• Title/Summary/Keyword: Partial discharge pulse

Search Result 145, Processing Time 0.037 seconds

Comparative Analysis of PD Characteristics Under SF6, g3 and Dry Air Insulation (SF6, g3 및 Dry Air 절연에서 PD 특성 비교 분석)

  • Shin, Han-sin;Kim, Nam-Hoon;Kim, Sung-Wook;Kil, Gyung-Suk
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.33 no.6
    • /
    • pp.490-494
    • /
    • 2020
  • Sulphur hexafluoride (SF6) is mostly used as a current-insulating medium in gas-insulated switchgears (GIS), owing to its excellent dielectric strength and arc-extinguishing performance. The global warming potential (GWP) of SF6, however, is 23,900 times that of CO2, and its life time in the atmosphere is 3,200 years. For these reasons, new eco-friendly gases to replace SF6 are required. In this study, the partial discharge (PD) characteristics of green gas for grid (g3) and dry air (N2/O2) were analyzed to compare with those of SF6. A PD electrode system was designed to simulate the protrusion defect in GISs and fabricated for experimentation. To compare the PD characteristics of each gas, the discharge inception voltage (DIV), discharge extinction voltage (DEV), discharge magnitude, discharge pulse number, and phase pattern were analyzed. Results from this study are expected to provide fundamental materials for the design of eco-friendly GISs.

Characteristic Analysis on the Distribution Pattern of Discharge Signals Generated in the Power Cable (전력 케이블에서 발생되는 방전 신호의 분포패턴에 관한 특성 분석)

  • So, Soon-Youl;Hong, Kyung-Jin;Jung, Woo-Seong;Lim, Jang-Seob;Lee, Jin;Lee, Joon-Ung;Kim, Tae-Sung
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.11 no.11
    • /
    • pp.1035-1042
    • /
    • 1998
  • After the 1990's, a computer-aided partial discharge(PD) measurement system was referred in part of aging diagnosis using digital signal processing as the new technology has been studied. The PD patterns and relevant information for pattern recognition are discussed in PD research area, because discharge quantity(q), the number of discharge pulse(n) and the applied boltage phase($\varphi$) was combined with the system information of the aging state. This paper investigates the discharge phase and quantity, as well as the number of discharge(n) with regard to discharge signals generated in power cable. therefore, according to characteristic analysis on the distribution of $\varphi$, q and n, it is able to apply in the aging analysis of power cable which visual observation is impossible and distribution change of discharge signals offers much information for risk degree on aging progress of insulation materials.

  • PDF

Evaluation of Winding Insulation of IGBT PWM Inverter-Fed Low-Voltage Induction Motors

  • Park Doh-Young;Hwang Don-Ha;Kim Yong-Joo;Kang Do-Hyun;Lee Young-Hoon;Kim Dong-Hee;Lee In-Woo
    • Proceedings of the KIPE Conference
    • /
    • 2001.10a
    • /
    • pp.470-474
    • /
    • 2001
  • IGBT inverters have switching rise times of 0.2-2 $\mu$ sec, and have been believed to cause insulation stresses and premature motor failures. Inverter driven induction motors with high speed switching and advanced PWM techniques are widely used for variable speed applications. Recently, the insulation failures of stator winding have attracted many concerns due to high dv/dt of IGBT PWM inverter output. In this paper, the detailed insulation test results of 19 low-voltage induction motors are presented. Different types of insulation techniques are applied to 19 motors. The insulation characteristics are analyzed with partial discharge, discharge inception voltage, and dissipation factor tests. Also, breakdown tests by high voltage pulses are performed, and the corresponding breakdown voltages are obtained.

  • PDF

A Study on Insulation Degradation Diagnosis Using a Neural Network (신경회로망을 이용한 절연 열화진단에 관한 연구)

  • 박재준
    • The Journal of Information Technology
    • /
    • v.2 no.2
    • /
    • pp.13-22
    • /
    • 1999
  • In this paper, we purpose automatic diagnosis in online, as the fundamental study to diagnose the partial discharge mechanism and to predict the lifetime by introduction a neural network. In the proposed method, we use AE(acoustic emission) sensing system and calculate a quantitative statistic parameter by pulse number and amplitude. Using statically parameters such as the center of gravity(G) and the gradient if the discharge distribute(C), we analyzed the early stage and the middle stage. the quantitative statistic parameters are learned by a neural network. The diagnosis of insulation degradation and a lifetime prediction by the early stage time are achieved. On the basis of revealed excellent diagnosis ability through the neural network learning for the patterns during degradation, it was proved that the neural network is appropriate for degradation diagnosis and lifetime prediction in partial discharge.

  • PDF

Partial Discharge Characteristics at a Internal Void Using a Pulse Superimposing Technique (펄스 중첩법을 이용한 내부 보이드에서의 부분방전 특성.)

  • Kang, Ji-Hoon;Shin, Doo-Sung;HwangBo, Seung;Han, Min-Koo
    • Proceedings of the KIEE Conference
    • /
    • 1997.07d
    • /
    • pp.1624-1626
    • /
    • 1997
  • In this paper, a new PD measurement technique of pulse superposition method was proposed in order to investigate both PD mechanism and phase related PD patterns. From the experimental results, we could find that the polarity and the phase angle of the superposed pulse take great effects on PD characteristics and these method make it possible to get the physical information which statistical approach can not give. We could conclude that the changes of PD characteristics in the void surrounded by polymers may be attributed to the injection of charge carriers thereby formation of space charge in the surface and/or the bulk of the polymer.

