• Title/Summary/Keyword: Roof ventilator

Search Result 9, Processing Time 0.02 seconds

The Study on the Improvement of Ventilation Performance in the Soundproof Tunnel (방음터널의 자연환기성능 향상에 대한 연구)

  • Lee Kyung-Hee;Cho Sung-Woo;Choi Jeong-Min;Kim Kyung-hwan;Park Chang-Sub
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.10
    • /
    • pp.922-929
    • /
    • 2005
  • This paper compared ventilation performance between the sound roof tunnel with flat roof and the sound roof tunnel with gable roof. The ventilation rate of the sound roof tunnel is calculated by natural ventilation rate plus ventilation by vehicle. The roof type is divided by the shape of the roof and the ventilator location on the roof. The results between calculation and CFD on the ventilation rate are almost alike. The ventilation rate on the flat roof is $558.4\;m^3/s$ with mid-ventilator and $496.8\;m^3/s$ with left-right ventilator. The ventilation rate on the gable roof is $653.2\;m^3/s$ with mid-ventilator and $611.6\;m^3/s$ with left-right ventilator. The ventilation rate of soundproof with gable roof is higher than that with flat roof. The ventilation rate and with mid-ventilator is higher than that with left-right ventilator the soundproof roof. Therefore, the ventilation performance of soundproof roof depends on the roof shape and ventilator location on the roof.

Study on the Performance Evaluation of the Exhaust Stack used in High Riser Public House (초고층공동주택 국소배기용 입상덕트의 배기성능평가에 관한 연구)

  • Kwon, Yong-il;Lee, Tae-Kyu;Ahn, Jung-Hun
    • Proceedings of the SAREK Conference
    • /
    • 2008.06a
    • /
    • pp.889-894
    • /
    • 2008
  • Exhaust system used in toilet and cooking place of high riser public house is roof fan of two basic types : natural roof ventilator and natural/forced roof ventilator. Natural/forced roof ventilator has a motor in the rotary shaft. There are many high riser public house in Korea. These buildings were not viewed as being major contributors to exhaust pollutants producted in indoor. It was because many engineers thought that exhaust in high riser building depend on stack effect. This study investigates on stack pressure determined by exterior pressure and the difference pressure control in exhaust stack used in high riser public house. This paper focuses mainly on the effect of the time interval for power supply of motor installed in roof fan with function of natural wind velocity and of exhaust air volume of toilet. It is observed there are higher exhaust efficiency than the existing natural roof ventilator.

  • PDF

The Performance Evaluation of the Exhaust Stack used in High Riser Public House (초고층 공동주택 국소배기용 입상덕트의 배기성능평가)

  • Kwon, Yong-Il;Kim, Ung-Yong;Shin, Hyun-Gon
    • Journal of the Korea Organic Resources Recycling Association
    • /
    • v.22 no.3
    • /
    • pp.60-67
    • /
    • 2014
  • Exhaust system used in toilet and cooking place of high riser public house is roof fan of two basic types : natural roof ventilator and natural/forced roof ventilator. Natural/forced roof ventilator has a motor in the rotary shaft. There are many high riser public house in Korea. These buildings were not viewed as being major contributors to exhaust pollutants producted in indoor. It was because many engineers thought that exhaust in high riser building depend on stack effect. This study investigates on stack pressure determined by exterior pressure and the difference pressure control in exhaust stack used in high riser public house. This paper focuses mainly on the effect of the time interval for power supply of motor installed in roof fan with function of natural wind velocity and of exhaust air volume of toilet. It is observed there are higher exhaust efficiency than the existing natural roof ventilator.

Study on the Control Performance Evaluation of the Exhaust Stack used in High Riser Public House (초고층공동주택 국소배기용 입상덕트시스템의 제어성능평가에 관한 연구)

  • Kwon, Yong-Il;Ahn, Jung-Hun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.2
    • /
    • pp.103-108
    • /
    • 2009
  • Local exhaust system used in toilet and cooking place of low-rise public house installed roof ventilator at terminal of stack. There are many high riser public houses in Korea. These buildings were not viewed as being major contributors to exhaust pollutants producted in indoor. It was because many engineers thought that exhaust in high riser public house depends on stack effect. But Neutral pressure level represents in a terminal of stack with air tightness for the best exhaust efficiency. Thereby, lower floors have the worst indoor air quality. This paper focuses mainly on the exhaust efficiency improved by roof fan with motor installed in high riser public house. It is observed there is higher exhaust efficiency than the existing natural roof ventilator.

