Browse > Article

A Study on Development of High Voltage Mica Capacitors  

Yun, Eui-Jung (호서대 공대 시스템제어공학과)
Choi, Cheal-Soon (에스아이알(주))
Kim, Jae-Wook (남서울대 공대 전자공학과)
Lee, Dong-Hyuk (호서대 공대 시스템제어공학과)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.57, no.7, 2008 , pp. 1229-1234 More about this Journal
Abstract
In this work, ultra high-voltage (17 - 50 kV AC), reliable 80 pF mica capacitors for partial discharge system application were investigated. Mica was used as the dielectric of the capacitors. Using the conservative design rule, over 3 individual $50\;{\mu}m$ thick mica sheets with a size of 30mm{\times}35mm were used with lead foils to form a parallel capacitor element and 20 mica sheets were interleaved with lead foils to form a series stack of parallel capacitor element to meet the requirements of the capacitors. The dimensions of the fabricated 80 pF capacitors for 17 kV AC and 50 kV AC were $90\;mm{\times}90\;mm$ and $95\;mm{\times}180\;mm$, respectively. The high-frequency characteristics of the capacitance (C) and dissipation factor (D) of the developed capacitors were measured using a capacitance meter. The developed capacitors exhibited C of 79.5 - 87.5 pF, had D of 0.001% over the frequency ranges of 150 kHz to 50 MHz, had a self-resonant frequency of 65 MHz, and showed results comparable to those measured for the capacitors prepared recently by $Adwel^{Tm}$. The developed capacitors also showed excellent characteristics for thermal shock test and temperature cycling test.
Keywords
Epoxy-Mica Capacitor; High Voltage; Partial Discharge; on-line Detection Method; Temperature Cycling Test;
Citations & Related Records

Times Cited By SCOPUS : 0
연도 인용수 순위
  • Reference
1 Dong-Sik Kang, Yong-Joo Kim, Young-Ho Yun, 'Evaluation of Reliability on the 6.6kV Class Ceramic Coupler for On-line Partial Discharge Measurement in Winding Machines', KIEE International Transactions on Power Engineering, Vol. 54, No. 2, pp. 69-75, Feb. 2005
2 윤대희, 황돈하, 신병철, 김용주, 이광식, '회전기 고정자 권선에서의 운전 중 절연열화 진단기법', 한국조명.전기설비학회 추계학술대회 논문집, pp.89-93, Nov. 2000
3 신희상, 조성민, 강철, 김재철, 강동식, 조국희, '고압 회전기 부분방전 신호의 노이즈 특성 분석', 한국조명.전기설비학회 추계학술대회논문집, pp.287-290, Nov. 2007
4 T.E. Goodeve, G.C. Stone, and L. Macomber, 'Experience with Compact-Mica Capacitors for Rotating Machine Partial Discharge Detection', Electrical Electronics Insulation Conference, and Electrical Manufacturing & Coil Winding Conference, pp. 685-689, September 1995
5 J.S. Bowers, 'Characterization of Reconstituted Mica Paper for Use in High Voltage Capacitors', Electrical Insulation Conference and Electrical Manufacturing & Coil Winding Conference, pp. 303-307, October 1999