절연가스 성분분석을 통한 154kV 가스절연변압기 내부결함 판정 (The decision of the inner fault of 154kV Gas Insulated Transformer through analyzing ingredients of insulated gas.)

  • 문병선;탁의균;이태규;박찬의;이민호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2015년도 제46회 하계학술대회
    • /
    • pp.447-448
    • /
    • 2015
  • In order to looking for method of detecting inner fault of a 154kV GIT(Gas Insulated Transformer), it was considered that diagnosis partial discharge(PD) in UHF band and that analyze the ingredients of SF6 insulating gas. UHF PD diagnosis that is optimized to GIS was considered unsuitable through checking of inner part of a transformers which PD is detected excessively. The method analyzing the content of six kinds of gas(SOF2, SO2F2, etc)was decided through analysis of chemical degradation and combination process and discharge experiment. With the result applying this method to analyze the content of insulated gas of eighty five Gas Insulated Transformers.

  • PDF

154 kV 변압기 보호용 비율차동계전기 오동작 방지를 위한 2고조파 억제 방식의 적용방법 및 정정값에 관한 연구 (A Study on the 2nd Harmonic Blocking Scheme and Setting Value of a Current Differential Relay for 154 kV Transformers to Prevent Maloperation)

  • 손용범;강상희
    • 전기학회논문지
    • /
    • 제67권1호
    • /
    • pp.29-37
    • /
    • 2018
  • Inrush current and fault current in a transformer need to be distinguished from one another. In order to do this, KEPCO uses a 2nd harmonic restraint/block method. We use two setting values for 2nd harmonic restraint; 15% and 10%. We also apply per-phase blocking method among various harmonic restraint methods. If the transformer is located at the radial system, we adjust 10% in the 2nd harmonic restraint, but this method is not enough to prevent mal-operations of the current differential relay and let us spend more time to change setting value again as the power system changes. In this paper, a more reasonable setting value for a 2nd harmonic blocking scheme in KEPCO is proposed. To present a proposed method, the fault data of the current differential relays which have occurred since 2009 are analyzed. To evaluate the performance of the proposed method, the results of the RTDS test for the current differential relay of the transformer by KEPCO are analyzed.

Fuzzy Logic Based Relaying Using Flux-differential Current Derivative Cure for Power Transformer Protection

  • 권명현;박철원;서희석;이복구;신명철
    • 한국지능시스템학회논문지
    • /
    • 제8권5호
    • /
    • pp.72-82
    • /
    • 1998
  • Power transformer protective relay should block the tripping during magnetizing imrush and rapidly operate the tripping during internal faults. But traditional approaches maloperate in the case of magnetizing inrush with low second harmonic component and internal faults with high second harmounic component. To enhance the fault detection sensitivities of conventional technuques, flux-differential current derivative curve by fuzzy theory approaches is used. This paper deals with fuzzy logic based protective relaying for power transformer. The proposed fuzzy based relaying algorithm consisits of flux-differential current derivative curve, harmonics restraint, and precentage differential characteristic curv. The proposed relaying was tested with relaying signals obtained from Salford EMTP simulation package and showed a fast and accurate trip operation.

  • PDF

신경회로망에 의한 변압기의 여자돌입과 내부고장 판별에 관한 연구 (A Study on the Discriminate between Magnetizing Inrush and Internal Faults of Power Transformer by Artificial Neural Network)

  • 박철원;조필훈;신명철;윤석무
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1995년도 하계학술대회 논문집 B
    • /
    • pp.606-609
    • /
    • 1995
  • This paper presents discriminate between magnetizing inrush and internal faults of power transformer by artificial neural networks trained with preprocessing of fault discriminant. The proposed neural networks contain multi-layer perceptron using back-propagation learning algorithm with logistic sigmoid activation function. For this training and test, we used the relaying signals obtained from the EMTP simulation of model power system. It is shown that the proposed transformer protection system by neural networks never misoperated.

