• Title/Summary/Keyword: Load interruption

Search Result 89, Processing Time 0.023 seconds

Decomposition Properties of Trifluoroiodomethane under Discharges and Interruptions

  • Cai, Fan-Yi;Tan, Dong-Xian;Zhou, Bai-Jie;Xue, Jian;Xiao, Deng-Ming
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.6
    • /
    • pp.2385-2391
    • /
    • 2018
  • This paper is devoted to detecting decomposition characteristics of Iodotrifluoromethane ($CF_3I$) under alternating current (AC) discharges or load current interruptions. The decomposition products are measured utilizing chromatography-mass spectroscopy. It is found that less than 1% $CF_3I$ gas decomposed after several interruptions at load current of 200 A or hundred times of AC discharges. However, under interruptions at a current of 400 A, more than 95% $CF_3I$ gas decomposed into carbon tetrafluoride ($CF_4$) and hexafluoroethane ($C_2F_6$). The equilibrium compositions based on Gibbs free energy minimization of $CF_3I$ was calculated to explain the decomposition mechanism.

Assessment of the optimal basic reliability in distribution system using genetic algorithm (배전계통 최적기본신뢰도 지수 평가를 위한 유전자 알고리즘의 적용)

  • Kim, Jae-Chul;Han, Seong-Ho;Lee, Bo-Ho;Rhee, Wook;Jang, Jeong-Tae
    • Proceedings of the KIEE Conference
    • /
    • 1995.11a
    • /
    • pp.64-66
    • /
    • 1995
  • This paper presents a new approach to evaluate optimal basic reliability indices of electric distribution systems using genetic algorithm. The use of optimal reliability evaluation is an important aspect of distribution system planning and operation to determine adequacy reliability level of each area. In this paper, the reliability model is based on the analytical method, connecting component failure to load point outage in each section. The proposed method applies genetic algorithm to calculate the optimal values of basic reliability indices, ie. failure rate and repair time, for a load point in the power distribution system, subject to minimizing interruption cost. Test results for the model system are reported in the paper compared with a direct optimization method(gradient projection).

  • PDF

Power Quality Analysis of Wind Power System Embedded in Distribution Networks (풍력발전시스템의 배전계통 연계운전 시 전의품질 해석)

  • Kim, Eung-Sang;Roh, Pyung-Kweon;Chu, Jin-Bu;Chang, Byung-Tae;Lee, Seung-Hak
    • Proceedings of the KIEE Conference
    • /
    • 1999.11b
    • /
    • pp.229-231
    • /
    • 1999
  • This paper deals with electromagnetic transient modelling of wind power system embedded in distribution networks. Wind power system consists of induction generator link reactor, distribution line, and controlled load unit. The introduction of embedded wind power system presents a new set of conditions to networks both with respect to power quantify needed to be transported and power quality such as sag swell, very short interruption, and flicker. This paper investigates the transient behavior of voltage, frequency, and load flow in wind driven induction generation system embedded in distribution networks.

  • PDF

A Study on the Restoration Aid Expert System for Distribution Networks (배전계통의 복구 지원 전문가 시스템에 관한 연구)

  • Lee, H.J.;Lee, K.S.;Lee, C.K.
    • Proceedings of the KIEE Conference
    • /
    • 2001.07a
    • /
    • pp.3-5
    • /
    • 2001
  • When a fault occurs on distribution network. blackout region may happen, then it should be restored as fast as possible to minimize interruption of electric service. In this paper. A near optimal method to restore distribution network is proposed. For an optimal restoration, the number or switching operations must be minimized. The proposed method generates a general restoration plan for any distribution network fault and designed to reduce switching operations considering available load transfers. In this method overall process time can reduce with heuristic rules, which make a reduction of search space before restoration process. To achieve a near optimal solution, multiple load transfer algorithm is proposed too.

  • PDF

Digital Control of Single Phase UPS for Input Power Factor Compensation (입력역률 보정을 위한 단상 UPS의 디지털제어)

  • Kim, D.G.;Lee, S.H.;Park, H.A.;Lee, K.Y.;Han, E.Y.;Baek, H.L.
    • Proceedings of the KIEE Conference
    • /
    • 1998.07f
    • /
    • pp.2054-2056
    • /
    • 1998
  • A conventional UPS can supply the clean power to the load. However, it may generate input current harmonics and the input power factor can be very poor. Therefore, the UPS itself may be a power interruption. This paper provides multifunctional converter of using single phase UPS. The proposed UPS can supply the clean power to the load without polluting the mains power system. The multi-functional converter provides battery charging, var compensation and harmonic suppression simultaneously. It was simulated to verify this work.

