• 제목/요약/키워드: Line voltage regulation

검색결과 129건 처리시간 0.03초

용량성배전변압기에 관한 연구 (A study on capacitive transformer)

  • 이승원
    • 전기의세계
    • /
    • 제18권2호
    • /
    • pp.7-14
    • /
    • 1969
  • From the first customer located right at the substation to the last customer at the end of the line, voltage must be held within close limits, so the voltage regulation is more important than the thermal limit. On a typical distribution system during the peak load period, the voltage drop may be serious enough to cause unsatisfactory operation of home appliances in the residential area, and present many problems to manufacturing industries, where the voltage must be maintained within close limits to insure smooth operation. Among all the factors contributing to voltage drop in the distribution system, the voltage drop in the distribution transformer may account for 30% of this figure. If we can eliminate this factor, the power companies can provide better quality electricity to more customers with the existing distribution facilities, thus saving on initial investment costs. Taking all these problems into consideration, the author undertook the design of a capacitive transformer which would give zero voltage drop at rated load and at 80% lagging power factor while incorporating overload features to withstand 400% overload for at least 100 seconds. The following are the results obtained through design, manufacture and test of an initial experimental transformer built with these specific purposes.

  • PDF

역률개선 위한 자기에어지 궤환기법의 간단한 삼상 단일전력단 AC/DC 컨버터 (A Simple Three-Phase Single-Stage AC/DC Converter with Magnetic Energy Feedback Technique for Power Factor Correction)

  • 문건우;윤석호;윤종수;이기선;추진부
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 1998년도 전력전자학술대회 논문집
    • /
    • pp.438-443
    • /
    • 1998
  • A simple single-stage AC/DC forward converter with transformer magnetic energy feedback technique for power factor correction is proposed. The operational principle of the proposed converter is presented. The proposed converter gives the good power factor correction, low line current harmonic distortions, and tight output voltage regulation. The prototype shows high power factor with low line current harmonics.

  • PDF

저전력 용량성 센서 인터페이스를 위한 저잡음 CMOS LDO 레귤레이터 설계 (Design of the low noise CMOS LDO regulator for a low power capacitivesensor interface)

  • 권보민;정진우;김지만;박용수;송한정
    • 센서학회지
    • /
    • 제19권1호
    • /
    • pp.25-30
    • /
    • 2010
  • This paper presents a low noise CMOS regulator for a low power capacitive sensor interface in a $0.5{\mu}m$ CMOS standard technology. Proposed LDO regulator circuit consist of a voltage reference block, an error amplifier and a new buffer between error amplifier and pass transistor for a good output stability. Conventional source follower buffer structure is simple, but has a narrow output swing and a low S/N ratio. In this paper, we use a 2-stage wide band OTA instead of source follower structure for a buffer. From SPICE simulation results, we got 0.8 % line regulation and 0.18 % load regulation.

A High Current Efficiency CMOS LDO Regulator with Low Power Consumption and Small Output Voltage Variation

  • Rikan, Behnam Samadpoor;Abbasizadeh, Hamed;Kang, Ji-Hun;Lee, Kang-Yoon
    • 전기전자학회논문지
    • /
    • 제18권1호
    • /
    • pp.37-44
    • /
    • 2014
  • In this paper we present an LDO based on an error amplifier. The designed error amplifier has a gain of 89.93dB at low frequencies. This amplifier's Bandwidth is 50.8MHz and its phase margin is $59.2^{\circ}C$. Also we proposed a BGR. This BGR has a low output variation with temperature and its PSRR at 1 KHz is -71.5dB. For a temperature variation from $-40^{\circ}C$ to $125^{\circ}C$ we have just 9.4mV variation in 3.3V LDO output. Also it is stable for a wide range of output load currents [0-200mA] and a $1{\mu}F$ output capacitor and its line regulation and especially load regulation is very small comparing other papers. The PSRR of proposed LDO is -61.16dB at 1 KHz. Also we designed it for several output voltages by using a ladder of resistors, transmission gates and a decoder. Low power consumption is the other superiority of this LDO which is just 1.55mW in full load. The circuit was designed in $0.35{\mu}m$ CMOS process.

Current Detection 구조 및 향상된 Load Regulation 특성을 가진 LDO 레귤레이터 (LDO Regulator with Improved Load Regulation Characteristics and Current Detection Structure)

  • 권상욱;공준호;구용서
    • 전기전자학회논문지
    • /
    • 제25권3호
    • /
    • pp.506-510
    • /
    • 2021
  • 본 논문에서는 current detection 구조로 인하여 load regulation의 변화를 향상시킨 LDO를 제안하였다. 제안된 LDO 레귤레이터는 출력단에 제안된 current detection 회로를 추가하였다. 그로인하여 출력에 부하전류에 따른 전압 값의 regulation을 향상시켜 기존 LDO 레귤레이터보다 load Regulation의 변화량을 향상시켰다. 제안한 current detection 구조를 사용하여 부하전류의 변화에 따른 출력 변화를 약 60 % 가량 향상시킬 수 있었다. Cadence의 Virtuoso, Spectre 시뮬레이션을 사용하여 특성을 시뮬레이션 및 검증하였다.

