• Title/Summary/Keyword: Rating Distribution

Search Result 270, Processing Time 0.025 seconds

An Investigation on the Fault Currents in 22.9 kV Distribution System Due to the Increased Capacity and Operating Conditions of Power Transformers in 154 kV Substation (154 kV 변전소 주변압기의 용량 및 운전조건이 22.9 kV 배전계통의 고장전류에 미치는 영향)

  • Cho, Seong-Soo;Han, Sang-Ok
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.57 no.3
    • /
    • pp.302-310
    • /
    • 2008
  • In order to evaluate the nominal rating of breakers in distribution system due to the increased capacity and operating conditions of power transformers in 154 kV substation, the fault currents in distribution system were calculated by the conventional method and simulations of PSCAD/EMTDC program. Consequently, under the condition of the parallel operation of transformers, the fault currents exceed the nominal current of the breakers in some areas. Without NGR at the secondary neutral of the transformer, the current of single line-to-ground fault was bigger than that of 3-phase fault. Therefore, the results clearly show that the measures to limit the fault currents in distribution system are needed when the increased capacity of power transformers is introduced into 154 kV substation.

Thermal Distribution Modeling of IGBT with heatsink areas (히트싱크 면적에 따른 IGBT의 열 분포 모델링)

  • Ryu, Se-Hwan;Hong, Jong-Kyoung;Won, Chang-Sub;Ahn, Hyung-Keun;Han, Deuk-Young
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2008.06a
    • /
    • pp.30-31
    • /
    • 2008
  • As the power density and switching frequency increase, thermal analysis of power electronics system becomes imperative. The analysis provides valuable information on the semiconductor rating, long-term reliability. In this paper, thermal distribution of the Non Punchthroug(NPT) Insulated Gate Bipolar Transistor with heatsink areas has been studied. For analysis of thermal distribution, we obtained results by using finite element simulator, ANSYS and compared with experimental data by thermocam.

  • PDF

Thermal Characteristics and Heatsink Modeling. for IGBT (IGBT의 열 특성 및 히트싱크 모델링)

  • Ryu, Se-Hwan;Bea, Kyung-Kuk;Shin, Ho-Chul;Ahn, Hyung-Keun;Han, Deuk-Young
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2007.06a
    • /
    • pp.172-173
    • /
    • 2007
  • As the power density and switching frequency increase, thermal analysis of power electronics system becomes imperative. The thermal analysis provides valuable information on the semiconductor rating, long-term reliability. In this paper, thermal distribution of the Non Punchthrough(NPT) Insulated Gate Bipolar Transistor has been studied. For analysis of thermal distribution, we obtained experimental and simulation results by using finite element simulator, Ansys and by using photographic infrared thermometer, we compared experimental date with simulation result. and got good agreement. Also this paper provided thermal distribution of IGBT connected to heat sinks. and this results will be good information to design optimal heat sink for IGBT.

  • PDF

Prediction of temperature rise of Electric Switching Device Using CFD-CAD Integrated Analysis (CFD-CAD 통합해석을 이용한 전력기기 온도상승 예측)

  • Ahn, Heui-Sub;Lee, Jong-C.;Choi, Jong-Ung;Oh, Il-Sung
    • Proceedings of the KIEE Conference
    • /
    • 2002.07b
    • /
    • pp.808-810
    • /
    • 2002
  • Higher current-rating and improved thermal performance are being sought for existing medium-voltage vacuum circuit breakers(VCB) in order to meet market needs which require to be compact and downsized. In this paper, thermal performance of medium voltage vacuum circuit breaker was investigated through experiments and numerical analysis. We changed several major parameters of current-rating and heat sink affecting on thermal behaviors in the breaker and observed the results. To predict the temperature distribution in complex three-dimensional (3-D) VCB components and gas, the commercial package was used to simulate conjugate heat transfer. Although some assumptions and simplifications were introduced to simulate the model, results from the computational model were in good agreement with actual temperature rise measurements obtained from experiments.

  • PDF

Validation Comparison of Credit Rating Models Using Box-Cox Transformation

  • Hong, Chong-Sun;Choi, Jeong-Min
    • Journal of the Korean Data and Information Science Society
    • /
    • v.19 no.3
    • /
    • pp.789-800
    • /
    • 2008
  • Current credit evaluation models based on financial data make use of smoothing estimated default ratios which are transformed from each financial variable. In this work, some problems of the credit evaluation models developed by financial experts are discussed and we propose improved credit evaluation models based on the stepwise variable selection method and Box-Cox transformed data whose distribution is much skewed to the right. After comparing goodness-of-fit tests of these models, the validation of the credit evaluation models using statistical methods such as the stepwise variable selection method and Box-Cox transformation function is explained.

  • PDF

Analysis on the Protective Coordination with Hybrid Superconducting Fault Current Limiter (저항접지 시스템에서 지락사고시 CLR과열 소손방지를 위한 GPT 정격용량의 적정성 연구)

  • Shin, Ho-Jeon;Kim, Jin-Seok;Park, Yu-Hwan;Kim, Jae-Chul;Cho, Man-Young
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.4
    • /
    • pp.503-508
    • /
    • 2012
  • Among the high distribution voltage consumers, high-capacity consumers are often applying the grounding resistance method in order to overcome demerits such as erroneous operation of the ground reply or potential increase in the battery at the accident of the isolated neutral system. In this paper, to prevent damage to CLR and GPT in the delay to block the breakdown in the resistance grounded neutral system, this study aims to provide a proper suggestion for continuous rating capacity of GPT to check the appropriateness of CLR size and reduce GPT burden. Thereupon, this study comparatively analyzes CLR current applied in general GPT and the current gained when CLR demanded in the system is used and analyzes the simulated system through simulation using PSCAD/EMTDC in order to suggest GPT's proper continuous rating capacity.

