DOI QR코드

DOI QR Code

Lightning Impulse Breakdown Characteristic of Dry-Air/Silicone Rubber Hybrid Insulation in Rod-Plane Electrode

  • Kwon, Jung-Hun (Dept. of Electrical and Electronic Engineering, Chungbuk National University) ;
  • Seo, Cheong-Won (Dept. of Electrical and Electronic Engineering, Chungbuk National University) ;
  • Kim, Yu-Min (Dept. of Electrical and Electronic Engineering, Chungbuk National University) ;
  • Lim, Kee-Joe (Dept. of Electrical and Electronic Engineering, Chungbuk National University)
  • 투고 : 2014.07.29
  • 심사 : 2014.11.29
  • 발행 : 2015.05.01

초록

Sulfur hexafluoride (SF6) gas is used widely in electric power equipment such as Gas Insulated Switchgear (GIS), Gas Insulation transmission Line (GIL), and Gas Circuit Breaker (GCB). But applications of SF6 should be restricted because SF6 gas is one of the greenhouse effect gases. To reduce use of SF6 gas, a study on eco-friendly alternative insulation medium is needed. In this paper, we investigated lightning impulse (LI) breakdown of dry-air which is attracting attention as an ecofriendly alternative gas and the LI breakdown of hybrid insulation combined with dry-air and solid insulation (Room-Temperature Vulcanizing Silicone Rubber-RTV SIR) and dry-air in inhomogeneous fields according to gap distance and pressure. The experiment results showed that the LI breakdown strength of hybrid insulation system was higher than that of dry-air insulation system. It was verified that the development of technology related to eco-friendly power apparatus compact such GIS, GCB and GIL can be used as basic research data.

키워드

1. Introduction

SF6 gas chemically is extremely stable and not only has excellent insulation performance compared with other gases but also outstanding current block and arc extinguishing capability [1]. So gas insulated high voltage equipment such as Gas Insulated Switchgear (GIS), Gas Insulation transmission Line (GIL), and Gas Circuit Breaker (GCB) in electric power applications have been mainly used in pressured SF6 gas. SF6 significantly contributed to reduce economic costs and size of the highvoltage equipment for a GIS, GCB and GIL. The emission of SF6 gas into the atmosphere needs to be reduced drastically because SF6 gas is one of the greenhouse gases [2-8].

Accordingly, to reduce amount of SF6 gas the researchers on an alternative insulated medium in a various ways are active situation over the world. Studies on mixed with N2, CO2 and other gases have been proceeding to reduce amount of SF6 gas [9]. SF6 /N2 mixture gas is known as a valid current breaking medium [10]. SF6 /CO2 mixture gas has been reported to have more excellent insulation characteristics than SF6 /N2 mixture gas [11-13]. Also in non-uniform electric field, SF6 /air and SF6 /CO2 mixture gas showed a higher breakdown strength than breakdown strength of SF6 gas and by addition of 1% CO2 in 50% SF6 / N2 gas mixture, breakdown strength has been reported to be more increased than breakdown strength of SF6 /N2 and SF6 respectively 1.31 and 1.15 times [14-15]. But in case of these mixture gases, there are problems that do not completely ban the use of SF6. Therefore, for the development of eco-friendly gas insulated component that does not use SF6 gas at all, research on Solid Insulated Switchgear (SIS), Dry-Air Insulated Switchgear (DAIS), and Nitrogen Insulated Switchgear (NIS) is being actively conducted and distribution class power apparatus has already been commercialization. However, because such the insulating strength of an alternative insulating gas is considerably lower than dielectric strength of SF6 gas, in order to obtain required dielectric strength it is necessary to maintain very high pressures of the gas. So comercialization is difficult over distribution class yet.

Studies on the dry-air, which is attracting attention as an eco-friendly alternative gas, have been mainly studied in the uniform and non-uniform electric field [16-18]. Although there are many non-uniform electric fields in actual high voltage equipment, these researches are not many. Also the field utilization factor is an important design criterion that is dependent on the shape of the components and inner structures [19-20]. Therefore, the insulation design has to the lowest field utilization. So in this paper field utilization factor is less than 0.5 and discharge characteristic process studied at extreme non-uniform field according to gap distance and pressure. Since the dielectric strength of the dry air is one third of the level of SF6 gas and breakdown is mainly starts from weak point where the electric field is concentrated and it lead to whole breakdown of equipment. When such an electrical weak point is coated with a solid dielectric, it is possible to obtain the electric field relaxation effect [21-24].