  • PDF

DGA Interpretation of Oil Filled Transformer Condition Diagnosis

  • Alghamdi, Ali Saeed;Muhamad, Nor Asiah;Suleiman, Abubakar A.
    • Transactions on Electrical and Electronic Materials
    • /
    • 제13권5호
    • /
    • pp.229-232
    • /
    • 2012
  • DGA is one of the most recent techniques developed to diagnose the fault condition on oil filled insulation transformers. There are more than 6 known different methods of DGA fault interpretation technique and so there is the likelihood that they may vary in their interpretations. A series of combined interpretation methods that can determine the power transformer condition faults in one assessment is therefore needed. This paper presents a computer program- based system developed to combine four DGA assessment techniques; Rogers Ratio Method, IEC Basic Ratio Method, Duval Triangle method and Key Gas Method. An easy to use Graphic User Interface was designed to give a visual display of the four techniques. The result shows that this assessment method can increase the accuracy of DGA methods by up to 20% and the no prediction result had been reduced down to 0%.

The Fault Diagnosis of a Transformer Using Neural Network and Transfer Function

  • Park, Byung-Koo;Kim, Jong-Wook;Kim, Sang-Woo;Park, Poo-Gyeon;Park, Tae-Joon
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 제어로봇시스템학회 2001년도 ICCAS
    • /
    • pp.127.2-127
    • /
    • 2001
  • A transformer is one of the most important elements in the power network. Transformer faults could cause costly repairs and be dangerous to personnel. To avoid this, its reliable operation has great significance and, therefore, the diagnosis system of the transformer is necessitated. The dissolved gas-in-oil analysis (DGA) is the worldwide popular method of detecting faults such as a hot spot or partial discharges inside the transformer. DGA, however, is not a reliable technique to identify aging phenomena and mechanical faults including insulation failure, inter-turn short, etc. To overcome the drawbacks of DGA, the transfer function method is used to identify effectively these kinds of the mechanical faults. The transformer has a unique transfer function independent of the shape of the input waveform, which can be evaluated through sweep test. This transfer function changes by winding ...

  • PDF

전압-전류 추이와 자속-차전류 기울기 특성을 이용한 변압기 보호계전기법의 성능 개선 (Performance Improvement of Protective Relaying for Large Transformer by Using Voltage-Current Trend and Flux-Differential Current Slope Characteristic)

  • 박철원;박재세;정연만;하경재;신명철
    • 전기학회논문지P
    • /
    • 제53권2호
    • /
    • pp.43-50
    • /
    • 2004
  • Percentage differential characteristic relaying(PDR) has been recognized as the principal basis for power transformer protection. Second harmonic restraint PDR has been widely used for magnetizing inrush in practice. Nowadays, relaying signals can contain 2nd harmonic component to a large extent even in a normal state, and 2nd harmonic ratio indicates a tendency of relative reduction because of the advancement of material. Further, as the power system voltage becomes higher and more underground cables are used, larger 2nd harmonic component in the differential current under internal fault is observed. And then, conventional 2nd harmonic restraint PDR exposes some doubt in reliability. It is, therefore, necessary to develop a new algorithm for performance improvement of conventional protective relaying. This paper proposes an advanced protective relaying algorithm by using voltage-current trend and flux-differential current slope characteristic. To evaluate the performance of the proposed algorithm, we have made comparative studies of PDR, fuzzy relaying and DWT relaying. The paper is constructed power system model including power transformer, utilizing the WatATP, and data collection is made through simulation of various internal faults and inrush. As the results of test, the new proposed algorithm was proven to be faster and more reliable.

