• Title/Summary/Keyword: SF$_{}$ 6/ gas circuit breaker

Search Result 55, Processing Time 0.027 seconds

Influence of $SF_6$ Gas On An Arc Plasma In UHV Circuit Breaker ($SF_6$ gas가 초고압 차단기 내에서 Arc Plasma에 미치는 영향)

  • Choi, Kyung-Chuel;Whang, Ki-Woong
    • Proceedings of the KIEE Conference
    • /
    • 1987.11a
    • /
    • pp.278-282
    • /
    • 1987
  • Computational and theoritical investigations of an arc plasma have been made for the design of a circuit breaker. Modeling of an arc plasma used to be very involved and difficult because of the many variables and factors, In this paper, the dynamic behavior of an arc plasma is investigated by solving the MHD equations. Comparing an $SF_6$-blast arc with a non-blast arc, it has been found that the effect of gas-blast has a great influence on density rather than temperature.

  • PDF

Study on the Measurement of Radiation Energy of the Arc in GCBs (가스차단기내 아크의 복사에너지 측정에 관한 연구)

  • Song, Ki-Dong;Oh, Yeon-Ho;Chong, Jin-Kyo;Cho, Young-Sung
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.56 no.12
    • /
    • pp.2122-2126
    • /
    • 2007
  • A special PM-Tube(Photo Multiplier Tube) that is using the photoelectric effect has been designed and manufactured to measure the radiation energy of arc in a gas circuit breaker(GCB). The PM-Tube, LLG(liquid light guides), ND(neutral density) filter, and a model gas circuit breaker have been combined for the reception and the transmission of the light and a simplified synthetic test facility with the arc energy measuring system has been established. In the case of $SF_6$ gas pressure $5kg.f/cm^2$ and arc length 20mm, the radiation energy increases with the arc current but it tend to be saturated in the above 20kA. Under the arc current 20kA, the total radiation energy has the biggest value around 8kA and was not exceeded 40% of the total arc energy.

The development of computational fluid dynamics tools for thermal expansion type interrupter with the arc rotary (아크회전과 열팽창 방식을 적용한 소호부에 대한 아크유동 해석)

  • Choulkov, Victor;Lee, B.W.;Seo, J.M.
    • Proceedings of the KIEE Conference
    • /
    • 2000.07b
    • /
    • pp.813-815
    • /
    • 2000
  • This paper is concerned with the development of PC based computer simulation and design tools for auto-expansion SF6 circuit breaker with the arc rotary. The simulation model takes into account radiation transport, turbulence enhanced momentum. energy transport. The conversation gas dynamic equation together with Maxwells equations are solved. For the arc simulation the straightforward procedure has been used. The temperature, gas density and velocity space distributions within the circuit breaker are simulated in details. The presented results show that the computer simulation of gas flow in SF6 interrupter is a subject of much interest for design and optimization of contacts. The presented results show that the shape and sizes of contacts are chosen by this tool from judiciously compromise between electrical breakdown strength and interruption ability that are functions of gas flow parameters.

  • PDF

Steady State Analysis of Nozzle Ablation Under High Temperature and High Pressure Arc Plasma (고온ㆍ고압 아크 플라즈마 하에서의 정상상태 노즐용삭 해석 기술)

  • 이병윤;송기동;정진교;박경엽
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.52 no.9
    • /
    • pp.395-399
    • /
    • 2003
  • In this paper, physical phenomena which are related to the high temperature and high pressure arc plasma generated during the fault current interruption by SF6 gas circuit breakers are reviewed. In particular, in order to analyze nozzle ablation induced by the heats transferred to the surface of the poly-tetrafluoroethylene(PTFE) nozzle through arc radiation, a governing equation for the calculation of PTFE concentration is added to the governing equations for SF6 arc Plasma analysis. The proposed method is applied to the steady state analysis of $SF_6$ arc plasma generated by direct current taking account of the nozzle ablation and the results are presented.

Analysis of Cold Gas Flow in Puffer Type GCB Considering the Real Gas Property of $SF_6$ ($SF_6$ 가스의 실제 기체특성을 고려한 파퍼식 가스차단기 내의 냉가스 유동해석)

  • 김홍규;정진교;박경엽
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.53 no.3
    • /
    • pp.129-134
    • /
    • 2004
  • To analyze the performance of the gas circuit breaker(GCB), the flow field variables such as temperature, pressure and density should be evaluated accurately In the puffer chamber of puffer type GCB, the pressure rise may Exceed 20 bar and in this range of high pressure, $SF_6$ gas deviates the ideal gas property. Therefore, the real gas property of $SF_6$ should be taken into consideration for the accurate analysis of flow field. This paper presents the analysis technique of cold gas flow in GCB employing the real gas state equation of SF6. The FVFLIC method is Employed to solve the axisymmetric Euler equation. To reduce the computational effort of real gas state equation, the relationship between density and pressure is approximated by the polynomial at the temperature of 300K. The proposed method is applied to the test GCB model and simulation results show good agreement with the experimental ones.