To obtain an eco-friendly alternative insulated methods of SF6, This paper examines lightning impulse breakdown characteristic of hybrid insulation combined with dry-air and solid insulation in inhomogeneous field having a field utilization factor of range 0.1 to 0.4.

 

2. Experiments

2.1 Experimental setup

All experiments were carried out in a laboratory gas chamber made of stainless steel having 200 mm diameter and 200 mm height. The gas chamber which connected to the high pressure dry-air cylinder was evacuated to residual pressure of 1×10−6 Torr and then filled with dry-air. Gas pressure confirmed pressure gauge of gas chamber. The standard LI voltages (1.2/50 μs) with both polarities were applied using an IVG-600A rated up to 600 kV and has an efficiency of 80 %. Fig. 1 shows a schematic diagram of the test facility.

Fig. 1.Impulse breakdown experimental set-up.

The standard lightning impulse voltages with positive / negative polarities were determined by an up-and-down method until twenty sets of raw data were obtained. With a 63.2% Cumulative Failure Probability (CFP) of a breakdown voltage, the raw data was obtained from the Weibull-distribution. Fig. 2 shows an example of Weibull distribution plot which indicate positive polarity LI breakdown of dry-air at 6 atm.

Fig. 2.Weibull distribution plot

The electrode configuration in the chamber consisted of a hemispherical rod, a dielectric covered (roomtemperature vulcanizing silicone rubber-RTV SIR) hemispherical rod, and an earthed plane electrode. Table 1 and Fig. 3 show the experimental conditions and electrode systems, respectively.

Table 1.The electrode system.

Fig. 3.Bare and coated rod-plane electrode system.

 

3. Results and Discussions

3.1 Lightning impulse breakdown characteristics of dry-air

The lightning-impulse-breakdown voltage of dry-air increased with increasing pressure and gap distance by right region of Paschen’s law, when the pressure and the gap distance increases, the air density is increased and then collision ionization of electrons is decrease so breakdown voltage of dry-air increased as shown in Fig. 4. Under all test conditions, the negative breakdown voltage was higher than the positive breakdown voltage. This polarity effect can be understood as follows: In rod-plane electrodes, such as a non-uniform electric field, the gas breakdown mechanism proceeds in the following order: corona generation, corona progress, and spark discharge. In the case of a rod electrode with an applied negative LI, the initial electron emission is easy and the space charge effect time is short because of field emission or Schottky emission from the rod electrode metal to the gas. In addition, the negative corona generation voltage was reported to be lower than the positive corona voltage. On the other hand, growth of corona is slower than the positive electron avalanche because growth direction of the electron avalanche begins from a high field toward a lower field region. As the case stands, the positive breakdown voltage is lower than the negative breakdown voltage. Fig. 5 shows the extension process of corona positive and negative polarity at a non-uniform field. As indicated in Fig. 5 in the case of a positive corona, the spark discharge can be progressed easily [18, 25-26].

Fig. 4.LI breakdown of dry-air in the rod to plane according to gap distance with various pressure at (a) Positive polarity and (b) Negative polarity.

Fig. 5.Extension process of the corona: (a) Positive polarity; (b) Negative polarity.

The field utilization factor is an important design criterion that is dependent on the shape of the components and inner structures. Therefore, the insulation design is subject to the lowest field utilization. The field utilization factor (η) is defined as the ratio of the average electric field (Emean) and maximum electric field (Emax) [19-20]:

where Vd is the measured breakdown value and d is the gap distance between the rod to plane electrode. The maximum field of the rod to plane electrode is expressed in equation (3.3)

where r is the radius of the rod electrode. Substituting equation (3.3) to equation (3.1), the field utilization between the rod and plane electrode is expressed as equation (3.3). The field utilization is expressed as a function of the electrode distance, as shown Table 2.

Table 2.Electric field utilization factor of the electrode system as a function of the gap distance.

