• 제목/요약/키워드: PSS model parameters

검색결과 16건 처리시간 0.027초

다중입력 PSS 튜닝 방법과 612 MVA 화력기 적용: Part 1-IEEE PSS2A 튜닝 방법 (Tuning of Dual-input PSS and Its Application to 612 MVA Thermal Plant: Part 1-Tuning Methology of IEEE Type PSS2A Model)

  • 김동준;문영환;김성민;김진이;황봉환;조종만
    • 전기학회논문지
    • /
    • 제58권4호
    • /
    • pp.655-664
    • /
    • 2009
  • This paper, Part 1, describes the effective dual-input PSS parameter design procedure for the IEEE Type PSS2A against the Dangjin 612 MVA thermal plant's EX2000 excitation system. The suggested tuning technique used the model-based PSS tuning method and consisted of three steps: 1) generation system modeling; 2) determination of PSS2A model parameters using linear, time-domain transient and 3-phase simultaneous analyses, and 3) field testing and verification, which are described in Part 2. The effective PSS2A model parameters of EX2000 system in the Dangjin T/P #4 were designed according to the suggested procedure, and verified by using three analyses.

AVR 스템시험에 의한 울진 N/P 1호기 PSS 모델링 연구 (A Study of PSs Modeling of Ulchin N/P #1 by AVR Step Test)

  • 김동준;문영환;전동훈;김태균
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제50권8호
    • /
    • pp.351-358
    • /
    • 2001
  • This paper deals with the PSS modeling of Ulchin N/P #1 as well as the generator and excitation system modeling by utilizing the recorded data from AVR step test, which has been performed by entering small voltage signal into the AVR summing point. In addition to it. two recorded results obtained from the AVR step test with PSS sunning and without PSS running have not only been compared each other on the time domain, but also they heve been analyzed with FFT analysis on the frequency domain; thus, the desirable effects of running PSS in Ulchin N/P #1 on power system have been explicitly confirmed. Finally, the derived PSS model parameters lead to good matches between simulation results and recorded data.

  • PDF

대형 화력발전소 EX2000 여자시스템 PSS 튜닝 : Part 1- 최적 PSS 파라메터 설계 (PSS Tuning of EX2000 Excitation System in Thermal Plant: Part I- Optimal PSS Parameter Design)

  • 김동준;문영환;김성민;김진이;황봉환;조종만
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.13-14
    • /
    • 2008
  • This paper describes the optimal PSS parameter design for the PSS of EX2000 excitation system. The suggested tuning technique uses the model-based PSS tuning method which have three steps: generation system modeling, determination of PSS parameters, and on-site test. Using this method, the PSS parameters of EX2000 system in Dangjin T/P #4 was designed and verified by linear analysis program, PSS/E, and EMTDC/PSCAD.

  • PDF

다중-입력 PSS의 실제적인 튜닝 방법과 대형 전력 시스템에의 적용 (A Practical Tuning Method of Dual-Input PSS and its Application to Large Power System)

  • 김동준;문영환;허진;신정훈;김태균;추진부
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제51권7호
    • /
    • pp.362-370
    • /
    • 2002
  • This paper describes the practical tuning method of dual-input PSS and its application to Muju P/P #2 with Proto PSS, which is based on DSP technology and uses both frequency and power. First, the model parameters of generator system used in this paper have been derived from the generator characteristic testing. Then, in the selection of PSS parameters, the Bode plot is plotted in order to tune the PSS's time constants which are able to compensate the phase lagging due to generator and excitation system. In addition, the eigenvalue analysis is also performed for determining a reliable PSS gain, $K_{s}$. Finally, the transient stability program has been utilized to verify the safe operation of Proto PSS against the predictable disturbances such as the AVR-step test and generator unloading test. In on-site test, the simulated results have been identically duplicated by implementing AVR step test in Muju P/P #2 with Proto PSS, which has the previously designed PSS parameters.s.

보령 T/P 6호기 PSS 모델링과 검증 (PSS Modeling and Cerification for #6 Generator of Boryong T/P)

  • 최홍관;김동준;문영환;김용학;윤용범
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 A
    • /
    • pp.31-34
    • /
    • 2002
  • It studied modelling about employing analog PSS in domestic 500MW grade standard thermoelectric power plant in this paper. Modeling and parameters were verified by simulation of PSS response characteristics measured in AVR step examination and using power plant system model parameters decided by generator characteristics test. Through this PSS modelling research, contributed in domestic electrical power system small signal stability as that do modelling to be possible exact analysis of power system.

  • PDF

Enhancement of Power System Dynamic Stability by Designing a New Model of the Power System

  • Fereidouni, Alireza;Vahidi, Behrooz
    • Journal of Electrical Engineering and Technology
    • /
    • 제9권2호
    • /
    • pp.379-389
    • /
    • 2014
  • Low frequency oscillations (LFOs) are load angle oscillations that have a frequency between 0.1-2.0 Hz. Power system stabilizers (PSSs) are very effective controllers in improvement of the damping of LFOs. PSSs are designed by linearized models of the power system. This paper presents a new model of the power system that has the advantages of the Single Machine Infinite Bus (SMIB) system and the multi machine power system. This model is named a single machine normal-bus (SMNB). The equations that describe the proposed model have been linearized and a lead PSS has been designed. Then, particle swarm optimization technique (PSO) is employed to search for optimum PSS parameters. To analysis performance of PSS that has been designed based on the proposed model, a few tests have been implemented. The results show that designed PSS has an excellent capability in enhancing extremely the dynamic stability of power systems and also maintain coordination between PSSs.

