• Title/Summary/Keyword: Partial discharge detection

Search Result 196, Processing Time 0.025 seconds

Ultrasonic detection properties for partial discharge at the premolded joint of a 23kV cable (23kV급 조립형 케이블 접속재에서 부분방전 신호의 초음파 검출특성)

  • Lee, Woo-Young;Ryoo, Hee-Suk;Sun, Jong-Ho;Kim, Sang-Jun;Song, Il-Gun;Kim, Joo-Yong
    • Proceedings of the KIEE Conference
    • /
    • 1996.07c
    • /
    • pp.1907-1909
    • /
    • 1996
  • In this paper, ultrsonic detection properties at a premolde joint utilized in a 23kV cables are studied. In a experiment a artificial defect within a joint and a measuring system are builded for generating discharges, gathering data about a detection properties, respectively. The experiment results show that one point detection is not allowed for monitoring a global status of a joint discharges and a detection sensitivity is less than 100pC. And also the attenuation and wave speed at the material of joint insulator are obtained.

  • PDF

Partial Discharge Measurement of Power Cables for Nuclear Power Plant (원자력발전소 전력케이블 부분방전 진단 사례)

  • Ha, Che-Wung;Ju, Kwang-Ho;Lim, Woo-Sang
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.8
    • /
    • pp.1632-1638
    • /
    • 2011
  • Electric cables are one of the most important components in a nuclear power plant since they provide the power needed to operate electrical equipment. Despite their importance, cables typically receive little attention since they are considered passive, long-lived components that have been very reliable over the years when subjected to the environmental conditions for which they were designed. The operating experience reveals that a defect of the insulator or poor construction causes the initial failure of cable. However, the number of cable failures increase with plant aging, and these cable failures are occurring within the plants' 40-year licensed period. These cable failures have resulted in plant transients, shutdown, loss of safety functions or redundancy, entries into limiting conditions for operation, and challenges for plant operators. Therefore, diagnosis of MV cable installed in NPPs has become one of the most urgent issues in recent years. In accordance with PSR, condition maintenance for cables is also continuously required. Recently, HFPD tests have been widely performed to diagnose cable in the transmission and distribution cable system. However, on-line HFPD wasn't used in the NPPs because of the danger of plant shutdown, measurement sensitivity and application problems, etc. In this paper, HFPD measurement with portable device was performed to evaluate the integrity of the 4.16kV & 13.8kV cable lines. The test results show that HFPD is highly attractive to the diagnosis of MV cables in NPP by high detection sensitivity on-site.

The Study of The Calibration Method for The UHF PD Detection in GIS (GIS에서 UHF 부분방전 검출법의 교정방안 연구)

  • Lee, W.Y.;Chong, J.K.;Choi, Y.K.
    • Proceedings of the KIEE Conference
    • /
    • 1999.07e
    • /
    • pp.2290-2292
    • /
    • 1999
  • The Ultra-High Frequency(UHF) method for detecting a partial discharge in Gas-Insulated Substation(GIS) has some advantages compared to a conventional method(IEC 270) but there is a shortage in view of a quantitative analysis. Therefore, this paper describes the implementation of a calibrator and the calibration process based on it. And its characteristics are confirmed through the experiment using the 362kV GIS chamber.

  • PDF

The study of Detection System Constuction For Urban Transit Circuit Breaker Motion Characteristic (도시철도 차단기 동작특성 검출장치 구성에 관한 고찰)

  • Im, Hyeong-Gil;Ryu, Ki-Seon;Lee, Gi-Seung
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2010.06a
    • /
    • pp.95-95
    • /
    • 2010
  • Because of the environmental matters the importance of the city railroad is as time goes by increasing. The case of obstacle of the power equipment which supplies electric power to city railroad will occur social and economical enormous loss. Thus, I studied on the preventing method in advance which makes it possible for us to maintain facilities efficiently. The main check points of the power facilities are voltage, current, humidity, partial discharge, move current. These points are gathered by sensor and transmitting to data acquisition device. These data are used to check equipment status in real time. In this paper I described in brief test process and results of the detection system.

  • PDF

A study on the development of a UWB UHF coupler for GIS PD detection (GIS 부분방전 측정용 UWB UHF 커플러에 관한 연구)

  • Choi, J.G.;Kim, I.S.;Kim, K.H.
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1776-1778
    • /
    • 2003
  • Partial Discharge(PD) pulses propagate in gas insulated substation(GIS) with rise time shorter than one nanosecond. Therefore, Ultra high frequency(UHF) couplers which have ultra wide band(UWB) characteristics from hundreds of MHz to several GHz are desirable for the detection of the PB pulses in GIS. In this paper, the authors proposed a log-periodic antenna for GIS PD detection. Various parameters of the coupler such as frequency bandwidth, coupler gain, radiation pattern, coupler geometry were considered through the simulations and the experiments together.

