대형 화력발전소EX2000 여자시스템 PSS 튜닝 : Part 2-현장 튜닝시험 및 검증

PSS Tuning of EX2000 Excitation System in Thermal Plant: Part II-Site Tuning Test and Validation

  • 발행 : 2008.07.16

초록

This paper describes the on-site PSS Tuning Test of EX2000 excitation of Dangin T/P #4. The on-line 2% AVR step test in 500MW was performed by setting PSS gain from 0 to 15 by 3 increasement. The time-domain measured data was also analyzed by DFT analysis. Finally, the measured data was replicated and verified by running the time-domain dynamic simulation.

키워드