An Investigation on the Fault Currents in 22.9 kV Distribution System Due to the Increased Capacity and Operating Conditions of Power Transformers in 154 kV Substation

154 kV 변전소 주변압기의 용량 및 운전조건이 22.9 kV 배전계통의 고장전류에 미치는 영향

  • 조성수 (한전 전력연구원 배전연구소) ;
  • 한상옥 (충남대학교 전기공학과)
  • Published : 2008.09.01

Abstract

In order to evaluate the nominal rating of breakers in distribution system due to the increased capacity and operating conditions of power transformers in 154 kV substation, the fault currents in distribution system were calculated by the conventional method and simulations of PSCAD/EMTDC program. Consequently, under the condition of the parallel operation of transformers, the fault currents exceed the nominal current of the breakers in some areas. Without NGR at the secondary neutral of the transformer, the current of single line-to-ground fault was bigger than that of 3-phase fault. Therefore, the results clearly show that the measures to limit the fault currents in distribution system are needed when the increased capacity of power transformers is introduced into 154 kV substation.

Keywords

References

  1. 한국전력공사, 한전표준규격 ES 140-435-622 154 kV 전력용 변압기, pp.2-5, 2006
  2. 한국전력공사, 한전설계기준-2501 전력용변압기 선정기준, pp.1-8, 2005
  3. IEC 60076-1, Power Transformer-Part: General Edition 2.1, 1993
  4. 한국전력공사, 서울전력관리처 23 kV 모선임피던스 자료, 2005
  5. Westinghouse Co., Electrical Transmission and Distribution Reference Book, pp.136-137, 1950
  6. A.C. Franklin and D.P. Franklin, The J&P Transformer Book, 11th Edition, pp.737, 1983
  7. 이경호, "IEC 규격에 의한 고장전류 해석 및 차단기 용량 선정", 한국조명전기설비학회 2007춘계학술대회 논문집, pp.433-436, 2007
  8. 남재경, "고장사고시 전류의 흐름과 보호 계전기의 회로 점검 방법", 조명전기설비학회지, 제16권, 제3호, pp.46-53, 2002
  9. 조남훈, "지중배전선로의 다회로 차단기 운영방안 연구", 대한전기학회 논문지, 49, 4A, pp.143-151, 2000
  10. 오용택, 김진성, "배전계통에서 발생하는 돌입전류와 고장전류의 특성 비교연구", 한국조명전기설비학회 학술 대회 논문집, pp.51-57, 2001
  11. 정상진 외, "전력용 변압기 사고감소에 관한 연구 (최종 보고서), 한전 전력연구원, pp.157-204, 1992