• 제목/요약/키워드: Porcelain suspension insulator

검색결과 42건 처리시간 0.024초

폴리머 현수애자의 복합가속열화 평가기술 (Multi-Stress Aging Test Technology for Suspension Polymer Insulator)

  • 박효열;강동필;김익수;신영준
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2003년도 하계학술대회 논문집 Vol.4 No.1
    • /
    • pp.481-484
    • /
    • 2003
  • Recently polymer insulators are being used for outdoor high voltage applications. Polymer insulators have significant advantages over porcelain and glass insulators. With the gradual improvement of their design and material, their reliability has also increased. It is however difficult to establish how they will perform after several years of service. Aging of the insulator weathershed may lead to damages such as excessive chalking and crazing, erosion and tracking which affect the insulator performance. In service insulator are subjected to aging stresses such as humidity, pollution and electrical field which act singly or in combination. There have been numerous accelerated laboratory tests developed with the intention of evaluating suitability of polymeric materials. Some of these are strictly material tests, where as, others evaluate full scale devices. Service experience plays a key role in the utility selection of polymer insulator, but is time consuming, and may not always be available. Hence there is a need for a meaningful and reliable accelerated aging test for polymer insulator. This paper describes multi-stress aging test for reliability of polymer insulator This paper presents the rule of multi-stress aging test and test chamber for polymer insulator in korea electrotechnology research institute.

  • PDF

송전용 애자의 과전 열화 신뢰성 평가 기술 (Technical Aspects on Long term Reliability of Porcelain Insulators for Transmission Line)

  • 한세원;조한구;최인혁
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.255-257
    • /
    • 2003
  • The reliability of power transmission lines depends on long-term performance of the suspension insulators used on the lines. The importance of such long-term performance of the insulators has been recently noted, but its evaluation method has not been established yet. In this paper, various causes of insulator deterioration are verified and laboratory test method for evaluating the long term performance of insulators are studied.

  • PDF

애자류의 염해대책에 관한 기초연구 (A basic study on preventing insulators from salt accident)

  • 김원섭
    • 전기의세계
    • /
    • 제18권1호
    • /
    • pp.11-14
    • /
    • 1969
  • This paper shows experimentally one method of preventing porcelain insulators from salt accident likely to be caused in the region of sea coast. In this experiment some results that, if a conductor barrier is inserted into the flash over discharge path which is wetted by salt dissolved water, the flash over voltage found to be raised up, were gotten. This results may be actually applied to suspension insulator or bushing to prevent them from salt accidents.

  • PDF

비용해성 산업용 분진이 배전용 자기제 현수애자의 전기적 특성에 미치는 영향 (The Effect of the Non Soluble Industrial Dust on the Electrical Properties of Distribution Porcelain Suspension Insulators)

  • 김찬영;송일근;김주용;한재홍;김동명;이병성
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제50권4호
    • /
    • pp.182-189
    • /
    • 2001
  • In this paper, the distribution suspension porecelain insulators which had been used for long periods in the contaminated area were evaluated. The contaminated area is close to the sea and in the high density of industries. The heavily contaminated domestic and imported insulators were investigated by using electrical characteristics, such as power-frequency dry flashover voltage, power-frequency wet, flahover voltage, and leakage current. Also, these electrical results were compared with the contaminants on the surface. From these analysis, we found that the contamination from the industrial dust, only slightly decreased flashover voltage and increased leakage current. Therefore, the electrical properties of insulators used for 30 years in the area of coast and industrial complex were not much changed.

  • PDF

갓 형상에 따른 폴리머 현수애자의 열화특성 (Performance of Polymer Suspension Insulator with Shed Profile)

  • 조한구;이운용;강성화;임기조;여학규;지원영
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2003년도 추계학술대회 논문집 Vol.16
    • /
    • pp.539-542
    • /
    • 2003
  • Recently, the polymer insulators which are being used for high voltage applications have some advantages such as light weight, small size, vandalism resistance, hydrophobicity and easy making process. During outdoor service of polymer insulators, the surface of the insulating material is frequently subjected to moisture and contamination which lead to the well known phenomenon of dry band arcing. Their tracking resistance, erosion resistance, end sealing and shed design are very important because dry band arcing causes degradation of polymer surface. The shape design of porcelain insulator is formalized but design standard for polymer insulator is no standardized up to now, much research is necessary in real condition. In this paper, the aging property of polymer insulator with shed shape(regular, alternative type) is analyzed through numerical analysis, CEA(canadian electricity association) tracking wheel test and IEC 61109 Annex C.