Prediction of Insulation Capability for Ground Fault to Consider Asymmetry in SF6 Circuit Breaker

  • Oh, Yeon-Ho;Song, Ki-Dong;Kim, Hong-Kyu;Lee, Hae June;Hahn, Sung-Chin
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.5
    • /
    • pp.2046-2051
    • /
    • 2015
  • Currently, most high-voltage gas circuit breakers (CBs) include asymmetrical geometries in the shield, the tank, the hot-gas exhaust, and the connection parts for bushings. For this reason, a 3-dimensional (3-D) analysis of the insulation capability is necessary, rather than a 2-D analysis. However, a 3-D analysis has difficulties due to the computational time and complex modeling. This paper presents a 3-D analysis considering the asymmetry in high-voltage gas CBs and a technique to reduce the calculation time. In the proposed technique, the arc plasma requiring the most computational time is first calculated by a 2-D analysis. Then, the results such as pressure, temperature, and velocity are input as a source for the 3-D analysis. This technique is applied to a 145kV self-blast-type CB and the analysis result exhibits good agreement with the experimental result.

Breaking test of UHV circuit breaker by ANSI/IEEE standard (ANSI/IEEE를 적용한 초고압 차단기의 차단시험)

  • Park, Seung-Jae;Rhyou, Hyeong-Kee;Kang, Young-Sik;Koh, Heui-Seog
    • Proceedings of the KIEE Conference
    • /
    • 2003.07a
    • /
    • pp.467-469
    • /
    • 2003
  • IEC(International Electrotechnical Commission) 62271-100 has been adopted for the design test of circuit breaker which is used as the main protecting device of power system. But, it is also necessary to separately receive the testing certificate in accordance with ANSI/IEEE standard for getting into the american market. Up to now, several domestic companies have completed the ANSI/IEEE testing in medium circuit breaker of distribution system, but they recently started the ANSI/IEEE testing in ultra high-voltage class of transmission and substation system. This paper introduces the testing techniques and its results for the making and breaking performance of 145kV, 40kA $SF_6$ gas circuit breaker which was firstly performed in KERI(Korea Electrotechnology Institute) by the ANSI/IEEE standard.

  • PDF

Performance Evaluation of a $SF_6$ Gas Circuit Breaker with Experimental Investigation (초고압 $SF_6$ 가스 차단기의 실험적 차단성능 평가)

  • Jeong, Y.W.;Park, H.T.;Oh, I.S.
    • Proceedings of the KIEE Conference
    • /
    • 2005.11a
    • /
    • pp.96-99
    • /
    • 2005
  • In this study, we build system and techniques of evaluating the interruption performance of the GCB with experimental method. We constructed a simplified synthetic test circuit of which ability is up to 245kV, 50kA BTF test. And We composed a model test circuit breaker with puffer assisted self blasting type GCB. With this circuit breaker, we carried out the experiment of no load and SLF90. During the tests, we measured the several factors such as stroke, pressure, arc temperature, the voltage and current near the current zero and dI/dt, dV/dt. Arc conductivity before 200ns before current zero which is one of the indexes of the thermal recovery of a GCB was measured. With these kinds of measurement, we could estimate the performance of a GCB fundamentally. Futhermore these results were used to adjust the arc modeling with CFD(computational fluid dynamics) and we could increase the plausibility of the analytical method.

  • PDF

Lightning Impulse Breakdown Characteristic of Dry-Air/Silicone Rubber Hybrid Insulation in Rod-Plane Electrode

  • Kwon, Jung-Hun;Seo, Cheong-Won;Kim, Yu-Min;Lim, Kee-Joe
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.3
    • /
    • pp.1181-1187
    • /
    • 2015
  • Sulfur hexafluoride (SF6) gas is used widely in electric power equipment such as Gas Insulated Switchgear (GIS), Gas Insulation transmission Line (GIL), and Gas Circuit Breaker (GCB). But applications of SF6 should be restricted because SF6 gas is one of the greenhouse effect gases. To reduce use of SF6 gas, a study on eco-friendly alternative insulation medium is needed. In this paper, we investigated lightning impulse (LI) breakdown of dry-air which is attracting attention as an ecofriendly alternative gas and the LI breakdown of hybrid insulation combined with dry-air and solid insulation (Room-Temperature Vulcanizing Silicone Rubber-RTV SIR) and dry-air in inhomogeneous fields according to gap distance and pressure. The experiment results showed that the LI breakdown strength of hybrid insulation system was higher than that of dry-air insulation system. It was verified that the development of technology related to eco-friendly power apparatus compact such GIS, GCB and GIL can be used as basic research data.

Fault Analysis of a Gas Circuit Breaker in the 154kV Power Line (154kV 전력계통 가스차단기 고장 분석)

  • Kim, Young-Kyu;Ko, Young-Hoan;Jung, Lee-Sig;Lee, Sang-Il
    • Proceedings of the KIEE Conference
    • /
    • 2008.11a
    • /
    • pp.342-344
    • /
    • 2008
  • This paper describes fault analysis of a $SF_6$ gas circuit breaker of a transformer in a hydro power plant which is connected to the 154kV line. The fault is a single-line-to-ground fault, so that it gives power generation halt and economical loss. The analysis has been done in aspects of the status of the breaker, insulation degradation, surge invasion and earthing resistance of the switchyard.

  • PDF