복합화력발전소 가스터빈 발전기계통 모델정수 도출 및 검증을 위한 특성시험 (Characteristic Tests on the Gas Turbine Generator System for Determination and Verification of Model Parameters in a Combined Cycle Power Plant)

  • 김종구;유호선
    • 플랜트 저널
    • /
    • 제17권4호
    • /
    • pp.35-40
    • /
    • 2021
  • 본 연구에서는 서인천복합 6호기 가스터빈 발전기계통에 대하여 기술특성시험을 실시하여 모델정수를 도출하고 검증하였다. 발전기 최대/최소 무효전력 한계시험 결과 최대 무효전력 한계는 80 MVar이고, 최소 무효전력 한계는 -30 MVar이다. 발전기는 GENROU 모델을 사용하였고, 계자시정수(T'do)는 4.077 s, 관성정수(H)는 5.461 P.U로 결정하였다. 여자시스템은 ESST4B 모델을 사용, 무부하 2% AVR 스텝시험을 모의하는 방식으로 모델정수를 도출하고 검증하였으며, PSS 모델링은 PSS2A 모델정수로 도출하였고, PSS Off/On일때 측정된 계측 데이터를 모의, 비교하여 검증하였다. 조속기-터빈는 GGOV1 모델을 사용하여 모델정수를 도출하고 검증하였다. PSS/E 시뮬레이션 프로그램을 통해 10% 조속기 스텝시험을 모의하여 결정된 조속기-터빈 모델정수의 수치 안정성을 확인하였다.

다중입력 PSS 튜닝 방법과 612 MVA 화력기 적용: Part 2-현장 튜닝시험 및 성능검증 (Tuning of Dual-input PSS and Its Application to 612 MVA Thermal Plant: Part 2-Field Testing and Performance Verification)

  • 김동준;문영환;김성민;김진이;황봉환;조종만
    • 전기학회논문지
    • /
    • 제58권4호
    • /
    • pp.665-670
    • /
    • 2009
  • The second paper, Part 2, describes the field testing of IEEE type PSS2A EX2000 excitation in the Dangjin 612 MVA T/P #4. The final PSS gain, $K_s$, was determined by inputting 2%-step signals into AVR at a loading of 500MW and increasing $K_s$, from 0 to 15 in increments of 3. After the field testing, the measured data was also analyzed by Discrete Fourier Transformation(DFT) analysis, and the model parameters of generation system were verified by replicating the measured data with the transient stability program.

측정에 의한 울진 원자력 1호기 PSS 모델링 연구 (A Study of PSS Modelling of Ulchin Nuclear Plant Unit #1 by AVR Step Test)

  • 김동준;문영환;전동훈;김태균
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 추계학술대회 논문집 학회본부 A
    • /
    • pp.152-155
    • /
    • 2000
  • This paper deals with the PSS modelling of Ulchin N/P Unit #1 by utilizing the recorded data from AVR step test. In addition to it, the recorded results obtained from the AVR step test with PSS running and without PSS running are not only compared each other on the time domain but they are also analyzed with FFT on the frequency domain; the desirable effect of running PSS in Ulchin N/P Unit #1 is examined. Finally, the derived PSS model parameters lead to good matches between simulation results and recorded data.

  • PDF

A Simultaneous Perturbation Stochastic Approximation (SPSA)-Based Model Approximation and its Application for Power System Stabilizers

  • Ko, Hee-Sang;Lee, Kwang-Y.;Kim, Ho-Chan
    • International Journal of Control, Automation, and Systems
    • /
    • 제6권4호
    • /
    • pp.506-514
    • /
    • 2008
  • This paper presents an intelligent model; named as free model, approach for a closed-loop system identification using input and output data and its application to design a power system stabilizer (PSS). The free model concept is introduced as an alternative intelligent system technique to design a controller for such dynamic system, which is complex, difficult to know, or unknown, with input and output data only, and it does not require the detail knowledge of mathematical model for the system. In the free model, the data used has incremental forms using backward difference operators. The parameters of the free model can be obtained by simultaneous perturbation stochastic approximation (SPSA) method. A linear transformation is introduced to convert the free model into a linear model so that a conventional linear controller design method can be applied. In this paper, the feasibility of the proposed method is demonstrated in a one-machine infinite bus power system. The linear quadratic regulator (LQR) method is applied to the free model to design a PSS for the system, and compared with the conventional PSS. The proposed SPSA-based LQR controller is robust in different loading conditions and system failures such as the outage of a major transmission line or a three phase to ground fault which causes the change of the system structure.