  • PDF

Control Algorithm of Hybrid System for Feeder Flow Mode Operation in Microgrid (마이크로그리드에서 하이브리드 시스템의 Feeder Flow Mode 운영을 위한 제어 알고리즘)

  • Moon, Dae-Seong;Seo, Jae-Jin;Kim, Yun-Seong;Won, Dong-Jun
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.1
    • /
    • pp.1-7
    • /
    • 2011
  • Active power control scheme for distributed generation in microgrid consists of feeder flow control and unit power control. Feeder flow control is more useful than the unit power control for demand-side management, because microgrid can be treated as a dispatchable load at the point of common coupling(PCC). This paper presents detailed descriptions of the feeder flow control scheme for the hybrid system in microgrid. It is divided into three parts, namely, the setting of feeder flow reference range for stable hybrid system operation, feeder flow control algorithm depending on load change in microgrid and hysteresis control. Simulation results using the PSCAD/EMTDC are presented to validate the inverter control method for a feeder flow control mode. As a result, the feeder flow control algorithm for the hybrid system in microgrid is efficient for supplying continuously active power to customers without interruption.

An Expert System for the Restoration of Distribution Networks (배전망 복구지원 전문가 시스템에 관한 연구)

  • 이흥재;이경섭;박성민
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.17 no.3
    • /
    • pp.87-94
    • /
    • 2003
  • When faults occur in a distribution network, blackout loads must be restored as fast as possible to minimize interruption of electric service. This paper presents an expert system to restore distribution networks. The system is designed to minimize switching operations in a heuristic sense by using heuristic rules. The restoration process is converted to the feasible path finding problem in the state space of expert system by application of general topological knowledge base. Multiple load transfer algorithm is proposed to deal with complex situations.

Evaluation of Reliability Indices for Power Systems using Genetic Algorithm and Complex Method (유전알고리즘과 Complex Method를 이용한 전력시스템의 신뢰도 지수 산정)

  • 유현호;김진오
    • Journal of Energy Engineering
    • /
    • v.8 no.4
    • /
    • pp.583-591
    • /
    • 1999
  • this paper proposes a new approach for calculating the reliability indices of generation system, such as interruption frequency and duration, by using the moment matching technique Two separate expressions are derived, one for the loss of load expectation(LOLE) and the other for the loss of load frequency (LOLF). These expressions are combination of exponentials and are therefore easily integrable and can be readily evaluated. In this paper, the parameters of the distribution functions of the LOLE and LOLF are evaluated by using Genetic Algorithm and Complex Method, and the proposed approach is quite comparable with the other methods at the aspect of accuracy and efficiency.

  • PDF

Line-Interactive DVR Using Multi-Level H-Bridge Inverter (멀티-레벨 H-Bridge 인버터를 이용한 Line-Interactive DVR)

  • Kang Dae-Wook;Woo Sung-Min;Kim Tae-Jin;Choi Chang-Ho;Hyun Dong-Seok
    • Proceedings of the KIPE Conference
    • /
    • 2001.12a
    • /
    • pp.139-143
    • /
    • 2001
  • Recently, the interest on power quality has been hot issue. The equipments cause voltage disturbance and has become more sensitive to the voltage disturbance. This paper deals with 5-Level H-Bridge Line-Inter active Dynamic Voltage Restorer(LIDVR) system. The LIDVR has following advantages in comparison with the DVR with series injection transformer It has the power factor near to unity under normal source voltage, can compensate the harmonic current of the load and the instant interruption, and has the fast response. First, the construction, the operation mode and algebraic modeling of LIDVR are reviewed. And then a voltage controller is proposed to get sinusoidal load voltage with constant amplitude. To find PWM method suitable for H-Bridge converter, two PWM methods are compared and analyzed. Finally, simulation results verify the proposed 5-level H-Bridge LIDVR system.

  • PDF

A Voltage Control Technique of Line-Interactive DVR Using 7-Level H-Bridge Inverter (7-레벨 H-Bridge 인버터를 이용한 Line-Interactive DVR의 전압제어)

  • Kang, Dae-Wook;Hyun, Dong-Seok;Lee, Woo-Cheol
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.56 no.4
    • /
    • pp.705-715
    • /
    • 2007
  • Recently, the interest on power quality has been hot issue because the equipments cause voltage disturbance and have become more sensitive to the voltage disturbance. Additionally, the reseach on power electronic equipments applying to the high power has been increased. This paper deals with Line-Interactive Dynamic Voltage Restorer(LIDVR) system using 7-Level H-Bridge inverter, which is one of the solutions to compensate the voltage disturbance and to increase the power of equipments. The LIDVR has the following advantages comparing to the DVR with the series injection transformer. It has the power factor near to unity under the condition of normal source voltage, can compensate the harmonic current of the load and the instant interruption, and has the fast response. First, the construction, the operation mode and algebraic modeling of LIDVR are reviewed. And then the voltage control algorithm is proposed to get the sinusoidal load voltage with constant amplitude. Finally, simulation and experiment results verify the proposed LIDVR system.