• 제목/요약/키워드: PD localization.

검색결과 29건 처리시간 0.026초

차폐분리에 의한 전력케이블 및 접속함의 부분방전 위치 검출 (PD Localization by Metal Sheath Interruption Methods for Power Cable and Accessories)

  • 이창영;신두성;김충식;김동욱;박완기
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제49권3호
    • /
    • pp.196-201
    • /
    • 2000
  • It is very important not only to detect PD signal but also to locate PD source in power cable line including its accessories. In this paper, the PID localization technique using interruption of metal sheath of cable or accessory is described. By interruption of metal sheath, the polarity of PD pulse to be measured on each part can be compared. With this technique, the exact location of PD in the accessory which has some defects can be found. Although the 'Soft' interruption method, that is, cable sheath is divided by semi-conductive layer with the resistance of higher than 1 k$\Omega$, was used instead of 'Hard' interruption method, it is also possible to detect exact location of PD. This technique is considered to be very effective for detecting PD localization in the type test of cable and accessories.

  • PDF

Localization of Barley yellow dwarf virus Movement Protein Modulating Programmed Cell Death in Nicotiana benthamiana

  • Ju, Jiwon;Kim, Kangmin;Lee, Kui-Jae;Lee, Wang Hu;Ju, Ho-Jong
    • The Plant Pathology Journal
    • /
    • 제33권1호
    • /
    • pp.53-65
    • /
    • 2017
  • Barley yellow dwarf virus (BYDV) belongs to Luteovirus and is limited only at phloem related tissues. An open reading frame (ORF) 4 of BYDV codes for the movement protein (MP) of BYDV gating plasmodesmata (PD) to facilitate virus movement. Like other Luteoviruses, ORF 4 of BYDV is embedded in the ORF3 but expressed from the different reading frame in leaky scanning manner. Although MP is a very important protein for systemic infection of BYDV, there was a little information. In this study, MP was characterized in terms of subcellular localization and programmed cell death (PCD). Gene of MP or its mutant (ΔMP) was expressed by Agroinfiltration method. MP was clearly localized at the nucleus and the PD, but ΔMP which was deleted distal N-terminus of MP showed no localization to PD exhibited the different target with original MP. In addition to PD localization, MP appeared associated with small granules in cytoplasm whereas ΔMP did not. MP associated with PD and small granules induced PCD, but ΔMP showed no association with PD and small granules did not exhibit PCD. Based on this study, the distal N-terminal region within MP is seemingly responsible for the localization of PD and the induction small granules and PCD induction. These results suggest that subcellular localization of BYDV MP may modulate the PCD in Nicotiana benthamiana.

A Novel AE Based Algorithm for PD Localization in Power Transformers

  • Mehdizadeh, Sina;Yazdchi, Mohammadreza;Niroomand, Mehdi
    • Journal of Electrical Engineering and Technology
    • /
    • 제8권6호
    • /
    • pp.1487-1496
    • /
    • 2013
  • In this paper, a novel algorithm for PD localization in power transformers based on wavelet de-noising technique and energy criterion is proposed. Partial discharge is one of the main failures in power transformers. The localization of which could be very useful for maintenance systems. Acoustic signals due to a PD event are transient, irregular and non-repetitive. So wavelet transform is an efficient tool for this signal processing problem that gives a time-frequency demonstration. First, different wavelet based de-noising methods are analyzed. Then, a reasonable structure for threshold value determining and applying manner on signals is presented. Evaluated errors are good evidences for choices. Next, applying the elimination low energy frequency bands is discussed and developed as a de-noising method. Time differences between signals are used for PD localization. Different ways in time arrival detection are introduced and a novel approach in energy criterion method is presented. At the end, the quality of algorithm is verified through the different assays in lab.

Partial Discharge Localization Based on Detailed Models of Transformer and Wavelet Transform Techniques

  • Hassan Hosseini, Seyed Mohammad;Rezaei Baravati, Peyman
    • Journal of Electrical Engineering and Technology
    • /
    • 제10권3호
    • /
    • pp.1093-1101
    • /
    • 2015
  • Partial Discharge (PD) is a physical phenomenon, which causes defects and damages to the insulation. This phenomenon is regarded as the most important source of fault and defect in power transformers. Therefore, methods of high speed and precision are considered of special importance for the maintenance of transformers in localization of the origin of partial discharge. In this paper, the transformer winding is first modeled in a transient state by using RLC ladder network and multiconductor transmission line (MTL) models. The parameters of the two models were calculated by Ansoft Maxwell software, and the simulations were performed by Matlab software. Then, the PD pulses were applied to the models with different widths of pulses. With regard to the fact that the signals received after the application of PD had a variable frequency nature over time, and based on the wavelet transform and signal energy, a new method was presented for the localization of PD. Ultimately; the mentioned method was implemented on a 20 kV winding distribution transformer. Then, the performances of the models used in this paper, including RLC and MTL models, were compared in different frequency bands for the correct distinction of partial discharge location.

Atomic Structure Analysis of A ZnO/Pd Interface by Atomic Resolution HVTEM

  • Saito, Hiromitsu;Ichinose, Hideki
    • Applied Microscopy
    • /
    • 제36권spc1호
    • /
    • pp.41-46
    • /
    • 2006
  • Interfacial atomic structure (chemical structure) of a Pd/ZnO hetero junction was investigated by atomic resolution high voltage transmission electron microscopy (ARHVTEM). A misfit dislocation did not work as a stress accommodation mechanism in the ZnO(0001)/Pd (111) interface. But the periodic stress localization occurred in the ZnO($10\bar{1}0$)/(200) interface. The periodicity of the local strain coincided with that of misfit dislocation. Atomic structure image of the ARHVTEM showed that an atomic arrangement across the interface was in the order of O-Zn-Pd. It was shown that mechanical weakness of the ZnO(0001)/Pd(111) interface against cyclic heating is attributable to the absence of the periodic stress localization of the misfit dislocation.

