Browse > Article
http://dx.doi.org/10.9714/psac.2021.23.2.019

DC Superconducting fault current limiter characteristic test with a DC circuit breaker  

So, Jooyeong (Korea Polytechnic University)
Choi, Kyeongdal (Korea Polytechnic University)
Lee, Ji-kwang (Woosuk University)
Kim, Woo-Seok (Korea Polytechnic University)
Publication Information
Progress in Superconductivity and Cryogenics / v.23, no.2, 2021 , pp. 19-23 More about this Journal
Abstract
We have studied the breaking system that combines a resistive superconducting fault current limiter (SFCL) and a DC circuit breaker for DC fault current. To verify the design of the 15 kV DC SFCL, which was driven from the previous work, a 500 V DC system was built and a scale-down SFCL were manufactured. The manufactured SFCL module was designed as a bifilar coil which is a structure that minimizes inductive reactance. The manufactured SFCL module has been experiment to verify characteristics of the current-limiting performance in the DC 500 V system. Also, the manufactured FCL module was combined with the DC circuit breaker to be experimented to analyze the breaking performance. As a result of the experiment, when SFCL was combined to the DC circuit breaker, the energy dissipation received by the DC circuit breaker was reduced by up to 84% compared to when the DC circuit breaker operates alone. We are preparing methods and experiments for the optimal method for much higher performance as a future work.
Keywords
direct current circuit breaker; DC grid; SFCL; HTS;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Y. Morishita, T. Ishikawa, I. Yamaguchi, S. Okabe, G. Ueta, and S. Yanabu, "Applications of DC breakers and concepts for superconducting fault-current limiter for a DC distribution network," IEEE Trans. Appl. Supercond., vol. 19, no. 4, 2009, Art. no. 10794822.
2 J. Xi, X. Pei, W. Song, B. Xiang, Z. Liu, X. Zeng, "Experimental tests of DC SFCL under low impedance and high impedance fault conditions," IEEE Trans. Appl. Supercond., vol. 31, pp. 5601205, 2021.
3 Y Ayachi Amor, G Didier, F Hamoudi, "Application of a novel approach of resistive-type superconducting fault current limiter with a fast protection system in multi-terminal direct current network," International Transactions on Electrical Energy Systems, Aug. 2020.
4 H. Y. Lee, M. Asif, K. H. Park, B. W. Lee, "Assessment of appropriate SFCL type considering DC fault interruption in full bridge modular multilevel converter HVDC system," Phys. C Supercond., vol. 563, pp. xxx, 2019.
5 H. W. Choi, "A Study on the Current-limiting Type Superconducting DC Circuit Breaker for the Reliability Improvement in HVDC Power System," Ph. D Thesis, Chosun University, August 2019.
6 W. C. Kim, "A study on the recovery characteristics of resistive superconducting fault current limiter with respect to various winding types," M. S. Thesis, Yonsei University, February 2010.
7 J. So, S. Lee, W. S. Kim, J. K. Lee, and K. Choi, "Design of an HTS Fault Current Limiting Module for an MVDC Power Grid," IEEE Trans. Appl. Supercond., vol. 30, no. 4, 2020, Art. no. 5600705.
8 J. Lee and U. Khan, "Impact of SFCL on the four types of HVD circuit breakers by simulation," IEEE Trans. Appl. Supercond., vol. 26, no. 4, 2016, Art. no. 5602606.