• Title/Summary/Keyword: Overhead Transmission Line

Search Result 215, Processing Time 0.042 seconds

A Study on Analysis of Surge Characteristics on Gas Insulated Transmission Lines (가스절연송전선로의 서지특성 분석에 관한 연구)

  • Jung, Chae-Kyun;Park, Hung-Sok;Kang, Ji-Won;Jang, Tai-In;Yoon, Jong-Keon;Kim, Yang-Sang;Suk, Kwang-Hyun;Kim, Hyung-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.371_372
    • /
    • 2009
  • This paper describes surge characteristics on 345kV combined transmission system mixed overhead line and GIL(Gas Insulated Transmission Line). Then, it is compared with the results of the system mixed overhead line and XLPE power cables. Finally the lightning overvoltages are also discussed according to surge arrester installation in two kinds of combined transmission systems when the lighting strikes on the phase conductor.

  • PDF

A Study on Temperature and Tensile Load Analysis of Invar by Flame Exposure on Overhead Transmission Lines (화염노출에 의한 송전선로 인바 강심의 온도 및 인장하중 분석에 관한 연구)

  • Shin, Koo-Yong;Jung, Chae-Kyun;Lee, Sang-Yun;Kang, Ji-Won;Lee, Dong-Il
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.10
    • /
    • pp.1895-1901
    • /
    • 2009
  • This paper describes the conductor temperature and tensile load analysis of invar by flame exposure on STACIR(Super Thermal-resistance Aluminium-alloy Conductors Reinforced) overhead transmission line based on real fault phenomena. Firstly, short-circuit fault by flame exposure is analysed by EMTP/ATP simulation, then the cutting causes of Al layer are also discussed. And then, the conductor temperature is calculated based on IEC 60949 according to 3 kinds of materials including invar, Al conductor and ACSR when same load current respectively flows in 3 kinds of material, they are compared each other. Finally, the tensile load tests are performed with various samples including new invar, used invar for a long time and invar exposed flame.

Ion Effects of HVDC ±500 kV Double Bipole Overhead Transmission Line with Metallic Return Conductor Using Full-scale Test Line (실증시험선로를 이용한 도체귀로형 HVDC ±500 kV Double Bipole 가공송전선로의 이온류 특성 평가)

  • Shin, Kooyong;Kwon, Gumin;Ju, Munno;Woo, Jeong Min
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.5 no.4
    • /
    • pp.249-256
    • /
    • 2019
  • A full-scale test line was established to verify the electrical environmental interferences caused by the HVDC ±500 kV Double Bipole overhead transmission line with metallic return conductor, which is scheduled for construction in Korea and the fullscale test was conducted for one year. And through the human perception test of the DC electric-field under the HVDC Double Bipole line, the threshold value at which the human detects DC electric field was investigated to verify the validity of the design guide for the HVDC ±500 kV Double Bipole overhead transmission line. The polarity configuration of the HVDC ±500 kV Double Bipole test line was arranged diagonally with the same polarity in terms of the electrical environment disturbance and operation. The test line utilized the 6-bundle arrangement to prevent the corona discharge taking into account the domestic social acceptability. The test results show that the HVDC ±500 kV Double Bipole transmission line generated very little corona discharge from the conductors. Therefore, both DC electric field and ion current density met the domestic design guide for DC overhead transmission lines. Also, the human perception test of DC electric fields under the test line showed that 70% of participants did not recognize the DC electric field even when exposed to 23 kV/m.

Unbalace Current Analysis on the Bundled Conductors of the UHV Overhead Transmission Line (초고압 송전선로의 다도체 구성에 따른 불평형 전류 해석)

  • Jeong, Y.H.;Lee, H.K.;Sohn, H.K.;Cho, Y.K.
    • Proceedings of the KIEE Conference
    • /
    • 1999.07c
    • /
    • pp.1379-1381
    • /
    • 1999
  • The unbalance current on the bundled conductors of the UHV overhead transmission line is one of the factors affected on power transmission system. It is varied by distance between of bundled conductors and of phase to phase, phase arrangement. In this paper, we calculated unbalance current on the bundled conductors by a variety of line arrangements and also calculated magnetic field at the circumference of the line fed with this unbalance current.

  • PDF

Corona Cage Simulation on Environmental Characteristics Caused by the Ion flow of Candidated Conductor Bundles for HVDC Overhead Transmission (초고압 직류 가공송전 후보 도체방식의 이온류 환경특성 코로나 케이지 모의시험)

  • Ju, Mun-No;Yang, Kwang-Ho;Lee, Dong-Il;Shin, Koo-Yong
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.56 no.10
    • /
    • pp.1791-1795
    • /
    • 2007
  • Small ions generated at conductor corona sources remain in the atmosphere until they recombine with ions of opposite polarity, attach to aerosols, or make contact with an object. Ion current density is major factor to design conductor configuration of DC overhead transmission line. Several techniques have been used to measure the ion current of HVDC overhead transmission line. In this study, the ion current density was measured by a plate electrode made of a metal flat board at DC corona cage. The sensitivity of the plate electrode is $0.156uA/m^2/V$. To obtain an useful database on corona discharge, it is necessary to do corona test on several kinds of conductor bundles. Therefore, a number of experiments were conducted on several kinds of conductor bundles. To reliably analyze ion effects, corona cage test data were obtained over a long period of time under various weather conditions and expressed as a statistical distribution. Ion current density distribution in foul weather shows a significant increase in levels over the corresponding fair weather. Based on this results, we evaluated the environmental characteristic caused by ion flow of three candidated conductor bundles.