Comparison of High Frequency Detailed Generator Models for Partial Discharge Localization

  • Hassan Hosseini, S.M.;Hosseini Bafghi, S.M.
    • Journal of Electrical Engineering and Technology
    • /
    • 제10권4호
    • /
    • pp.1752-1758
    • /
    • 2015
  • This paper presents partial discharge localization in stator winding of generators using multi-conductor transmission line (MTL) and RLC ladder network models. The high-voltage (HV) winding of a 6kV/250kW generator has been modeled by MATLAB software. The simulation results of the MTL and the RLC ladder network models have been evaluated with the measurements results in the frequency domain by applying of the Pearson’s correlation coefficients. Two PD generated calibrator signals in kHz and MHz frequency range were injected into different points of generator winding and the signals simulated/measured at the both ends of the winding. For partial discharge localization in stator winding of generators is necessary to calculate the frequency spectrum of the PD current signals and then estimate the poles of the system from the calculated frequency spectrum. Finally, the location of PD can be estimated. This theory applied for the above generator and the simulation/measured results show the good correlation for PD Location for RLC ladder network and MTL models in the frequency range of kHz (10kHz<f<1MHz) and MHz (1MHz<f<5MHz) respectively.

Numerical Study of Estimating the Arrival Time of UHF Signals for Partial Discharge Localization in a Power Transformer

  • Ha, Sang-Gyu;Cho, Jeahoon;Lee, Juneseok;Min, Byoung-Woon;Choi, Jaehoon;Jung, Kyung-Young
    • Journal of electromagnetic engineering and science
    • /
    • 제18권2호
    • /
    • pp.94-100
    • /
    • 2018
  • Partial discharges (PDs) are electrical sparks that occur inside insulation between two conducting electrodes and can lead to the disastrous failure of insulation systems. To determine the location of a PD, a distributed array of UHF PD sensors is used to detect the electromagnetic (EM) signals emitted from the PD source, and the localization of the PD source can be estimated using the time difference of arrival (TDOA) between EM signals captured by the UHF PD sensor array. There are four popular methods to estimate the TDOA-the first peak method, the cross-correlation method, the energy criterion method, and the average time window threshold method. In this work, we numerically investigate the influence of noise on estimating the TDOA for the four different methods. Numerical results show that the energy criterion method is more robust against noise than other methods.

웨이브렛 변환을 이용한 부분방전신호의 잡음제거 특성 (Noise elimination of PD signal using Wavelet Transform)

  • 이현동;주재현;김기채;박원주;이광식;이동인
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 하계학술대회 논문집 C
    • /
    • pp.1679-1681
    • /
    • 2001
  • In this paper, As the wavelet transform has the properties of multi-resolution analysis and time-frequency domain localization, application of wavelet transform is used at partial discharge(PD) signal detected by electromagnetic wave detection method to extract PD signal's various frequency component and its time domain. therefore we can analyzed PD signal's time-frequency domain simultaneously. On the other hand, using wavelet transform denoising process, inclued noise signal in detected PD signal is well elimiated. we can propose the true shape of PD signal.

  • PDF

기중부분방전원 식별을 위한 광대역 부분방전신호의 측정 및 주성분분석기법의 적용 (Application of Principle Component Analysis and Measurement of Ultra wideband PD signal for Identification of PD sources in Air)

  • 이강원;김명룡;박대원;심재복;창상훈
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2006년도 하계학술대회 논문집 Vol.7
    • /
    • pp.505-506
    • /
    • 2006
  • PD(partial discharge) occurred from variable PD sources in air may be the cause of breakdown in high voltage equipment which affect huge outage in power system. Identification and localization of PD sources is very important for engineer to cope with huge accident beforhand. PD phenomena can be detected by acoustic emission sensor or electromagnetic sensor like antenna. This paper has investigated the identification method using PCA(principal component analysis) for the PD signals from variable PD sources, for which the electric field distribution and PD inception voltages were simulated by using commercial FEM program. PD signals was detected by ultra wideband antenna. Their own features were extracted as the frequency coefficients transformed with FFT(fast fourier transform) and used to obtain independent pincipal components of each PD signals.

  • PDF

웨이브렛 변환의 노이즈 제거기법에 의한 부분방전신호 특성 (Characteristics of Partial Discharges Signals Utilizing Method of Wavelet Transform Denoising Process)

  • 이현동;이광식
    • 조명전기설비학회논문지
    • /
    • 제15권4호
    • /
    • pp.62-68
    • /
    • 2001
  • 본 논문은 전기적 검출법에 의해 측정된 부분방전 신호에 대하여 웨이브렛 변환을 적용하여 각기 다른 주파수 성분을 동시에 추출하고 이들의 시간정보를 얻음으로써 시간과 주파수 영역에서 동시에 해석할 수 있도록 하였다. 그리고, 웨이브렛 변환의 노이즈 제거기법을 적용하여 부분방전 측정시에 포함되어 있는 노이즈를 제거하여 잡음제거 효과를 나타내었다.

  • PDF