• 제목/요약/키워드: Resistive SFCL

검색결과 120건 처리시간 0.026초

Operating Properties of Resistive Superconducting fault Current Limiters with Various Pattern Shapes

  • Park, Hyo-Sang
    • 한국전기전자재료학회논문지
    • /
    • 제16권12S호
    • /
    • pp.1286-1291
    • /
    • 2003
  • Quench behavior of resistive superconducting fault current limiters (SFCLS) with various pattern shapes was investigated. The pattern shapes employed were meander, bi-spiral, and spital shapes of identical line width, gap and margin. SFCLS were fabricated from YBCO thin films grown on two-inch diameter Al$_2$O$_3$ substrates under the same conditions. The total length of current limiting paths was the shortest at the spital shape due to its larger useless space. Inductance component of SFCLs with the spiral shape was around two times as high as those of other two shapes. This is not desirable since impedance characteristics of existing power systems can be changed. Resistance rise of current limiting elements was low at a spiral shape before the whole quench completion, which may act as a disadvantage for simultaneous quench in serial connection between current limiting elements, but the temperature tended to have similar values at higher voltages. On the other hand, hi-spital shape was severe at insulation level between current limiting lines. When these aspects were considered, we concluded that a meander shape was appropriate to design for a resistive SFCL based on thin films except the concentration of electric field at edge areas of strip lines.

DC Superconducting fault current limiter characteristic test with a DC circuit breaker

  • So, Jooyeong;Choi, Kyeongdal;Lee, Ji-kwang;Kim, Woo-Seok
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제23권2호
    • /
    • pp.19-23
    • /
    • 2021
  • We have studied the breaking system that combines a resistive superconducting fault current limiter (SFCL) and a DC circuit breaker for DC fault current. To verify the design of the 15 kV DC SFCL, which was driven from the previous work, a 500 V DC system was built and a scale-down SFCL were manufactured. The manufactured SFCL module was designed as a bifilar coil which is a structure that minimizes inductive reactance. The manufactured SFCL module has been experiment to verify characteristics of the current-limiting performance in the DC 500 V system. Also, the manufactured FCL module was combined with the DC circuit breaker to be experimented to analyze the breaking performance. As a result of the experiment, when SFCL was combined to the DC circuit breaker, the energy dissipation received by the DC circuit breaker was reduced by up to 84% compared to when the DC circuit breaker operates alone. We are preparing methods and experiments for the optimal method for much higher performance as a future work.

동일 병렬 저항을 이용한 초전도 저항형 한류소자 직렬연결방안 및 전압용량 증대 (Increase of the Voltage Rating of Resistive Type Superconducting Fault Current Limiter Using Equal Shunt Resistors)

  • 차상도;김혜림;심정욱;한용희;현옥배
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제52권7호
    • /
    • pp.327-334
    • /
    • 2003
  • We have investigated the quench behavior of the series connection of resistive type superconducting fault current limiter (SFCL) components based on YBCO films. Equal shunt resistors $R_s$ across individual SFCL components successfully produced simultaneous Quenches for 5 components in series, resulting in equal application of voltage to all components. If the two components having the highest and the lowest critical currents ($I_c$) quench safely, others quench altogether The highest shunt resistance is to guarantee the safe quenches of all components, leading to the equal voltage applications within the first half cycle after a fault in the short circuit test. The highest $R_s$ was found to be 28 [$\Omega$] for the components in the given quench environment. Considering the safe quenches and protection coordination, the optimal $R_s$ was suggested to be approximately a half of the highest $R_s$,, allowing wide selection of $R_s$ and $I_c$'s. This design provides a practical wav of connecting small SFCL components in series for high voltage application.

직렬 연결된 초전도 한류기의 퀜치 및 한류 특성 (Quench Characteristics of Resistive SFCL Elements in series)

  • 현옥배;최효상;김혜림;임해룡;김인선
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 B
    • /
    • pp.663-665
    • /
    • 2000
  • We fabricated resistive superconducting fault current limiters (SFCL) based on YBCO thin films grown on 2-inch diameter saphire substrates Two SFCLs with nearly identical properties were connected in series to investigate the simultaneous quench. There was a slight difference in the rate of voltage increase between two SFCL units when they were operated independently. This difference. however, resulted in significantly unbalanced power dissipation between the units. This imbalance was removed by connecting a shunt resistor to an SFCL in parallel. The appropriate values of the shunt resistances were $80{\Omega}$ at $75 V_{rms}$. $100{\Omega}$ at $100 V_{rms}$ and $110{\Omega}$ at $120 V_{rms}$, respectively. Increased power input at high voltages also reduced the initial imbalance in power dissipation. but with increase in film temperature to higher than 200 K.

