탄소블록과 동봉의 접지임피던스 비교 분석 (Comparative Analysis on Ground Impedance for a Carbon Block and a Copper Rod)

  • 서재석;박희철;길경석;오재근
    • 한국전기전자재료학회논문지
    • /
    • 제26권6호
    • /
    • pp.472-477
    • /
    • 2013
  • This paper carried out the comparative analysis on ground impedance of a carbon block and a copper rod. Two types of grounding electrode were compared ; a carbon block (L : 1 m, ${\Phi}$ : 245 mm) buried at a depth of 0.8 m and a three-linked copper rod (L : 1 m, ${\Phi}$ : 10 mm) of equilateral triangles with 1 m spacing. Ground impedance depending on applied current source was evaluated by the application of a sine wave current with 60 Hz ~ 3.5 MHz, a fast-rise pulse with rising time of 200 ns, a standard lightning impulse of $8/20{\mu}s$ and a 600 Hz square wave. Ground impedance for both electrodes were almost the same value below 100 kHz, and increased rapidly afterwards. The maximum ground impedance appeared $400{\Omega}$ at around 1.5 MHz. Ground impedance of the carbon block was lower at the square wave and was higher at fast-rise pulse than that of the copper rod. Also, ground impedance as ages showed no difference for the last 8 months. From the results, it is likely that ground performance for both electrodes shows no difference against commercial frequency and lightning impulse current, while the copper rod shows better performance against a fast-rise pulse with rise-time of a few hundred ns.

Simulations of Frequency-dependent Impedance of Ground Rods Considering Multi-layered Soil Structures

  • Lee, Bok-Hee;Joe, Jeong-Hyeon;Choi, Jong-Hyuk
    • Journal of Electrical Engineering and Technology
    • /
    • 제4권4호
    • /
    • pp.531-537
    • /
    • 2009
  • Lightning has a broad frequency spectrum from DC to a few MHz. Consequently, the high frequency performance of grounding systems for protection against lightning should be evaluated, with the distributed parameter circuit model in a uniform soil being used to simulate grounding impedances. This paper proposes a simulation method which applies the distributed parameter circuit model for the frequency-dependent impedance of vertically driven ground rods by considering multi-layered soil structures where ground rods are buried. The Matlab program was used to calculate the frequency-dependent ground impedances for two ground rods of different lengths. As a result, an increase of the length of ground rod is not always followed by a decrease of grounding impedance, at least at a high frequency. The results obtained using the newly proposed simulation method considering multi-layered soil structures are in good agreement with the measured results.

154kV 송전선로용(送電線路用) Arcing Horn 개발(開發)에 관한 연구(硏究) (A study for the development of arcing horns in 154kV T/L)

  • 이형권;박동욱;이동일;정동원;김정부
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1989년도 하계종합학술대회 논문집
    • /
    • pp.443-446
    • /
    • 1989
  • 154kV insulator strings are frequently damaged by lightning strokes, overvoltage and contamination. And this insulator damage inflicts a loss on the power company. The purpose of this paper is to develop the arcing horn as a protective device of 154kV insulator strings against lightning flashover and overvoltages. So We have developed the arcing horn which is suitable for 154kV transmission line and estimated the performance of arcing horn by high current arcs and high voltage tests.

  • PDF

Data Transmission over Power Line with Lightning Protection Devices

  • Kim, Sungeon;Jeon, Taehyun
    • International journal of advanced smart convergence
    • /
    • 제2권1호
    • /
    • pp.27-29
    • /
    • 2013
  • This paper discusses comparative analysis of the effects of surge protection devices (SPD) upon the power line communication channels. The quality of the data transmission channel is measured based on the data rate for the various channel parameters which include channel length and application method of the lightning protection device. The performance measurements are also carried out for various lengths of the communication channel. Experiment results show that specific combination of SPDs applied in the network causes severe degradation of the channel quality which is associated with the combination of grade levels and channel lengths.

154 kV 송전선로에 피뢰기 설치시 내뢰성 향상효과 모의 (A simulation of Lightning Performance of the 154 kV Transmission Line with the Surge Arrester Installation)

  • 심응보;우정욱
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 하계학술대회 논문집 E
    • /
    • pp.1642-1644
    • /
    • 1997
  • The simulation study of lightning faults reducing effects by the installation of surge arresters on the 154 kV transmission line is stated here. For the purpose of detailed simulation of arcing horn, a flashover model with dynamic characteristics of arcing horn gap was represented as a non-linear inductance which is controlled by EMTP/TACS(Electromagnetic Transient Program/fransient Analysis of Control Systems) switches. The back flashover inducing current was increased from 50 kA to 88 kA by the installation of surge arresters on the transmission line which has one ground wire and 20 ohms of tower footing resistances. The great advantage of surge arrester installation on one circuit of the double circuit transmission line is to prevent the simultaneous back flashover up to 190 kA.

  • PDF

전류구동형 서지카운터 (Current Driving Type Surge Counter)

  • 이복희;안창환;장석훈;정관모;전덕규
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 하계학술대회 논문집 E
    • /
    • pp.1712-1714
    • /
    • 1997
  • This paper deals with the surge counter drived by lightning and switching currents. In order to install the effective surge protective devices, it is important to find the parameters of incident surges. In this paper, for the purpose of protecting the electronic circuits and counting the occuring frequency, the current driving type surge counter is designed and fabricated. The surge counter consists of surge protective divices, current detector, metal oxide varistor(MOV), rectifier, capacitor, and electromagnetic counter. This surge counter is able to count the occuring frequency of surges and to clamp lightning surge current. To evaluate the performance of the surge counter, impulse voltage and current were applied at the surge counter by the surge generator. As a result, applied surges were exactly counted and clamped.