Evaluation of Ventilation Efficiency for Various Gravity Ventilators (자연환기 벤틸레이터 형태에 따른 환기효율 평가)

  • 하현철;김태형
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.14 no.7
    • /
    • pp.543-551
    • /
    • 2002
  • Gravity ventilators allow the escape of the warm air and air contaminants due to both (either) buoyancy and (or) convection. As a natural ventilation strategy, various gravity ventilators can be installed on the roof. Ventilation efficiency could be affected by various parameters, such as, area of openings, wind velocity and incidence angle, temperature difference between inside and outside, and shape of ventilator. Especially, the shape of roof gravity ventilator might be one of influencing factors for the effective ventilation. The window type gravity ventilators are frequently installed instead of general (standard) gravity ventilator. However, the ventilation efficiencies of them were not proved yet. To compare the ventilation efficiency, general type ventilator and two window type ventilators were numerically tested. Mean age of air, temperature and CO concentration were predicted by using commercial CFD code, AIRPAK (Ver. 2.0) with various conditions. The predicted result showed that general type ventilator is more effective for natural ventilation than window type ventilators.

Numerical Study on the Natural-Convection in a Shaft of an Apartment (공동주택 연도 내의 자연 대류를 고려한 열-유동 해석)

  • Park, Sung-Geun;Kim, Sang-Gyu;Yong, Ho-Taek;Choi, Hyoung-Gwon
    • Proceedings of the SAREK Conference
    • /
    • 2005.11a
    • /
    • pp.88-93
    • /
    • 2005
  • In this paper, the heat and fluid flow analysis in a shaft of an apartment has been performed in order to investigate the pressure distribution inside a shaft considering both natural and forced convection. The present CFD approach can be used in estimating the capacity of roof ventilator of an apartment reasonably. Furthermore, flow patterns inside a shaft have been examined for some operating conditions of hood system.

  • PDF

Full-scale study of wind loads on roof tiles and felt underlay and comparisons with design data

  • Robertson, A.P.;Hoxey, R.P.;Rideout, N.M.;Freathy, P.
    • Wind and Structures
    • /
    • v.10 no.6
    • /
    • pp.495-510
    • /
    • 2007
  • Wind pressure data have been collected on the tiled roof of a full-scale test house at Silsoe in the UK. The tiled roof was of conventional UK construction with a batten-space and bitumen-felt underlay beneath the interlocking concrete tiles. Pressures were monitored on the outer surface of selected tiles, at several locations within the batten-space, and beneath the underlay. Data were collected both with and without ventilator tiles installed on the roof. Little information appears to exist on the share of wind load between tiles and underlays which creates uncertainty in the design of both components. The present study has found that for the critical design case of maximum uplifts it would be appropriate to assign 85% of the net roof load to the tiles and 15% to the underlay when an internal pressure coefficient of -0.3 is used, and to assign 60% to the tiles and 50% to the underlay when an internal pressure coefficient of +0.2 is assumed (an element of design conservatism is inherent in the apparent 110% net loading indicated by the latter pair of percentage values). These findings indicate that compared with loads implied by BS 6399-2, UK design loads for underlay are currently conservative by 25% whilst tile loads are unconservative by around 20% in ridge and general regions and by around 45% in edge regions on average over roof slopes of $15^{\circ}-60^{\circ}$.

A Basic Study on Application of Small Wind Power System Combined Ventilator in Super High-rise Apartment (1) (초고층 공동주택의 배기겸용 소형풍력발전 적용을 위한 기초연구(1))

  • Park, Jung-Ha;Kim, Jin-Woo;Jang, Ho-Jin;Park, Jin-Chul;Hwang, Jung-Ha
    • Journal of the Korean Solar Energy Society
    • /
    • v.31 no.3
    • /
    • pp.126-132
    • /
    • 2011
  • Recently, high-rise apartment is being briskly built but there are problems such as lack of ventilation, stack effect and much energy consumption. Therefore It is recommended to develop a Small Wind Power System Combined Ventilator as a solution to solve these problems. The purpose of this study is to provide basis for Small Wind Power System Combined Ventilator in super high-rise apartment. This study conducted CFD simulation (Star-CCM) according to the shape of structures, building height and distance of two structures to identify the effect of wind speed increase when the structure is installed. As a result, pyramidal type was best suited for increase of wind speed. The best place was the front of the roof to main wind direction, and the best building height was 200m rather than 300m. If two or more small wind turbines combined ventilator are installed closely, vertical position to main wind direction is recommended. Horizontal position must necessarily be avoided, but height difference between two blades more than 3m showed good performance.

Simulation of the Kitchen and Bathroom Exhaust Systems in High-Rise Apartment Buildings (고층 아파트의 주방 및 욕실 배기 시스템 시뮬레이션)

  • 김영돈;김광우
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.12
    • /
    • pp.996-1006
    • /
    • 2003
  • The objective of this study is to find major variables which influence the performance of kitchen and bathroom exhaust systems in high-rise apartment buildings. For this purpose, the influencing factors on the exhaust airflow rates from the kitchen or bathroom are identified and in every cases, which are made of combinations between the influencing factors, the exhaust airflow rates are calculated through the simulations. The results of the simulation show that the exhaust airflow rates from the kitchen and bathroom mainly depends on outdoor air temperature, number of floors, airtightness of the building envelope, fan on ratio, vertically connected to same shaft, exhaust fan capacity for kitchen or bathroom, roof ventilator capacity and shaft area for kitchen or bathroom exhaust.