Fuzzy Logic Based Relaying Using Flux-differential Current Derivative Cure for Power Transformer Protection

  • 발행 : 1998.10.01

초록

Power transformer protective relay should block the tripping during magnetizing imrush and rapidly operate the tripping during internal faults. But traditional approaches maloperate in the case of magnetizing inrush with low second harmonic component and internal faults with high second harmounic component. To enhance the fault detection sensitivities of conventional technuques, flux-differential current derivative curve by fuzzy theory approaches is used. This paper deals with fuzzy logic based protective relaying for power transformer. The proposed fuzzy based relaying algorithm consisits of flux-differential current derivative curve, harmonics restraint, and precentage differential characteristic curv. The proposed relaying was tested with relaying signals obtained from Salford EMTP simulation package and showed a fast and accurate trip operation.

키워드

참고문헌

  1. IEEE Trans. on PAS v.PAS-91 no.3 A proposed method of harmonic restraint differential protection of transformers by digital computer J.A.Sykes(et al.)
  2. Power System Protection Vol.3: Application The Institution of Electrical Engineers
  3. IEEE Trans. on PWRD v.3 no.2 A state-of-art review of transformer protection algorithm M.A.Rahman(et al.)
  4. IEEE Trans. on PWRD v.3 no.2 Designed implementation of a digital differential relay for 3 phase power transformer based on kalman filtering theory W.J.Smolinski(et al.)
  5. IEEE Trans. on PWRD v.6 no.1 A stand-alone digital protective relay for power transformers M.A.Rahman(et al.)
  6. Final Report Development of the integrated digital protection&control system for substation M.C.Shin(et al.)
  7. IEEE Trans. on PWRD v.9 no.1 Training an artificial neural network to discriminate between magnetizing inrush and internal faults Luis(et al.)
  8. IEEE Trans. on PWRD v.10 no.4 A multi-criteria differential transformer relay based on fuzzy logic A.Wiszniewski(et al.)
  9. IEEE Trans. on PWRD v.12 no.3 A self-organizing fuzzy logic based protective relay an application to power transformer protection B.Kasztenny(et al.)
  10. IEE Proc, Gen. Trans. v.142 no.4 Neural network based algorithm for power transformer differential relays P.Bastard;H.Regal;M.Meunier
  11. IEEE Trans. on PAS v.PAS-102 no.11 A new computer relay fluxrestrained current differential relay for power transformer protection A.G.Phadke(et al.)
  12. KIEE 96 Annual Autumn Conference Inrush current detection of power transformer using flux-current derivative curve C.W.Park(et al.)
  13. International Conference on ISAP'97 A digital protective relaying using a fuzzy theory for power transformer protection C.W.Park(et al.)
  14. IEEE Trans. on PWRD v.9 no.2 A transformer model for winding fault studies P.Bastard(et al.)
  15. KIEE 96 Annual Summer Conference The fault analysis of transformer to develope protective relaying algorithm for transformer M.C.Shin(et al.)
  16. LEUVEN EMTP CENTER ATP Rule Book