  • PDF

내뢰성 향상을 위한 154 kV 송전선용 피뢰기의 성능 시험 (A Type Test of 154 kV Transmission Line Arrester for improvement of lightning performance)

  • 곽주식;강연욱;우정욱;심응보;박윤석
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 추계학술대회 논문집 전력기술부문
    • /
    • pp.454-456
    • /
    • 2003
  • This paper describes a type test results of 154 kV transmission line arrester with external gap. The test was carried on surge arrester unit and line arrester with external gap, respectively. Withstand voltage test demonstrate the voltage withstand capability of the line arrester with external series gap under the dry and wet conditions. In insulation coordination test external series gap shall be discharged every time when lightning impulse voltage with the steepness of more than 1500 $kV/{\mu}s$ are applied under the wet condition.

  • PDF

MATLAB 프로그램을 이용한 배전계통에 사용되는 동봉 접지전극의 과도 접지임피던스 특성 분석 (Transient Grounding Impedance Characteristic Analysis of a Copper Rod-type Grounding Electrode Used for Electric Distribution Systems Using MATLAB Program)

  • 김경철;오경훈;이규진;심건보;최종기
    • 조명전기설비학회논문지
    • /
    • 제23권9호
    • /
    • pp.40-46
    • /
    • 2009
  • 비록 접지저항은 접지전극의 접지성능을 좌우하는 지수이기는 하지만, 과도상태에서는 접지 성능을 반영하지 못한다. 동봉은 배전계통에서 가장 많이 쓰이는 접지전극이다. 본 논문에서는 동봉의 접지 임피던스를 주파수 60[Hz]에서 100[kHz] 범위까지 측정하여 등가 접지임피던스 모델을 구하였다. 뇌격서지가 유입되었을 때 MATLAB 프로그램으로 과도접지임피던스의 수치와 파형을 시뮬레이션하였다.

선화아연바리스터 기반의 1-포트 서지보호장치의 최적 설계 기법 (Optimal Design Method of 1-Port Surge Protective Device Based on Zinc Oxide Varistor)

  • 정태훈;김용성;박근보;이승일
    • 한국산학기술학회논문지
    • /
    • 제19권4호
    • /
    • pp.93-102
    • /
    • 2018
  • 본 논문은 뇌격전류에 따른 저압 배전계통의 전자식 전력량계 및 배전 패널의 통신설비와 전원장치를 보호할 목적으로 사용하는 서지보호장치(SPD)에 관한 것이다. 서지보호장치(SPD)는 접속방식에 따라 1-포트 서지보호장치(SPD)와 감결합 요소를 포함한 2-포트 서지보호장치(SPD)로 구분된다. 뇌격전류에 대한 내부 시스템의 보호는 협조된 서지 보호체계를 이루는 계통적인 접근이 필요하다. 이에 대응하기 위해 이론적인 검토를 통해 피뢰구역(LPZ) 정의에 대한 고찰 및 해석을 진행하였다. 뇌서지에 의한 뇌격전류는 상당히 크기 때문에 하나의 서지보호장치(SPD)로 방호하기에는 한계가 발생하며, 이를 해결하기 위해 다단의 종속적으로 서지보호장치(SPD)를 설치하게 된다. 본 논문에서는 전력계통에 있어 한전계통에 연계되는 Incoming side가 아닌 건물 내에 설치되는 분기형 배전패널 내부의 전자식 전력량계 및 각종 통신(제어)설비를 보호할 목적으로 한전계통이 연계되는 MOF 단에 설치되는 LPZ0에 해당하는 피뢰기(LA, SA)와 보호협조를 이루는 LPZ1과 LPZ2의 경계영역에 설치하는 저압 배전계통용 II등급 서지보호장치(SPD)에 대해 설계를 하였다. 또한 감결합 요소가 없고, 부하 전류를 흘릴 수 있는 직렬 접속 방식의 1-포트 서지보호장치(SPD)에 대한 최적의 설계 방안을 도출하고 실험을 통해 기존의 방식과 비교하여 성능 개선과 관련한 검증을 실시하였다.

안정성 개선을 위해 열폭주 방지 기능을 내장한 배리스터 설계에 관한 연구 (A Study on the Design of Varistor Prevented from Thermal Runaway to Improve Safety)

  • 정태훈;신희상;조성민;이희태;이준규;김재철
    • 조명전기설비학회논문지
    • /
    • 제24권2호
    • /
    • pp.69-76
    • /
    • 2010
  • 본 논문은 SPD에 사용되는 배리스터에 대한 성능을 개선하기 위해 저압 배전계통에 사용하는 ZnO 배리스터의 소자 표면에 온도감응 소재를 도포한 것을 내장한 SPD의 신뢰성과 안정성을 개선하였다. '열폭주 방지 기능을 내장한 배리스터'설계를 통해 SPD내에 장착 시 열 보호기능의 단로기의 기능에 대한 trade-off 관계해석(trade-off:단로기에 단일펄스피크전류(ITM), 다중펄스피크전류(ITSM)에 대한 신뢰성과 배리스터 소자의 열화 및 수명한계에 따른 열폭주 현상을 예방하기 위한 단로기의 안정성 확보를 위한 최적의 설계)을 통해 신뢰성과 안정성을 확보하였고 열 보호기능을 배리스터 내부에 적용하여 SPD제작시 소형/경량화가 가능하도륵 하였다.