As indicated in Fig. 6, the breakdown strength decreases with decreasing the field utilization factor because the electric field was more concentrated at the tip of the rod electrode. Fig. 7 shows that the maximum electric field is increased with decreasing the field utilization factor.

Fig. 6.Breakdown electric filed strength as a function of the electric field utilization factor in the case of (a) positive polarity and (b) negative polarity

Fig. 7.Maximum electric field at breakdown, Emax.BD according to the field utilization factor in case of (a) positive polarity and (b) negative polarity

3.2 Lightning impulse breakdown characteristic of Dry-Air/Silicone Rubber Hybrid Insulation

The LI breakdown properties of dry-air in the case of adopting electrodes with dielectric coating were examined. The experiments were carried out for rod to plane electrode systems with a 4.5 mm diameter. The coated length of the rod electrode and plane electrode was 12 and 70 mm, respectively. The hybrid insulation system was equivalent to that corresponding to the same conditions in the bare electrode system.

The principal idea of the hybrid insulation system is the intentional use of the surface charge density to re-distribute the electric field within the insulation system. The potential difference between the metal electrodes results in a charge density (±ρe) at the metal surfaces and polarization of the dielectric coating, which is represented by the equivalent polarization charge density (±ρρ). Owing to the electric field, the free charge in the dry-air gap, which is available from ionization discharge or other natural origins, is attracted to the surface of the coating. Together with the charge arising from the bulk condition through the dielectric coating, a surface charge density (±ρs) is formed. As a result, an electric field component is directed in opposite to the original electric field, resulting in decreased electrical stress in the dry-air gap [22-25]. Fig. 8 shows the simple principle, and Fig. 9 is a photograph taken at the breakdown of the hybrid insulation system.

Fig. 8.Basic concept hybrid insulation

Fig. 9.Photograph taken at the breakdown of the hybrid insulation system.

As shown Fig. 10, the LI breakdown voltage of hybrid insulation shows an increase according to the pressure and gap distance and depends on the polarity. Table 3 shows an increasing rate between the measured breakdown voltage of the coated electrode and uncoated electrode. From these results, substantial increase in breakdown voltage can be seen, with the exception of some cases which were attributed to experimental error. After the breakdown, voids were observed inside the specimen. Because the electric field is concentrated in the void after partial discharge occurs, it appears to have lower dielectric strength [27-29].

Fig. 10.Breakdown voltage of the hybrid insulation system: (a) Positive breakdown voltage; (b) Negative breakdown voltage.

Table 3.Increasing rate between the measured breakdown voltage of the coated electrode and uncoated electrode.

Under all test conditions, the positive breakdown voltage was higher than the negative breakdown voltage. This result is different from the bare electrode system. Previous studies reported that the discharge propagation of a covered rod to plane arrangement differs according to the polarity of the rod. At a positive polarity, flashover along the cover surface is followed by breakdown of the air gap. At negative polarity, breakdown of the air gap was followed by flashover along the cover surface, as shown Fig. 11. This can be explained as follows. In the case of positive polarity, the accumulation of surface charge, i.e. electrons, is easy because the mobility of electrons is faster than that of a positive ion. Therefore, the field relaxation effect of air gap was larger than that of the negative polarity because the surface charge density was different between the positive and negative polarity [29-33].

Fig. 11.Breakdown propagation: (a) positive polarity; (b) negative polarity

 

5. Conclusion

The study examined the breakdown characteristics of hybrid insulation in inhomogeneous fields under a lightning impulse voltage. The results can be summarized as follows:

1) LI breakdown voltage of dry-air increased with increasing pressure and gap distance. The negative breakdown voltage was higher than the positive breakdown voltage. The field utilization factor confirmed the important design criteria. 2) The LI breakdown voltage of hybrid insulation increased with increasing pressure and gap distance. The positive breakdown voltage was higher than the negative breakdown voltage. In most cases, the breakdown voltage of the hybrid insulation system increased substantially compared to that of the dry-air insulation system.

Therefore, the development of technology related to ecofriendly power apparatus compact such GIS, GCB and GIL can be used as basic research data.