  • PDF

30 kVA급 유도형 고온초전도 한류기의 특성 연구 (Study on the Characteristics of 30 kVA Inductive High-Tc Superconducting Fault Current Limier)

  • 이찬주;이승제;강형구;배덕권;안민철;현옥배;고태국
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제4권1호
    • /
    • pp.110-113
    • /
    • 2002
  • The high-tc superconducting fault current limiters (SFCL) are studied worldwide to be classified as resistive type or inductive type such as magnetic shielding type and dc reactor type. This Paper deals with an open core type SFCL, a kind of magnetic shielding type SFCL. We manufactured a 30 kVA open core type SFCL. It was modified from the old one with a rated power of 8 kVA. We stacked four superconducting tubes as magnetic shielding material and used the same primary winding as the old one. The experiments were performed with a maximum source voltage of 1 kV. The results show that the fault current in the source voltage of 1 kVrms was reduced to be about 105 Apeak, which was calculated to be about 22 % of the fault current in the system without an SFCL.

변압기형 초전도 한류기의 퀜치특성에 대한 중성선의 영향 (Influence of a Neutral Line on the Quench Behaviors of a Transformer Type SFCL)

  • 조용선;최효상;구경완
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.2212-2213
    • /
    • 2008
  • In this paper, we studied the method for simultaneous quenching of a transformer type superconducting fault current limiter (SFCL) with two superconducting elements connected in series. Only an element between two elements of the transformer type SFCL was quenched like the case of the resistive type SFCL. By this quenching characteristics, the power burden of the superconducting element was increased. In order to solve this problem, we connected the neutral line between two superconducting elements and the center of secondary coils. The two elements were all quenched in the transformer type SFCL with a neutral line. As a result, the power burden of superconducting elements was decreased, so it was efficient for the increase of power capacity of the transformer type SFCL.

  • PDF

배전계통 초전도 한류기 동작특성에 따른 계통 영향 분석 (System Effects by Operation Characteristics of Superconducting Fault Current Limiters in Distribution Systems)

  • 이상봉;김철환;김규호;김재철;현옥배
    • 전기학회논문지
    • /
    • 제57권7호
    • /
    • pp.1135-1140
    • /
    • 2008
  • Superconducting fault current limiters (SFCL) have been progressing due to the development of superconducting technology. The resistor type SFCL is one of the promising current limiting devices in power system for its effective operation. For proper application and operation of a SFCL, the prior investigation of fundamental characteristics and its effects to the distribution systems are needed. The most important current limiting behavior of a SFCL is dominated by quenching and recovery characteristics. In this paper, the resistive type SFCL was developed by using EMTP/ATPDraw and MODELS language. The operating characteristics and current limiting behaviors of the SFCL in distribution systems have been simulated and investigated.

유도형과 저항형 초전도한류기의 파라메타를 고려한 전력계통도입효과의 분석 및 성능평가에 관한 연구 (On the Current Limiting Characteristics and Parameters of Superconducting Fault Current Limiter Introduced to 345kV Electric Power System due to Resistive-Type, Reactive-Type and Their Performance Comparison)

  • 홍원표;김용학
    • 조명전기설비학회논문지
    • /
    • 제16권3호
    • /
    • pp.74-83
    • /
    • 2002
  • 본 논문은 전력설비에 조기적용이 예상되는 초전도한류기의 파라메타를 정의하고 앞으로 개발방향을 제시하기 위하여 한류기의 동작원리, 특성 및 계통조기적용가능성들을 근거로 파라메타의 특성을 비교 ·평가하였다. 또한 한류기의 계통적용효과를 분석하기 위하여 SFCL이 기간 특고압 모델계통에 도입한 경우를 상정하여 3선지락 고장에서 저항형과 유도형 SFCL의 도입 효과에 대하여 RTDS (Real Time Digital Simulation)/EMTDC(Electromagnetic Transient DC)로 시뮬레이션하였다. 특히 저항형과 유도형의 한류효과의 비교 평가, 모선전압의 저하 억제 및 계통과 한류기의 파라메타와의 관련성에 대하여 검토하였다.

초전도 한류기를 이용한 Bi-2223/Ag 선재의 퀜치 보호를 위한 기초 연구 (Preliminary study on the quench protection of Bi-22231 Ag tape using superconducting fault current limiter)

  • 두호익;임성우;현옥배;황시돌;조철용;박충렬;한영성
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2006년도 하계학술대회 논문집 Vol.7
    • /
    • pp.243-244
    • /
    • 2006
  • As an preliminary study for the quench protection of high temperature superconducting (HTS) cable using superconducting fault current limiter (SFCL), experimental research was carried out. The test circuit was composed of Bi-2223/Ag HTS tape and a SFCL made of YBCO thin films. In the normal state, the applied current of 56 A, which was critical current of HTS tape, could be flown through the circuit without resistive loss. Increasing the currents, the quench development of both materials was investigated from the voltage signal acquired from the resistance of the quenched superconductor. Up to around 10 times of the critical current was applied to the HTS tape and the current limiting characteristics of SFCL were investigated. In addition, for the finding out the optimal operating condition of SFCL such as the numbers of elements, a shunt resistor was applied to the SFCL and quench characteristics were analyzed as well.

  • PDF