  • PDF

400kN 송전용 자기애자의 재질에 따른 특성 연구 (A study on properties of 400kN porcelain suspension insulator for transmission line by analyzing of raw materials)

  • 최인혁;최장현;정윤환;이동일;정길조;민병욱
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 C
    • /
    • pp.1637-1639
    • /
    • 2004
  • In order to analyze the physical and chemical characteristics of the home production porcelain insulators by change of the alumina addition amount, 36000lbs ball socket type suspension insulators which were manufactured in 1989, 1995 and 2001 removed in transmission line and an experiment was performed. By the result, 8 [wt.%] alumina that influences the mechanical properties and arc resistance properties in case of insulators that were manufactured in 1989 was contained, and the relative density and the fracture toughness of insulators appeared by 94.2% and 1.4 [MPa $M^{1/2}$], respectively. However, 12 [wt.%] alumina was contained in case of insulators that were manufactured in 1995, and the relative density and the fracture toughness of insulators appeared preferably lower by 92% and 1.3 [MPa $M^{1/2}$], respectively. Amount of alumina was contained most by 17 [wt.%] in case of insulators that were manufactured in 2001. It was confirmed that the electrical and mechanical characteristics such as the relative density and the fracture toughness appeared excellently by 96% and 1.7 [MPa $m^{1/2}$], respectively.

  • PDF

뇌 임펄스를 이용한 현수애자의 내부결함 검출 (The Inner Defect Detection of Suspension Insulators by Lightning Impulse)

  • 송일근;곽희로
    • 한국조명전기설비학회지:조명전기설비
    • /
    • 제9권6호
    • /
    • pp.83-90
    • /
    • 1995
  • 본 논문에서는 자기체 현수애자 내부의 미세한 결함에 의한 관통사고 원인과 예방책을 제시하고자 PD(Partial Discharge)실험에 사용된 자기체 현수애자의 전계강도를 분석하였고, 상용주파 유중파괴 시험과 급준파 전압시험을 비교, 시험하였다. 이중 시료는 SEM(Scanning Electron Microscope)을 사용해서 단면촬영과 소재의 특성을 분석하였으며, 이종 물질간의 열팽창계수 차이로 인한 사고 진전 가능성이 큰 자기부와 금구류의 접착제로 사용하고 있는 포틀랜드 시멘트에 대하여 오토클래브 팽창도를 시험하였고, 사고 예방을 위한 내부결함 평가방법을 제시하였다.

  • PDF

송전선로 폴리머애자 공사용 장비 개발 (Development of Working Platform for the Polymer Insulator String)

  • 민병욱;위화복;방항권;최한열;백수곤;박재웅
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 제37회 하계학술대회 논문집 A
    • /
    • pp.438-439
    • /
    • 2006
  • Porcelain insulators have generally been used in Korea to insulate a transmission line from the tower, and a highly polymerized compound polymer insulator which has superior stain proof characteristics, has also been used widely. Currently, a worker rides on the suspension insulator string for installation on towers and conductors but in case of polymer insulators, this will pollute and scratch the housing result in durability reduction by deterioration and corona. This study developed a high strength aluminum compound metal lauder designed to work on polymer insulators without riding, and a clamp type connecting device and safety gear for easy installation on the tower and conductor. These polymer insulator work device can be used for 154kV and 345kV polymer insulators through a strength and load test to secure safety. This paper presents field usage.

  • PDF

송전용 자기재 애자의 알루미나 함유량에 따른 특성 연구 (Study according to additional Alumina of Porcelain Insulator for T/L)

  • 최인혁;최장현;신태우;이동일
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2005년도 춘계학술대회 논문집
    • /
    • pp.65-68
    • /
    • 2005
  • 알루미나 함유량의 변화에 따른 국산 2001년, 2004년 애자와 외국산 2000년도 36,000lbs 불소켓형 현수애자에 대해 물성 분석을 실시하였다. 그 결과 2001년도 자기애자의 알루미나 함유량을 17%로 하고 2004년도 알루미나 함유량이 20%로 하였을 경우 자기 애자의 기계적 특성은 10% 정도 향상되었다. 그리고 2001년도에 제조한 애자의 자기 상대밀도는 이론밀도의 96%에 도달하였으나 2004년도에 제조한 애자의 상대 밀도는 이론민도의 98%에 도달하였으면 애자의 균일성을 나타내는 Qs 값은 5.01로 높게 나타났다.

  • PDF

초고압 현수애자의 Pin 형상에 따른 응력해석 (The Temperature Distribution Analysis and Temperature Rise Test of Pole Mold Transformer)

  • 조한구;박기호;한세원;윤문수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.155-157
    • /
    • 2001
  • Various types suspension insulators made of toughness glass or porcelain are used in the power transmission. And, Insulators are continually subject to mechanical and electrical stresses which depend on the characteristics of the line. The main factor that influence the increase in reliability of insulators. In operation is the capacity of the design to withstand the certain load over a long time, the mechanical strength of the insulators. This paper describes the results of a study on the stress analysis of suspension insulator based on the finite element analysis using NASTRAN. And, the mechanical strength was evaluated through such as kinds of pin type.

  • PDF