• Title/Summary/Keyword: Line discharge

Search Result 529, Processing Time 0.037 seconds

On-line and Off-line Partial Discharge Monitoring System with HVAC Testing (HVAC에 의한 On-line, Off-line PD 모니터링)

  • Choi, Yong-Sung;Lee, Kyung-Sup
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2008.04c
    • /
    • pp.111-114
    • /
    • 2008
  • The paper considers the relation between on-line monitoring and diagnostics on the one hand and high-voltage (HV) withstand and partial discharge (PD) on-site testing on the other. HV testing supplies the basic data (fingerprints) for diagnostics. In case of warnings by on-line diagnostic systems, off-line withstand and PD testing delivers the best possible information about defects and enables the classification of the risk. Because alternating voltage (AC) is the most important test voltage, the AC generation on site is considered. Frequency tuned resonant (ACRF) test systems are best adapted to on-site conditions. They can be simply combined with PD measuring equipment. The available ACRF test systems and their application to electric power equipment -from cable systems to power transformers - is described.

  • PDF

Evaluation of Reliability on the 6.6kV Class Ceramic Coupler for On-line Partial Discharge Measurement in Winding Machines (권선형기기 On-line 부분방전 측정용 6-6kV급 Ceramic Coupler의 신뢰성 평가)

  • Kang Dong-Sik;Kim Yong-Joo;Yun Youn-Ho
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.54 no.2
    • /
    • pp.69-75
    • /
    • 2005
  • In order to improve the reliability of high voltage rotating machines and mold transformers, it is necessary to understand the breakdown mechanism and life assessment of the high voltage winding parts. Especially the on-line PD test provides the ability to monitor effects, such as slot discharge, internal discharge, and end-winding discharge without interrupting the electrical machines, this method has been proven the major testing technology. Capacitive couplers have been the most widely used sensors for the on-line partial discharge detection in rotating machines nowadays. This paper deals with the electrical characteristics and long-term reliability of a ceramic coupler(CC), which can be easily mounted into high voltage input terminal part, has been developed and tested to continuously measure PD activity during operating condition. This paper presents electrical characteristics (dielectric loss angle, capacitance, PD inception level, breakdown voltage, and frequency response bandwidth) and long-term life test result of the developed 6.6 kV class on-line ceramic coupling sensor. It was found that this sensor had good electrical characteristics to detect PD activity during the operating condition with its detection frequency band is between several and several tens MHz. Also, the voltage life of the 6.6kV class ceramic coupler was calculated over 60 years.

Insulation Aging Properties of Off-Line and On-Line High Voltage Motor Stator (정지중 및 운전중 고압전동기 고정자 권선의 절연열화 특성)

  • Kim, Hee-Dong;Lee, Young-Jun;Ju, Young-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2001.07c
    • /
    • pp.1694-1696
    • /
    • 2001
  • Partial discharge(PD) tests are used to evaluate the insulation condition of stator windings in six 6.6kV motors. These tests were conducted using a conventional partial discharge detector (PDD), turbine generator analyzer(TGA) and partial discharge analyzer(PDA). Off-line PD measurements were performed on six 6.6kV motors. PD magnitudes ranged from 740 pC to 5,100 pC at the normal line-to-ground voltage. Six 6.6kV motors have been equipped with eighteen 80pF epoxy-mica couplers(one per phase) on the motor terminal boxs. The PD pulse from sensors were measured with the TGA and PDA instruments on a normally operating motors. The PDD, TGA and PDA test results showed that internal discharge was detected in voids of the groundwall insulation.

  • PDF

A Study on the Optical Gain Characteristics of a UV Line 250.199nm from Helium-Zinc Discharge Excited by CCRF with Overlapped DC (DC 중첩형 CCRF 여기 헬륨-아연방전에서 자외선 250.199nm의 광이득 특성 연구)

  • Choi, Sang Tae
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.28 no.7
    • /
    • pp.13-18
    • /
    • 2014
  • On 250.199nm uv-line, witch has the potential to emit as a laser line, from a ccrf-excited He-Zn discharge with overlapped DC was carried out optimization of the discharge parameters and measurement of the optical gain. In this study the optical gain of the 250.199nm uv-line has been optained 4% for the first time. At a rf-power of 400W with the frequency 13.56MHz the optimal He-pressure indicated 2kPa.

A Study on the on Line Monitoring Techniques of the Partial Discharge for Transformer (변압기 부분방전 상시 감시기법에 관한 연구)

  • 권동진;박재준
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.14 no.12
    • /
    • pp.1032-1040
    • /
    • 2001
  • In order to apply the partial discharge measuring technique utilizing electrical pulse to the transformer at sites, this paper describes the measuring technique obtaining only the signals due to internal partial discharge in the transformer, but the noises due to external corona which has been a major problem so far. At first, partial discharge and corona noise were simultaneously generated in the model transformer by using needle-plane electrodes and rod-sphere electrodes out of it in a high voltage laboratory, respectively. It was verified that only the partial discharge signals in the transformer could be measured by removing the noise signals from the superposed signals of partial discharges and noises on the grounding wire of the model transformer. By application to a 345kV transformer in service, it was also confirmed that the partial discharge could be on-line monitored by removing the noise signals measured by the inductance sensor on the grounding wire of a 154kV lightning arrester from the superposed signals of internal partial discharge and external corona noise measured by bushing tap coupler of the transformer.