Assessment of the Electrical Environmental Characteristics to Decide Optimal Bundle Type for HVDC ${\pm}500kV$ Overhead Transmission Lines (HVDC ${\pm}500kV$ 가공 송전선로의 최적 도체방식 선정을 위한 전기환경특성 평가)

  • Ju, Mun-No;Kil, Gyung-Suk;Yang, Kwang-Ho;Lee, Sung-Doo;Hwang, Gi-Hyun
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.55 no.11
    • /
    • pp.520-526
    • /
    • 2006
  • Corona interferences, such as radio noise, audible noise and television noise, need to be taken into account in the design of HVDC transmission line conductor configuration. Therefore the line designer requires data from which to estimate the corona performance of any set of conductors. To get a sufficiently complete set of design data, it is necessary to examine the corona test of a large number of conductor geometries. This paper presents the results of corona cage test among three types of candidate conductors. It is quite clear from test results that the conductor geometries play an important role in establishing the magnitude of corona noise. Corona noise data from corona cage test are expressed as a statistical distribution of results obtained over long periods of time and various weather conditions. Therefore we can determine an environmentally-friendly conductor bundle for HVDC overhead transmission line. Based on this finding results, various simulations about HVDC line configurations, such as pole space and pole height, will be conducted. And then finally an optimal configuration for HVDC transmission line will be decided.

345kV Overhead Transmission Line Collapse Analysis and Countermeasures (345kV 인천화력 송전선로 철탑도괴 원인분석 및 대책)

  • Park, Jae-Ung;Shin, Tai-Woo;Choi, Jin-Sung;Choi, Han-Yeol;Min, Byeong-Wook
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.59 no.3
    • /
    • pp.531-535
    • /
    • 2010
  • 345kV Incheon Thermal Power Plant Transmission Line Collapse Analysis and Countermeasures. The Typhoon Galmaegi which had been formed in July 15, 2008 diminished into a tropical cyclone and cooled the air above the West Sea. The cooled air colliding with the warm inland air caused a strong whirlwind at some places in the west seaside; the whirlwind battered the 345kV Incheon Thermal Power Plant Transmission Line to be collapsed. The resistance of transmission towers against wind pressure, one of the key elements in transmission line engineering, is designed to endure the pressure corresponding to the maximum instantaneous wind speed. Before the above accident happened, no transmission line has ever been collapsed by a whirlwind. So this paper is aimed to analyze causes that collapsed 345kV Incheon Thermal Power Plant transmission line and to introduce countermeasures.

A Study for Computation of Swaying Angle for Jumper Safety Improvement in the Overhead Line (송전선로의 점퍼선 안전성 향상을 위한 횡진각 계산에 관한 연구)

  • 안영주;신춘식;변기식
    • Journal of the Korean Society of Safety
    • /
    • v.12 no.1
    • /
    • pp.44-50
    • /
    • 1997
  • As jumpers for overhead transmission lines increase In size, it Is necessary to take into the characteristics of jumper swaying space in order to determine jumper reinforcements adequately. From the theory of a structure made of beams, formulas for the sideway swaying of overhead transmission lines due to wind are modeled. And also natural frequency of the vibrated jumper is estimated to check the system resonance. The theoretical results can be led good suggestions to improve the economy and reliability of jumper structure.

  • PDF

Dynamic Line Rating Estimation Using Indirect Conductor Method in Overhead Transmission Lines (간접도체 방식을 이용한 가공송전선의 동적송전용량 추정)

  • Kim, Sung-Duck;Lee, Seung-Su;Jang, Tae-In;Kang, Ji-Won;Lee, Dong-Il
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.18 no.5
    • /
    • pp.189-197
    • /
    • 2004
  • The thermal rating of an overhead conductor, which is the maximum allowable current, is generally calculated on the basis of heat balance equation found in IEEE P738 standard. This is given as a function of the weather conditions such as air temperature, wind speed, wind direction, and sun heat. Wind speed among such weather parameters is strongly affected on determining the line rating when it appears very low level. Therefore there may occur inaccuracy since most anemometers used in line rating monitor systems may show low resolutions and stall speed performance. In this paper, we introduce a new methodology for determining the dynamic line rating in overhead transmission lines, without using my anemometer. It was shown that wind speed can be estimated by the temperatures of 2 indirect conductors, and through experimental study, the dynamic line rating obtained by the estimated wind speed was very closely that of weather model.

A study on the wind noise from transmission line and mitigation methods (송전선로에 의한 풍소음 발생 저감 기법)

  • Shin, K.Y.;Lee, D.I.;Yoon, J.Y.;Oh, C.H.;Kim, S.H.;Kim, J.Y.
    • Proceedings of the KIEE Conference
    • /
    • 1999.07e
    • /
    • pp.2143-2145
    • /
    • 1999
  • Measurements of wind noise, generated by High-voltage overhead transmission lines placed in a uniform flow are carried out in the Anechoic windtunnel. High-voltage overhead transmission lines generates audible wind noise, which cause a serious environment problem. Accordingly, wind noise has become one of major concerns for design engineers and operations personnel. In the present research, tests were mainly performed with various configuration of transmission line with spiral wires. Remarkable noise reduction was observed for some of the spiral transmission lines, compared with the noise generated without the spiral wire.

  • PDF