지상변압기의 내부 보호장비 작동을 위한 MCA 보호협조에 대한 연구 (A study on Protective Coordination of MCA for Performing of the Pad Mounted Transformer's inside Protective Device)

  • 현승윤;김창환
    • KEPCO Journal on Electric Power and Energy
    • /
    • 제8권1호
    • /
    • pp.5-7
    • /
    • 2022
  • KEPCO's plan is undergoing a trial operation to replace the open-loop section with ring main units configuration where underground distribution lines are installed, by linking the multi-way circuit breakers auto (MCA) on the power side of each pad-mounted transformer. However, ring main units application mentioned above may cause the ripple effects, when implementing the configuration without a study of protection coordination. Because ring main units with classical pre-set protection devices contribution in fault condition didn't consider yet. For the reliable ring main units operation, it is necessary to resolve several protection issues such as the protection coordination with substation side, prevention of the transformer inrush current. These issues can radically deteriorate the distribution system reliability Hence, it is essential to design proper protection coordination to reduce these types of problems. This paper presents a scheme of ring main units' configuration and MCA's settings of time-current curves to preserve the performance of protection coordination among the switchgears considering constraints, e.g. prevention of the ripple effects (on the branch section when a transformer failure occurs and the mainline when a branch line failure occurs). It was confirmed that the propagation of the failure for each interrupter segment could be minimized by applying the proposed TCC and the interrupter settings for the MCAs (branch, transformer). Further, it was verified that the undetected area of the distribution automation system (DAS) could be supplemented by having the MCA configurated ring main units operate first, instead of the internal protection equipment in the transformer such as the fuse, STP when a transformer failure occurs.

인버터식 고효율 네온관용 변압기 (Inverter type High Efficency Neon Transformers for Neon Tubes)

  • 변재영;김윤호
    • 조명전기설비학회논문지
    • /
    • 제16권6호
    • /
    • pp.22-29
    • /
    • 2002
  • 무방향성 규소강판을 사용한 자기식 네온관용 변압기는 내구성이 좋은 반면에 용량에 따른 규소 강판의 무게가 무겁고 외형이 큰 관계로 네온관 설치 작업 시 상당히 불편한 점이 많다. 또한 네온관의 다양한 디스플레이 제어성면에서도 비합리적 이었다. 이를 개선하기 위한 방법으로 네온 트랜스포머의 전원장치 및 2차측 고압 출력부를 고속의 고주파 스위칭 파워 트랜지스터(MOSFET)를 이용하여 상용주파수 60[Hz]를 고속 스위칭 제어를 통하여 20[KHz]의 고주파로 변환시킨후, 네온관을 방전시키기 위한 고전압을 발생시키는 인버터식 네온관용 변압기를 구현하였다. 또한 네온관의 파손이나 누전으로 인한 화재나 인체 감전의 위험을 사전에 방지할 수 있는 보호회로 GFCI(Ground Fault Circuit Interrupter)를 제안 하였다.

Short-circuit Analysis by the Application of Control Signal of Power Converter to the Inductive Fault Current Limiter

  • Ahn, Min-Cheol;Hyoungku Kang;Bae, Duck-Kweon;Minseok Joo;Park, Dong-Keun;Lee, Sang-Jin;Ko, Tae-Kuk
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제6권2호
    • /
    • pp.25-28
    • /
    • 2004
  • Three-phase inductive superconducting fault current limiter (SFCL) with DC reactor rated on 6.6 $KV_{rms}/200 A_{rms}$ has been developed in Korea. This system consists of one DC reactor, AC/DC power converter, and a three-phase transformer, which is called magnetic core reactor (MCR). This paper deals with the short-circuit analysis of the SFCL. The DC reactor was the HTS solenoid coil whose inductance was 84mH. The power converter was performed as the dual-mode operation for dividing voltage between the rectifying devices. The short-term normal operation (1 see) and short-circuit tests (2∼3 cycles) of this SFCL were performed successfully. In regular short-circuit test, the fault current was limited as 30% of rated short-circuit current at 2 cycles after the fault. The experimental results have a very similar tendency to the simulation results. Using the technique for the fault detection and SCR firing control, the fault current limiting rate of the SFCL was improved. From this research, the parameters for design and manufacture of large-scale SFCL were obtained.