입력전압 파형 검출만으로 구성된 단상 PFC 정류회로 (single-phase PFC rectifier circuit consonant to Input voltage waveform detection)

  • 정상화;이현우;전중함;서기영
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 학술대회 논문집 전문대학교육위원
    • /
    • pp.12-15
    • /
    • 2002
  • This propose a simple DC voltage sensor less single phase PFC(Power Factor Correction Circuit) converter by detecting a AC current sensors are not required to construct the control system. The DC voltage is directly controlled by the command input signal Kd($V_o/V_a$)for the boost chopper circuit. The DC voltage regulation is small because of the feed forward control for the AC line voltage VS and no dependence of the circuit parameters. The sinusoidal current waveform in phase with the AC input voltage can be obtained. These characteristics are confirmed by some experiment results.

  • PDF

Design of an Adaptive Fuzzy Controller for Power System Stabilization

  • Park, Young-Hwan;Park, Jang-Hyun;Yoon, Tae-Woong;Park, Gwi-Tae
    • 한국지능시스템학회:학술대회논문집
    • /
    • 한국퍼지및지능시스템학회 1998년도 The Third Asian Fuzzy Systems Symposium
    • /
    • pp.432-437
    • /
    • 1998
  • Power systems have uncertain dynamics due to a variety of effects such as lightning, severe storms and equipment failures. The variation of the effective reactance of a transmission line due to a fault is an example of uncertainty in power system dynamics. Hence, a robust controller to cope with these uncertainties is needed. Recently fuzzy controllers have become quite popular for robust control due to its capability of dealing with unstructured uncertainty. Thus in this paper we design an adaptive fuzzy controller using an input-output linearization approach for the transient stabilization and voltage regulation of a power system under a sudden fault. Simulation results show that satisfactory performance is achieved by the proposed controller.

  • PDF

전력 계통 과도상태 안정화를 위한 비선형 적응 백스테핑 제어기 설계 (Design of an Adaptive Nonlinear Backstepping Controller for Transient Stabilization of Power Systems)

  • 김동헌;김홍필;양해원
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제49권7호
    • /
    • pp.332-338
    • /
    • 2000
  • In this paper, a robust nonlinear excitation controller is proposed to achieve both voltage regulation and system stability enhancement for single machine-infinite power systems. The proposed method employs backstepping technique and combines this with an adaptation algorithm for estimating the effective reactance of transmission line, thereby leading to adaptive nonlinear control. Simulation results show that power that angle stabilization as well as voltage regulation is achieved in a satisfactory manner, regardless of the system operating conditions and system structure.

  • PDF

안정적 전력공급을 위한 154kV 변전소 배전선로간 연계운영에 관한 연구 (A Study on Loop operation of 154kV Substation Distribution line for Stable power supply)

  • 김광호;손명권;정종찬
    • 산업기술연구
    • /
    • 제29권B호
    • /
    • pp.221-228
    • /
    • 2009
  • For a stable supply of electric power, periodical inspection of the electric facilities and repair of the distribution lines are required. In case of any unexpected accidents, looped operation among distribution lines may be necessary in order to supply electricity through the sound lines, separating the faulted lines. As a result of this study, it was found that normal looped operation became impossible when phase difference of the looped distribution lines is more than 3 degrees compared with the voltage supply of the distribution lines. Therefore, for a stable supply of electric power to Chuncheon, it is judged to be desirable that looped operation of the distribution lines coming from the same substation M. Tr Bank shall be performed in principle and in case of looped operation with the substation of different system, looped operation among the lines shall be performed after voltage regulation of the substation M. Tr Bank, maintaining similar voltages and load supply volume in order to avoid phase difference through checking the operation conditions of each substation M. Tr Banks. And when looped operation among the distribution lines is scheduled, voltage regulation schedule has been established so far by calculating maximum supply volume through the transformer of the substation and the maximum load volume through the distribution lines but in the future, looped operation of the distribution lines shall be carried out by removing voltage difference with regulating tap or load of the surrounding transformers, with giving prior notice to the substation operators.

  • PDF

ULTC 와 SVR 이 설치된 배전계통에서 LDC Parameters 을 고려한 최대 DG 용량 산정 (The Installable Maximum DG Capacity Considering LDC Parameters of ULTC and SVR in Distribution Systems)

  • 김미영
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.27-28
    • /
    • 2008
  • For stable and sustainable energy supply, distributed generator (DG) has become an essential and indispensable element from environmental and energy security perspectives. However, installation of DG in distribution systems may cause negative affects on feeders because power outputs of DG could be changed irregularly. One of major negative affects is variation in voltage profile. In general, voltage regulation devices such as under load tap changer (ULTC) at distribution substation and step voltage regulator (SVR) along feeder in distribution system are used to maintain customers' receiving voltage within a predetermined range. These regulators are controlled by line drop compensation (LDC) method which calls for two parameters; the equivalent impedance and the load center voltage. Therefore, consideration of DG outputs in the LDC parameter design procedure may give large impact on the installable DG capacity. This paper proposes a method that estimates maximum Installable DG capacity considering LDC parameters of ULTC and SVR. The proposed algorithm is tested with model network.

  • PDF