• 제목/요약/키워드: Pressurized smoke control system

검색결과 13건 처리시간 0.028초

부속실 급기가압제연시 차압변화에 관한 실험적 연구 (An Experimental Study on the Pressure Differentials during the Pressurized Air Supply to the Elevator Lobby)

  • 김범규;박용환;김홍식
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2009년도 춘계학술논문발표회 논문집
    • /
    • pp.110-119
    • /
    • 2009
  • A fire should be accompanied by the heat and smoke. However, smoke is considered main cause of heavy casualties. Smoke easily spreads away from the fire area to remote space and cause mortal wound for the resident. A technical way effectively protecting the life and property from the smoke is the smoke control system of the building. Pressurized air supply system can be considered to prevent the refuge area from the smoke infiltration that evacuate residents via evacuation route for life safety. This paper is related with performance estimation and the effectiveness of the pressurized air supply system through experiments.

  • PDF

국내 고층건물의 피난성능확보를 위한 급기가압방연(제연) 시스템의 제도개선연구 (A Legal Alternative for Effective Application of Pressurized Smoke Control System to Provide ′Smoke-free′ Access for Escape Shafts Used in High-Rise Building)

  • 박형주;김상욱
    • 한국화재소방학회논문지
    • /
    • 제15권4호
    • /
    • pp.49-56
    • /
    • 2001
  • 화재시 특별피난계단의 부속실의 연기침입을 방지하기 위해 적용하고 있는 급기가압방연시스템의 효능에 대한 논란이 증가하고 있는 바, 국내 고층 건축물의 특별피난계단에 설치운용중인 급기가압시스템의 설계시 핵심요소인 가압공간의 누설틈새, 계단실과 부속실 또는 부속실과 거실공간사이의 출입문을 통한 방연풍속과 출입문의 자동폐쇄를 보장하는 도어 개폐장치등에 대한 문제점을 조사연구하여 실질적인 효과를 보장할 수 있는 기준을 설정하고, 안전성확보를 보장하면서 경제성을 고려한 설계안을 세부적인 사례를 들어 구체적으로 제시하였다.

  • PDF

급기가압 조건에서 복합 구획 공간 화재의 연기 거동에 대한 수치해석 연구 (Numerical Simulation on Smoke Movement in Multi-Compartment Enclosure Fires under Pressurized Air Supply Conditions)

  • 고권현
    • 한국화재소방학회논문지
    • /
    • 제32권6호
    • /
    • pp.15-21
    • /
    • 2018
  • 본 연구에서는 급기가압 조건에서 거실, 부속실 및 계단실로 구성된 복합 구획 공간에 대해 화재해석을 수행하고 가압 및 환기 조건에 따른 화재 연기의 유동 특성을 분석하였다. 화재 해석은 유효누설면적을 측정하기 위해 제작된 누기율 시험설비에 대하여 수행하였으며, 화재의 거시적 특성과 각 구획에 대한 유동 및 압력 특성의 분석을 통해 급기가압 조건에서의 화염 및 연기 거동에 대한 이해를 증진시키고자 하였다. 화재 해석 결과는 화재 발열량의 크기가 환기 시스템에 의해 공급되는 공기량에 의해서 민감하게 영향을 받게 됨을 보여주었다. 거실과 부속실에서의 속도분포 분석 결과를 통해 급기가압의 조건에서도 화재 연기가 문의 상층부를 통해 부속실로 유출될 수 있음을 확인하였다. 이를 통하여 급기가압 제연시스템의 설계와 적용에 있어서 화재 크기와 공간적 특성과 같은 요인을 고려하는 것이 매우 중요하다는 것을 확인할 수 있었다.

Elevator Pressurization in Tall Buildings

  • Klote, John H.
    • 국제초고층학회논문집
    • /
    • 제2권4호
    • /
    • pp.341-344
    • /
    • 2013
  • During a building fire, smoke can flow through elevator shafts threatening life on floors remote from the fire. Many buildings have pressurized elevators intended to prevent such smoke flow. The computer program, CONTAM, can be used to analyze the performance of pressurization smoke control systems. The design of pressurized elevators can be challenging for the following reasons: (1) often the building envelope is not capable of effectively handling the large airflow resulting from elevator pressurization, (2) open elevator doors on the ground floor tend to increase the flow from the elevator shaft at the ground floor, and (3) open exterior doors on the ground floor can cause excessive pressure differences across the elevator shaft at the ground floor. To meet these challenges, the following systems have been developed: (1) exterior vent (EV) system, (2) floor exhaust (FE) system, and ground floor lobby (GFL) system.