참고문헌

  1. L. G. Christophorou, J. K. Olthoff and R. J. Van Brunt, “Sulfur Hexafluoride and the Electric Power Industry”, IEEE Electrical insulation Magazine, Vol. 13, No. 5, pp. 20-24, 1997. https://doi.org/10.1109/57.620514
  2. W. Wiegart, “A Model for the Production of Initial Electron by Detachment of. Ions”, IEEE Trans., Vol. PAS-88, No. 10, 1969.
  3. N. H. Malik and A. h. Qureshi, “Breakdown mechanisms in sulphur-hexafluoride”. IEEE Trans. on Elect, Vol. Ei-12, No. 3, pp. 135~145, 1991
  4. S. Yanabu, Y. Murayama, S. Matsmoto, “SF6 Insulation and its Application to HV Equipment” IEEE Trans. Elect, Vol. 26, No. 3, pp. 358~366, 1994.
  5. Y. Yamagata et al., "Development of UHV gas insulated switchgear", Hitachi Hyoron, Vol. 76, p. 21-26.
  6. B. H. Lee, et al, “Dielectric Characteristics of SF6 Gas under Fast Transient Overvoltages in A Non- Uniform Electric Field”, Proc of Int. Conf. on Gas Discharge and Their Application, pp. 1-34-307, 1995
  7. T. Hasegawa, K. Yamaji, M. Hatano, F. Endo, T. Rokunohe, and T. Yamagiwa, “Development of insulation structure and enhancement of insulation reliability of 500kV DC GIS”, IEEE Trans Power Del., Vol. 12, No. 1, pp. 194~202, Jan. 1997 https://doi.org/10.1109/61.568241
  8. M. Yaegashi, T. Ishiguro, K. Ohkubo, N. Yaginuma and H. Kawamoto, “Development of 362 kV 63 kA gas circuit breaker”, Nat. Convention Rec., IEEJ No. 6-210, pp. 358~359, 2003.
  9. A. H. Cookson and B. O. Pedersen, “High voltage performance of mixtures of with, air and in compressed gas-insulated equipment”, 1978 IEE Conf. on Gas Discharge, IEE Conf. Publ. No. 165, pp. 161~164, 1978.
  10. Yamada T, Ishida T, Hayakawa N, Okubo H, "Partial discharge and breakdown mechanism in ultra-dilute SF6/N2 GAS MIXTURES", IEEE Trans DEI Vol. 8, No. 1, pp. 137-142, 2001.8. https://doi.org/10.1109/94.910436
  11. A. H. Cookson and B. O. Pedersen, “High voltage performance of mixtures of with, air and in compressed gas-insulated equipment”, 1978 IEE Conf. on Gas Discharge, IEE Conf. Publ. No. 165, pp. 161~164, 1978.
  12. D. Zheng, P. Zhang, G. Gong, Z. Wen: “Study about the Electrical Behaviour of the Binary Gaseous Mixtures of”, Proc. of 1998 Intern. Symp. on Elect. Insul. Master, Toyohashi, Japan, Sept. 27-30, pp.437-440, 1998.
  13. Y. Qiu, E. Kuffel, “Comparison of and Gas Mixtures as Alternatives to Gas”, IEEE Trans. Dielec. Elec. Insul., Vol. 6, No. 6, pp. 892-895 Dec. 1999 https://doi.org/10.1109/94.822033
  14. X.Q. Qiu, I.D. Chalmers, P. Coventry : “A studt of alternative insulating gases to”, J.Phys.D: Appl. Phys. 32, pp. 2918-2922, 1999. https://doi.org/10.1088/0022-3727/32/22/314
  15. S. Ohtsuka, S. Nagara, K. Miura, M. Nakamura, M. Hikita, “Effect of Mixture of a Small Amount of in Mixed Gas on the Insulation Performance under Nonuniform Field”, Conf, Record of the 2000 IEEE Intern. Symposium on Electrical Insulation, Anaheim, CA USA, April 2-5, pp. 288-291, 2000.
  16. Akyuz, M., Positive Streamer discharges in air and along insulator surface: experiment and simulation. 2002, University of Uppsala.
  17. Akyuz, M., A. Larsson, V. Cooray, and G. Sandberg, 3D simulations of streamer branching in air. Journal of Electrostatics, 2003, issue 59:115-141