  • PDF

A Study on the Insulation Performance Improvement of Induction Motors Fed by IGBT PWM Inverter (IGBT PWM 인버터 구동 유도전동기의 절연성능 향상기술 연구)

  • Hwang D.H.;Park D.Y.;Kim Y.J.;Lee Y.H.;Kim D.H.;Lee I.W.
    • Proceedings of the KIPE Conference
    • /
    • 2001.07a
    • /
    • pp.335-339
    • /
    • 2001
  • The recent advancements in power electronic switching devices have enabled high frequency switching operation and have improved the performance of pulse-width modulated (PWM) inverters for driving induction motors. But, the insulation failures of stator winding have attracted much concern due to high dv/dt of IGBT PWM inverter. In this paper, the test results for evaluation on the stator winding insulation of low-voltage induction motors for IGBT PWM inverter applications are presented. The insulation characteristics are analyzed with partial discharge and dissipation factor tests. Also, insulation breakdown tests by switching pulse voltage are performed. An effective insulation technique to enhance the insulation strength is suggested from the test results.

  • PDF

Comparision Study Between Modeling and Experiment of the Breakdown Voltage for AC Plasma Display Panel (AC 플라즈마 디스플레이패널의 방전개시전압에 모델과 실험의 비교에 관한 연구)

  • 박장식
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.13 no.12
    • /
    • pp.1039-1044
    • /
    • 2000
  • Breakdown voltage model and expertiments are compared for discharge cells of AC plasma display panel. In the model, discharge paths are assumed to be initial electric field lines and the one-dimensional continuity equation is applied to the charged particle transport at each field line. The comparisons are performed in the wide range of gas pressure (50-600torr), Xe partial pressure over total pressure (1-6%), sustain electrode gap(100-1000$\mu\textrm{m}$), wall height(130, 300$\mu\textrm{m}$), and voltage pulse width(2-6${\mu}$s). The presented breakdown voltage model well agree with experiments in the above wide range. The increase of breakdown voltage with the decrease of the width(L) of protruding electrode is also described by the model.

  • PDF

Discharge characteristics of a Flat Fluorescent Lamp(FFL) contanining Penning gases

  • Lee, Sang-Mok;Cho, Yong;Jung, Sang-Kooun;Jeong, Byoung-Hyun;Jeong, Yun-Cheol;Kwak, Min-Gi;Sohn, Sang-Ho
    • 한국정보디스플레이학회:학술대회논문집
    • /
    • 2006.08a
    • /
    • pp.675-678
    • /
    • 2006
  • We developed a Flat Fluorescent Lamp(FFL) with a high luminance by using the same discharge mode as PDP. Our FFL has the simple and unique structure where the glass substrates are used as dielectric layers. The panel has a striped line shape of 7 inch diagonal size. The Xe-Ne-He mixture gas was used to generate the plasma, and the gas discharge characteristics under both total gas pressure and partial gas pressure were investigated. The panel showed a maximum high luminance $7,270cd/m^2$ under bias of 20KHz pulse of 3KV.

  • PDF

A Life Prediction of Insulation Degradation Using Regression Analysis (회귀분석을 이용한 절연열화의 수명예측)

  • 김성홍;김재환;박재준;김순기;심종탁;최재관;이영상
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1997.11a
    • /
    • pp.302-305
    • /
    • 1997
  • Treeing due to partial discharge(PD) is one of the main causes of breakdown of the insulating materials and reduction of tile insulation life. Therefore the necessity for establishing a method to diagnose the aging of insulation materials and to predict the breakdown of insulation has become important. From this viewpoint, our studies diagnose insulation degradation using the method of computer sensing system, which has the advantages of PD and acoustic emission(AE) sensing system. To use advantages of these two methods can be used effectively to search for treeing location and PD in some materials. In analysis method of degradation. using statically operator such as the center of gravity (G). the gradient of the discharge distribution(C), we have analyzed far tole prediction of life which we can be obtained the time, occurred of many pulse of small discharge amplitude.

  • PDF

Analysis of Partial Discharge Pulse direction algorithm development and verification (부분방전 펄스 진행 방향 분석 알고리즘 개발 및 검증)

  • Kim, Dong-Ho;Kim, Jung-Yoon;Lee, Yong-Sung;Lee, Hyun-Sun;Choi, Won;Lee, Chang-Su
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.1560-1561
    • /
    • 2011
  • 본 논문에서는 전력케이블에서 부분방전이 발생했을 시 부부분방전 발생 진행 방향을 알 수 있는 펄스 진행 방향 분석 알고리즘 개발 및 검증을 하였다. 측정 센서로는 케이블 표면에 취부가 쉬운 UHF센서를 사용하였으며 고성능의 오실로 스코프와 방향추정 S/W에 알고리즘을 적용하여 모의 선로가 있는 실험실 환경에서 검증하였다.

  • PDF