v13n1_105_f0008.png 이미지

Fig. 8. Generator angle responses when 765 kV T/L #3two-lines are tripped in SN 3: (a) without generatortrip; (b) 1 generator trip

E1EEFQ_2018_v13n1_105_f0009.png 이미지

Fig. 9. Bus voltage responses when 765 kV T/L #3 two-lines are tripped in SN 3: (a) without generator trip;(b) 1 generator trip

E1EEFQ_2018_v13n1_105_f0010.png 이미지

Fig. 10. HVDC responses when 765 kV T/L #3 two-linesare tripped with 1 generator trip: (a) active power:(b) reactive power; (c) alpha; (d) gamma; (e) DCvoltage; (f) DC current

E1EEFQ_2018_v13n1_105_f0011.png 이미지

Fig. 11. (a) Generator angle; (b) Bus voltage when 765 kVT/L #1 two-lines are tripped with 2 generators tripby applying overload capability

E1EEFQ_2018_v13n1_105_f0012.png 이미지

Fig. 12. HVDC responses when 765 kV T/L #1 two-linesare tripped with 2 generators trip by applyingoverload capability: (a) active power; (b) reactivepower; (c) alpha; (d) gamma; (e) DC voltage; (f)DC current

Table 1. Proposed scenarios of interface transmission systems for planned generations

E1EEFQ_2018_v13n1_105_t0001.png 이미지

Table 2. Interface power flows and interface line loadings of SN 1 in N ? 1 contingency

E1EEFQ_2018_v13n1_105_t0002.png 이미지

Table 3. Interface power flows and interface line loadings of SN 2 in N ? 1 contingency

E1EEFQ_2018_v13n1_105_t0003.png 이미지

Table 4. Interface power flows and interface line loadings of SN 3 in N ? 1 contingency

E1EEFQ_2018_v13n1_105_t0004.png 이미지

Table 5. Power reserve in metro area with the proposed scenarios

E1EEFQ_2018_v13n1_105_t0005.png 이미지

Table 6. SPS analyses of critical line trip on SN 1

E1EEFQ_2018_v13n1_105_t0006.png 이미지

Table 7. SPS analyses of critical line trip on SN 2

E1EEFQ_2018_v13n1_105_t0007.png 이미지

Table 10. SPS analyses of critical line trip on SN 3

E1EEFQ_2018_v13n1_105_t0010.png 이미지

참고문헌

  1. DongHee Choi, Soo Hyoung Lee, Yong Cheol Kang, and Jung-Wook Park, "Analysis on Special Protection Scheme of Korea electric power grid by Fully Utilizing STATCOM in a Generation Side," IEEE Transactions on Power Systems, vol. 32, no. 3, pp. 1882-1890, May 2017. https://doi.org/10.1109/TPWRS.2016.2597307
  2. Jochen Kreusel and Dietmar Retzmann, "Integrated AC/DC Transmission Systems - Benefits of Power Electronics for Security and Sustainability of Power Supply," Power System Computation Conference, 2008.
  3. DUSAN POVH, "Use of HVDC and FACTS," PROCEEDINGS OF THE IEEE, vol. 88, no. 2, February 2000.
  4. P. M. Anderson and B. K. LeReverend, "Industry Experience with Special Protection Scheme," IEEE Trans. on Power Systems, vol. 11, no. 3, pp. 1166-1179, Aug. 1996. https://doi.org/10.1109/59.535588
  5. Ministry of Trade, Industry and Energy, "6th basic plan of long-term electricity supply and demand," Feb. 2013.
  6. Ministry of Trade, Industry and Energy, "2nd Master Plan for National Energy" Jan. 2014.
  7. Erik Ela, Michael Milligan, and Brendan Kirby, "Operating Reserves and Variable Generation," NERL Technical Report, August 2011.
  8. Prabha Kundur, Power System Stability and Control, McGraw-Hill, 1994.
  9. WECC HVDC Task Force, "Planning Models for High-Voltage Direct Current (HVDC) Transmission Systems - Draft Work," July 2011.