  • PDF

An Application of the On Line Partial Discharge Measurement Method in Transformer (온라인 변압기 부분방전 측정기법 적용)

  • Kweon, Dong-Jin
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.50 no.8
    • /
    • pp.394-400
    • /
    • 2001
  • This paper describes an application of the on line partial discharge measurement method in operating transformer. In the operating transformer, the partial discharge signal may be superimposed by radio intereference voltage(RIV) and pulse shaped noise signals generated by external corona. The partial discharge quantity showed about 3,800pC due to very high sinusoidal interferences at the measuring impedance terminal of the transformer bushing tap. In order to reject these noises, this paper applied RIV filter, band-pass filters and noise gating method. The resulting measuring sensitivity was improved from 3,800pC to 160pC.

  • PDF

On Line Partial Discharge Measurement Method for Transformer (온라인 변압기 부분방전 측정기법)

  • Kweon, Dong-Jin;Choi, In-Hyuk;Song, Il-Keun;Park, Jae-Jun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.05c
    • /
    • pp.38-42
    • /
    • 2001
  • This paper describes an application of the on line partial discharge measurement method in operating transformer. In the operating transformer, the partial discharge signal may be superimposed by radio intereference voltage(RIV) and pulse shaped noise signals generated by external corona. The partial discharge quantity showed about 3,800pC due to very high sinusoidal interferences at the measuring impedance terminal of the transformer bushing tap. In order to reject these noises, this paper applied RIV filter, band-pass filters and noise gating method. The resulting measuring sensitivity was improved from 3,800pC to 160pC.

  • PDF

Analysis of Off-Line and On-Line Partial Discharge in High Voltage Motor Stator Windings

  • Kim, Hee-Dong;Kong, Tae-Sik;Lee, Sang-Kil;Kim, Beom-Soo;Kim, Doo-Young
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.3
    • /
    • pp.1086-1092
    • /
    • 2015
  • The off-line and on-line partial discharge (PD) in the stator winding of three high-voltage (HV) motors (1,400 HP, 6.6 kV) is measured and analyzed in this paper. The off-line PD is measured at high values between 24,300 ~ 36,100 pC after 18 years of motor operation. Spare replacement motors were not available for testing the degree of deterioration of the stator windings in standstill status. Therefore, on-line periodic analysis was conducted to monitor the trend of PD after installing a ceramic sensor (110 pF, 6.6 kV) in the terminal box for each phase of each motor. In the stator winding of the No.1 and No.2 HV motors, which showed high magnitudes of off-line PD and low magnitudes of on-line PD, defects are expected to appear in the neutral end of the winding. On the contrary, in the stator windings of the No.3 HV motor, which exhibits high off-line and on-line PD magnitude, defects are expected to appear in the terminal end of the winding where a voltage close to the phase voltage is applied.

Considerations on the Long-term Reliability of On-line Partial Discharge Ceramic Sensor for Thermal Power Generators and its Demonstration in the Field

  • Sun, Jong-Ho;Youn, Young-Woo;Hwang, Don-Ha;Kang, Dong-Sik
    • Journal of Electrical Engineering and Technology
    • /
    • v.7 no.1
    • /
    • pp.103-108
    • /
    • 2012
  • The present study describes the considerations on the long-term reliability of the on-line partial discharge (PD) ceramic sensor for thermal power generators. Voltage acceleration aging tests were carried out under continuous and impulsive thermal aging at more than $100^{\circ}C$, considering the practical service environment. Experimental results show that the sensors have a life that could last for more than 100 years, excellent dielectric characteristics, and insulation strength. In addition, the ceramic on-line PD sensors were installed in a thermal power generator in Korea for demonstration. The results of the PD calibration and test voltage application prove that the on-line ceramic sensors have satisfactory performances for on-line PD measurement.

Fundamental study of electrolyte cathode atomic discharge for development of on-line monitoring system (On-line monitoring system 개발에 관한 음극 액상 글로우 방전의 기초 연구)

  • Kim, Kyung-Mi;Woo, Young-A;Cho, Won-Bo;Kim, Hyo-Jin
    • Analytical Science and Technology
    • /
    • v.15 no.6
    • /
    • pp.496-501
    • /
    • 2002
  • The electrolyte cathode glow discharge (ELCAD) is a new optical system for direct determination of trace heavy metals in flowing water. ELCAD has been successfully developed for on-line monitoring of heavy metals in flowing water. The application of an atmospheric glow discharge between an electrolyte solution cathode and a platinum rod anode led to the development of stable discharge. The fundamental aspects of new plasma source have been investigated. The fundamental study of ELCAD system has been measured plasma temperature using Einstein-Boltzmann equation after searching Fe atomic emission lines. The spectrum of each elements such as Cu, Pb, Fe, Ni and Cr show only major elemental line and no ionic line possibly due to low temperature plasma source. The detection limits of each elements are also investigated. These informations show that this type of plasma may apply for monitoring of heavy metals in waste water which consists of complex matrix.