초고층 건축물의 수직 구획화에 따른 급기가압제연시스템 성능평가에 관한 연구 (A Study on the Smoke Control Performance Evaluation of High-rise Buildings under Smokeproof Enclosure Design Scenarios)

  • 배상환;류형규;이병석
    • 설비공학논문집
    • /
    • 제26권7호
    • /
    • pp.343-350
    • /
    • 2014
  • Regardless of the building design scenarios, evaluation of high-rise buildings required to have smoke-proof enclosures that are provided with a smoke management system. The goal of the smoke management system design is to make sure the pressure differentials at every story within the building fall within the allowable pressure range. If the minimum design pressure is not met, smoke may enter the stair. If the provided pressure is too great, it becomes difficult for occupants to open the doors, while attempting to egress. Ensuring that the pressure differential between the vestibule and the floor is within the prescribed range becomes challenging, due to natural effects on the building, such as the stack effect. In this research, smokeproof enclosure design scenarios were evaluated; and as a result, separation levels for compartmentation were deduced, in the balancing of pressurized-vestibule smoke control systems.

급기가압 제연설비의 내부 유동특성에 대한 수치해석 (Numerical Analysis on Flow Characteristics in the Pressurized Air Supply Smoke Control System)

  • 고권현
    • 한국화재소방학회논문지
    • /
    • 제31권4호
    • /
    • pp.52-58
    • /
    • 2017
  • 본 연구에서는 급기가압에 따른 건축물 내부의 공기유동에 대한 수치해석을 수행하고 거실, 부속실 및 계단실 간의 차압분포 및 유동 특성을 분석하였다. 유동 해석은 유효누설면적을 측정하기 위해 제작된 누기율 시험설비에 대하여 수행하였으며, 급기가압에 따른 각 실의 압력 및 유속분포 등을 분석하였다. 본 해석에서 공기의 누설은 유효누설면적을 갖는 얇은 틈새를 방화문과 창문에 위치시키는 방법으로 모사하였다. 이러한 방법을 이용한 해석은 계단실과 부속실 간의 차압에 대한 기존 실험의 결과를 적절히 예측하였다. 해석 결과를 통해 국부적인 누설이 급기가압 제연 설비의 전체적인 유동 패턴 및 압력 분포에 큰 영향을 미치지 않음을 확인하였다. 거실-부속실 문 단면에서의 평균속도가 방연풍속에 대한 국가화재안전기준을 만족하였으나 문의 상부와 같은 국부적인 위치에서 부속실로의 유출이 발생할 수 있음을 확인하였다.

댐퍼의 위치가 부속실 및 방화문에서의 열 유동 특성에 미치는 영향에 관한 수치해석 연구 (Numerical Study on the Effect of Damper Position on Characteristics of Thermal Flow at the Vestibules and Fire Door)

  • 문효준;고권현;유홍선
    • 한국화재소방학회논문지
    • /
    • 제27권1호
    • /
    • pp.31-38
    • /
    • 2013
  • 급기가압 제연시스템은 재실자의 피난활동 및 피난시간에 직접적인 영향을 미치므로 건축물의 화재안전에 있어 핵심적인 설비이다. 하지만 댐퍼의 위치에 따라 방화문에서 부속실로 연기가 유입되는 현상이 발생할 수 있으며 이에 대한 연구는 미비한 실정이다. 본 연구에서는 댐퍼위치에 따른 부속실과 방화문에서의 열 유동특성 및 연기가 부속실로 유입되는 현상을 FDS 5.5를 이용하여 수치해석으로 분석하였다. 또한 실제 현상을 구현하기 위해 재실자의 피난을 가정하여 방화문이 개방되고 폐쇄되는 효과를 설정하였으며 열 방출률을 변화시키면서 수치해석을 수행하였다. 수치해석 결과, 열 방출률이 200 kW에서 400 kW 일 때는 댐퍼의 위치가 방화문의 정면일 때 다른 댐퍼의 위치보다 연기가 부속실로 유입되는 현상을 나타났다. 하지만 열 방출률이 400 kW 이상일 경우에는 댐퍼의 위치에 대한 영향이 크지 않았다.

급기가압 제연시스템의 성능개선을 위한 무지향성 제연댐퍼시스템 개발연구 (Non-directional Smoke Damper System Development for Pressurized Smoke Control System)

  • 배상환;류형규;이병석;장세웅
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2012년도 춘계학술발표회 초록집
    • /
    • pp.357-360
    • /
    • 2012
  • 본 연구에서는 기존 급기가압 제연의 성능평가를 수행하였고, 이를 기반으로 급기가압제연댐퍼의 기류방향에 따른 방연풍속 확보가 곤란한 점에 착안하여 무지향성 제연댐퍼시스템을 개발하였다. 개발된 무지향성 제연댐퍼를 대상으로 Mockup 실험을 수행한 결과 화재실 출입문과 제연댐퍼의 설치위치와 상관없이 방연풍속 확보가 가능하여 급기가압제연시스템의 성능개선효과가 매우 큰 것으로 나타났다.

  • PDF