• 제목/요약/키워드: PSS tuning

검색결과 36건 처리시간 0.024초

면역 알고리즘을 이용한 전력 계통 안정화 장치의 최적 파라미터 선정 (An Optimal Parameter Selection of Power System Stabilizer using Immune Algorithm)

  • 정형환;이정필;정문규;이광우
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제49권9호
    • /
    • pp.433-445
    • /
    • 2000
  • In this paper, optimal tuning problem of power system stabilizer(PSS) using Immune Algorithm(IA) is investigated to improve power system dynamic stability. In proposed method, objective function is represented as antigens. An affinity calculation is embedded within the algorithm for determining the promotion or suppression of antibody. An antibody that most fits the antigen is considered as the solution to PSS tuning problem. The computaton performance by the proposed method is compared with Genetic Algorithm(GA). The porposed PSS using IA has been applied for two sample system, single-machine infinite bus system and multi-machine power system. The performance of the proposed PSS is compared with that of conventional PSS. It is shown that the proposed PSS tuned using immune algorithm is more robust than conventional PSS.

  • PDF

청평양수 발전기의 PSS 파라메터 튜닝 및 시뮬레이터를 이용한 성능검증 (Application of a Digital PSS to 220MVA Pumped Storage Unit and Its Validation Using Real-Time Digital Simulator)

  • 신정훈;김태균;추진부;백영식
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 A
    • /
    • pp.319-322
    • /
    • 2005
  • This paper describes practical tuning methods and testing of a digital PSS, which uses both frequency and power, with the 220MVA Chungpyung P/P #1 in the KEPCO system to enhance the damping of local modes. In the first step, the objective phase of PSS is computed through a phase leading function to provide compensation between the exciter reference point and the generator air-gap torque before tuning the PSS's time constants. In addition, eigenvalue analysis was used to determine a range of PSS's gain, whichis the more useful for field testing rather than a single gain value. The Real-Time Digital Simulator was used to verify safe operations of the PSS in the presence of disturbances, such as AVR step and three phase fault.

  • PDF

PSS 정수 튜닝을 위한 전력시스템 미소신호 안정도 해석 프로그램 (Computer Analysis Program of Small-Signal Stability of Power System for Tuning PSS′s parameters)

  • 김동준;문영환;허진;신정훈;김태균;추진부
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제52권5호
    • /
    • pp.241-249
    • /
    • 2003
  • This paper describes a novel approach for performing eigenvalue analysis and frequency domain analysis of multi-machine power system. The salient feature of this approach is a direct approach for constructing the state matrix equations of linearized power systems about its operating point using modular technique. These state matrix equations are then used to obtain eigenvalues and mode shapes of the system, and frequency response, or Bode, plots of selected transfer functions. The proposed program provides a flexible tool for systematic analyses of tuning PSS's parameters. The paper also presents its application to the analyses of a single-machine infinite bus system and two-area system with 4 machines.

대형 화력발전소EX2000 여자시스템 PSS 튜닝 : Part 2-현장 튜닝시험 및 검증 (PSS Tuning of EX2000 Excitation System in Thermal Plant: Part II-Site Tuning Test and Validation)

  • 김동준;문영환;김성민;김진이;황봉환;조종만
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.15-16
    • /
    • 2008
  • This paper describes the on-site PSS Tuning Test of EX2000 excitation of Dangin T/P #4. The on-line 2% AVR step test in 500MW was performed by setting PSS gain from 0 to 15 by 3 increasement. The time-domain measured data was also analyzed by DFT analysis. Finally, the measured data was replicated and verified by running the time-domain dynamic simulation.

  • PDF

다중-입력 PSS의 실제적인 튜닝 방법과 대형 전력 시스템에의 적용 (A Practical Tuning Method of Dual-Input PSS and its Application to Large Power System)

  • 김동준;문영환;허진;신정훈;김태균;추진부
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제51권7호
    • /
    • pp.362-370
    • /
    • 2002
  • This paper describes the practical tuning method of dual-input PSS and its application to Muju P/P #2 with Proto PSS, which is based on DSP technology and uses both frequency and power. First, the model parameters of generator system used in this paper have been derived from the generator characteristic testing. Then, in the selection of PSS parameters, the Bode plot is plotted in order to tune the PSS's time constants which are able to compensate the phase lagging due to generator and excitation system. In addition, the eigenvalue analysis is also performed for determining a reliable PSS gain, $K_{s}$. Finally, the transient stability program has been utilized to verify the safe operation of Proto PSS against the predictable disturbances such as the AVR-step test and generator unloading test. In on-site test, the simulated results have been identically duplicated by implementing AVR step test in Muju P/P #2 with Proto PSS, which has the previously designed PSS parameters.s.