  • PDF

Diagnosis of power cable system based on the HFPD detection at on-site (HFPD 검출법을 이용한 지중 케이블 실선로 진단)

  • Lee, J.S.;Kim, C.S.;Lee, D.G.;Kong, C.H.;Seok, K.H.;Lee, K.W.
    • Proceedings of the KIEE Conference
    • /
    • 2004.05b
    • /
    • pp.97-100
    • /
    • 2004
  • HFPD(High Frequency Partial Discharge) measurement has been widely performed to diagnosis of cable system in the world although Korea just begin. The efficiency of measurement has been reported and proved by many researchers who are engaged in the diagnosis of high power apparatus. LG Cable has investigated the technology of diagnosis for cable system by means of PD measurement for 10 years. In this paper, PD measurement with portable device was performed to evaluate the quality of the 154kV transmission line and the 22.9kV XLPE cable line. Test results are shown that the HFPD detection technology is very attractive for the diagnosis of power cable system by high detection sensitivity at on-site.

  • PDF

The development of Ultra-High Frequency(UHF) sensor for Partial Discharge monitoring in Gas Insulated Switchgears (GIS내 부분방전 검출을 위한 광대역 UHF 센서 개발)

  • Kim, Young-Ro;Choi, Jae-Ok;Lee, Young-Sang;Kim, Jae-Chul;Park, Ki-Jun;Goo, Sun-Geun;Yoon, Jin-Yul
    • Proceedings of the KIEE Conference
    • /
    • 2004.07c
    • /
    • pp.1975-1978
    • /
    • 2004
  • We developed internal and external type sensor to measure ultra-high frequency (UHF) partial discharge (PD) in 170 kV gas-insulated switchgears (GIS). We also manufactured a PD-generator to verify and measure the detection sensitivity of those sensors. We measured the output power of the UHF PD sensors induced by PDs of 5 pC using the PD-generator. We measured UHF propagation loss of an 170 kV GIS for optimal arrangement of the sensors. We used swept UHF signal from a network analyzer into the GIS to measure the loss of various components of the GIS.

  • PDF

A Novel AE Based Algorithm for PD Localization in Power Transformers

  • Mehdizadeh, Sina;Yazdchi, Mohammadreza;Niroomand, Mehdi
    • Journal of Electrical Engineering and Technology
    • /
    • v.8 no.6
    • /
    • pp.1487-1496
    • /
    • 2013
  • In this paper, a novel algorithm for PD localization in power transformers based on wavelet de-noising technique and energy criterion is proposed. Partial discharge is one of the main failures in power transformers. The localization of which could be very useful for maintenance systems. Acoustic signals due to a PD event are transient, irregular and non-repetitive. So wavelet transform is an efficient tool for this signal processing problem that gives a time-frequency demonstration. First, different wavelet based de-noising methods are analyzed. Then, a reasonable structure for threshold value determining and applying manner on signals is presented. Evaluated errors are good evidences for choices. Next, applying the elimination low energy frequency bands is discussed and developed as a de-noising method. Time differences between signals are used for PD localization. Different ways in time arrival detection are introduced and a novel approach in energy criterion method is presented. At the end, the quality of algorithm is verified through the different assays in lab.

A Study on Development of High Voltage Mica Capacitors (고전압 마이카 커패시터 개발에 관한 연구)

  • Yun, Eui-Jung;Choi, Cheal-Soon;Kim, Jae-Wook;Lee, Dong-Hyuk
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.7
    • /
    • pp.1229-1234
    • /
    • 2008
  • In this work, ultra high-voltage (17 - 50 kV AC), reliable 80 pF mica capacitors for partial discharge system application were investigated. Mica was used as the dielectric of the capacitors. Using the conservative design rule, over 3 individual $50\;{\mu}m$ thick mica sheets with a size of 30mm{\times}35mm were used with lead foils to form a parallel capacitor element and 20 mica sheets were interleaved with lead foils to form a series stack of parallel capacitor element to meet the requirements of the capacitors. The dimensions of the fabricated 80 pF capacitors for 17 kV AC and 50 kV AC were $90\;mm{\times}90\;mm$ and $95\;mm{\times}180\;mm$, respectively. The high-frequency characteristics of the capacitance (C) and dissipation factor (D) of the developed capacitors were measured using a capacitance meter. The developed capacitors exhibited C of 79.5 - 87.5 pF, had D of 0.001% over the frequency ranges of 150 kHz to 50 MHz, had a self-resonant frequency of 65 MHz, and showed results comparable to those measured for the capacitors prepared recently by $Adwel^{Tm}$. The developed capacitors also showed excellent characteristics for thermal shock test and temperature cycling test.