Fatigue Life Analysis for Angular Contact Ball Bearing with Angular Misalignment (각 어긋남을 고려한 각접촉 볼베어링의 피로수명 해석)

  • Bae, Gyu-Hyun;Tong, Van-Canh;Hong, Seong-Wook
    • Journal of the Korean Society for Precision Engineering
    • /
    • v.33 no.1
    • /
    • pp.53-61
    • /
    • 2016
  • Angular misalignment has a significant effect on the characteristics of angular contact ball bearings (ACBBs). This paper presents an analysis of fatigue life for ACBBs subjected to angular misalignment. A simulation model is developed with de Mul's bearing model and the ISO basic reference rating life model. Simulation is performed to calculate the life of the ACBBs subjected to angular misalignment. The numerical results show that angular misalignment influences the load distribution significantly, thus reducing the bearing rating life. The fatigue life of ACBBs is decreased by angular misalignment regardless of axial preload, external radial load and rotational speed. The results show that angular misalignment should be maintained at less than 1mrad for ACBBs.

Analysis of Discomfort Glare by luminous intensity distribution of Marine Indoor Luminaires (선박용 실내조명기구의 배광에 따른 불쾌글레어 분석)

  • Cho, Sang-Hee;Kim, Kun-Yul;Yu, Young-Moon
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.28 no.3
    • /
    • pp.18-25
    • /
    • 2014
  • In this paper, tried to find out the proper luminous intensity distribution for the cabin with low-level height by analyzing the changing tendency of discomfort glare according to luminous intensity distribution of marine indoor luminaires using Unified Glare Rating(UGR). First, we analyzed UGR of the indoor luminaires in the existing cabin, and then evaluated influence on luminous intensity distributions of marine indoor luminaire. The results showed that $cos^2{\Theta}$ distribution got almost low UGR results regardless of height and UGR 16.5 in cabin height of 2m. However, Gaussian distribution with the same beam angle showed that UGR results consistently increased by getting lower height and UGR 20.7 in the same height. In conclusion, the $cos^2{\Theta}$ distribution in consideration of luminous intensity on the direction of observer's eye was appropriate for general cabin indoor luminaires because it decreased UGR in the low-level height.

Field Applications on Groundwater Management Scheme of Subwatershed Unit in Hampyeong-Gun (단위유역 단위의 지하수 관리기법 현장적용성 검토 (함평군 중심으로))

  • Jung, Chan Duck;Song, In sung
    • Economic and Environmental Geology
    • /
    • v.46 no.6
    • /
    • pp.545-559
    • /
    • 2013
  • Until now, research achievements of groundwater such as groundwater to depth distribution, usage, the available amount of development, water quality have been written in the watershed units($25{\sim}250km^2$). However, complex topography and geology, and the rivers of our country does not fit. And a clear management standards have not been able to present measures in groundwater quantity, water quality management such as rainfall, groundwater, utilization, water quality, pollution, etc. Therefore, in this study, the classification criterion of subwatershed unit($2.5{\sim}25km^2$), which is suitable for topography and geology of Korea, for rainfall-rating, groundwater level-rating, groundwater pollution-rating, groundwater quality-rating presented and proved its efficiency by applying in Hampyeong-Gun area.

Structural health rating (SHR)-oriented 3D multi-scale finite element modeling and analysis of Stonecutters Bridge

  • Li, X.F.;Ni, Y.Q.;Wong, K.Y.;Chan, K.W.Y.
    • Smart Structures and Systems
    • /
    • v.15 no.1
    • /
    • pp.99-117
    • /
    • 2015
  • The Stonecutters Bridge (SCB) in Hong Kong is the third-longest cable-stayed bridge in the world with a main span stretching 1,018 m between two 298 m high single-leg tapering composite towers. A Wind and Structural Health Monitoring System (WASHMS) is being implemented on SCB by the Highways Department of The Hong Kong SAR Government, and the SCB-WASHMS is composed of more than 1,300 sensors in 15 types. In order to establish a linkage between structural health monitoring and maintenance management, a Structural Health Rating System (SHRS) with relevant rating tools and indices is devised. On the basis of a 3D space frame finite element model (FEM) of SCB and model updating, this paper presents the development of an SHR-oriented 3D multi-scale FEM for the purpose of load-resistance analysis and damage evaluation in structural element level, including modeling, refinement and validation of the multi-scale FEM. The refined 3D structural segments at deck and towers are established in critical segment positions corresponding to maximum cable forces. The components in the critical segment region are modeled as a full 3D FEM and fitted into the 3D space frame FEM. The boundary conditions between beam and shell elements are performed conforming to equivalent stiffness, effective mass and compatibility of deformation. The 3D multi-scale FEM is verified by the in-situ measured dynamic characteristics and static response. A good agreement between the FEM and measurement results indicates that the 3D multi-scale FEM is precise and efficient for WASHMS and SHRS of SCB. In addition, stress distribution and concentration of the critical segments in the 3D multi-scale FEM under temperature loads, static wind loads and equivalent seismic loads are investigated. Stress concentration elements under equivalent seismic loads exist in the anchor zone in steel/concrete beam and the anchor plate edge in steel anchor box of the towers.