유전알고리즘을 이용한 전력계통 안정화 장치의 강인한 $H_\infty$최적 튜닝 ($H_\infty$ Optimal tuning of Power System Stabilizer using Genetic Algorithm)

  • 정형환;이준탁;이정필;한길만
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제49권3호
    • /
    • pp.85-94
    • /
    • 2000
  • In this paper, a robust H$\infty$ optimal tuning problem of a structure-specified PSS is investigated for power systems with parameter variation and disturbance uncertainties. Genetic algorithm is employed for optimization method of PSS parameters. The objective function of the optimization problem is the H$\infty$-norm of a closed loop system. The constraint of the optimization problem are based on the stability of the controller, limits on the values of the parameters and the desired damping of the dominant oscillation mode. It is shown that the proposed H$\infty$ PSS tuned using genetic algorithm is more robust than conventional PSS.

  • PDF

대형 화력발전기 전력계통 안정화장치(IEEEST-PSS)의 정수선정 기법과 실계통 적용: PART II - PSS 현장 성능시험 절차 및 성능검증 (A Tuning Method for the Power System Stabilizer of a Large Thermal Power Plant and Its Application to Real Power System : PART II - Field Tests and Verification of PSS Performance)

  • 신정훈;남수철;백승묵;송지영;이재걸;김태균
    • 조명전기설비학회논문지
    • /
    • 제25권8호
    • /
    • pp.114-121
    • /
    • 2011
  • This paper, as the second part of the paper, dealt with the field test and test results to validate PSS(Power System Stabilizer) parameters which are previously tuned in Part 1 paper. In Part 1 of the paper, the selection of parameters such as lead-lag time constants for phase compensation and system gain was optimized by using linear & eigenvalue analyses and they were verified through the time-domain transient stability analysis. In part 2, the performance of PSS was finally verified by the generator's on-line field test. Through the comparisons of simulation results and measured data before and after tuning of the PSS, the models of generator and its controllers including AVR, Governor and PSS used in the simulation are verified and confirmed.

하이브리드시스템 모델링 기반 발전기 전력시스템 안정화장치 정수선정 기법 (Parameter Selection Method for Power System Stabilizer of a Power Plant based on Hybrid System Modeling)

  • 백승묵
    • 전기학회논문지
    • /
    • 제63권7호
    • /
    • pp.883-888
    • /
    • 2014
  • The paper describes the parameter tuning of power system stabilizer (PSS) for a power plant based on hybrid system modeling. The existing tuning method based on bode plot and root locus is well applied to keep power system stable. However, due to linearization of power system and an assumption that the parameter ratio of the lead-lag compensator in PSS is fixed, the results cannot guarantee the optimal performances to damp out low-frequency oscillation. Therefore, in this paper, hybrid system modeling, which has a DAIS (differential-algebraic-impusive-switched) structure, is applied to conduct nonlinear modeling for power system and find optimal parameter set of the PSS. The performances of the proposed method are carried out by time domain simulation with a single machine connected to infinite bus (SMIB) system.

자기조정 퍼지제어기를 이용한 SVC계통의 안정화 장치의 설계 (A Design of Power System Stabilization for SVC System Using Self Tuning Fuzzy Controller)

  • 주석민;허동렬;김해재
    • 전기학회논문지P
    • /
    • 제51권2호
    • /
    • pp.60-67
    • /
    • 2002
  • This paper presents a control approach for designing a self tuning fuzzy controller for a synchronous generator excitation and SVC system. A combination of thyristor-controlled reactors and fixed capacitors (TCR-FC) type SVC is recognized as having the most flexible control and high speed response, which has been widely utilized in power systems, is considered and designed to improve the response of a synchronous generator, as well as controlling the system voltage. The proposed parameter self tuning algorithm of fuzzy controller is based on the steepest decent method using two direction vectors which make error between inference values of fuzzy controller and output values of the specially selected PSS reduce steepestly. Using input-output data pair obtained from PSS, the parameters in antecedent part and in consequent part of fuzzy inference rules are learned and tuned automatically using the proposed steepest decent method. The related simulation results show that the proposed fuzzy controller is more powerful than the conventional ones.

퍼지형 전력계통안정화제어기의 실계통 적용 및 안정도 향상 (Application of Fuzzy-PSS to KEPCO power system and stability enhancement)

  • 최경선;이동인;이광식
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 하계학술대회 논문집 D
    • /
    • pp.1052-1055
    • /
    • 1997
  • The importance of dynamic stability of power system is increasing as the excitation system using static type are greatly enlarged. There are several types of PSS at Present, Elements of PSS consist of Notch filter, lead-lag filter, washout limiter which are variable. The existing power system has a difficulty in determining the optimal PSS parameters whenever PSS is installed. And it is recommended to retune PSS parameters periodically because system characteristics change due to aging. In this paper, intelligent PSS using fuzzy concept is introduced to get over difficulties mentioned above. The usefulness of fuzzy-type PSS was verified by applying FPSS to KEPCO power system. Generally, the voltage regulation deteriorates if conventional PSS is applied because supplementary signal is added into AVR summing point to damp Power oscillation. In this paper this problem is solved by AVR limiter and fuzzy members tuning.

  • PDF