  18. Feng Li, Y-H Yoo, D-K Kim, B-K lee “Dielectric Characteristic of SF6 and Dry-Air Gases under Lightning Impulse Voltage”, Journal of the Korean of Institute of illumination and Elec Insul Eng, pp. 142~149, 2010.
  19. E. Kuffel, "High-voltage Engineering-Fundamentals, Press 1984, ISBN 0-08-024213-8.
  20. T. Nitta, Y. Shibuya, Y. Fujiwara, “Voltage-time characteristics of Electrical Breakdown in SF6”, IEEE Trans., Vol. PAS-94, No. 1, pp. 108~115, 1975.
  21. F.M “Charge accumulation in rod-plane air gap with covered rod”, PhD Thesis, Norwegian University of Science and Technology, 2006.
  22. H. J. M. Blennow, M L-A, Sjöberg, M. À. S. Leijon and S. M. Gubansk, "Electric Field Reduction Due to Charge Accumulation in a Dielectric-Covered Electrode System", IEEE Trans DEI Vol. 7, No. 3, pp. 340-345. https://doi.org/10.1109/94.848912
  23. H. J. M. Blennow, M. Å. S. Leijon, S.M. Gubanski, “Active High Voltage Insulation”, Journal of Electrostatics Vol. 55, issue 2, pp. 159-172, June 2002. https://doi.org/10.1016/S0304-3886(01)00189-9
  24. Sjöberg, M., Charge Accumulation in Hybrid High-Voltage Insulation, PhD Thesis, Chalmers University of Technology, 2003,
  25. H. K Kang, J B. Nah, Y. D. Chung, M. C. Ahn, D. K. Bae, T. K. Ko, “Study on the Breakdown Voltage Characterization of Insulation Gases for Developing a High Voltage Superconducting Apparatus”, IEEE Trans on Applied superconductivity, Vol. 20, No. 3, pp. 1646~1649, 2010. https://doi.org/10.1109/TASC.2010.2041342
  26. Hermann Karner, “High Voltage Insulation Technology”, Press 1985, ISBN 3-528-08599-1.
  27. K. Mekala, S. Chandrasekar and R. Samson Ravindran, “Investigations of Accelerated Aged Polymeric Insulators Using Partial Discharge Signal Measurement and Analysis”, Journal of Electrical Engineering & Technology, vol. 10, no. 1, pp. 299- 307, 2015. https://doi.org/10.5370/JEET.2015.10.1.299
  28. V. Jayaprakash Narayanan, B. Karthik and S. Chandrasekar, “Flashover Prediction of Polymeric Insulators Using PD Signal Time-Frequency Analysis and BPA Neural Network Technique”, Journal of Electrical Engineering & Technology, vol. 9, no. 4, pp. 1375-1384, 2014. https://doi.org/10.5370/JEET.2014.9.4.1375
  29. Jian Lin Yan Wang and Lianwei Bao, “Space Charge Behavior of Oil-Impregnated Paper Insulation Aging at AC-DC Combined Voltages”, Journal of Electrical Engineering & Technology, vol. 9, no. 2, pp. 635-642, 2014. https://doi.org/10.5370/JEET.2014.9.2.635
  30. G. Baldo and G. Pesaven, “Impulse Performance of Air Gaps in Series with Thick Insulating Layers”, Proc 5th Int. Symp. On HV Engineering, paper no. 14. 25, Braunschweig, Germany, 1987.
  31. Walfridsson, L., et al. Solid Insulation Covering of Conductors Improves Air Insulation System. Int. Conference on Conduction and Breakdown in Solid Dielectric in Compresses Gases: A Review. IEEE Transaction on Electrical Insulation, Vol. 21, issue 5, October 1986.
  32. L. Ming, U. Fromm, M. Leijon, D. Windmar, L Walfridsson, A. Vlastos, M. Darveniza and J. Kucera, “Insulation Performance of Covered Rod/Plane Air Gap under Lightning Impulse Voltage”, Proc. 10th Int. on HV Engineering, paper no. 3236, Montreal, Canada, 1997.
  33. E. H. Kreuger, Industrial high dc voltage, Delft University Press, ISBN 90_407_1110_0, The Netherlands, 1995.