• 제목/요약/키워드: Interfacial breakdown

검색결과 61건 처리시간 0.025초

도포된 오일의 변화에 따른 Epoxy/EPDM 계면의 교류 절연파괴 특성에 관한 연구 (A Study on the AC Interfacial Breakdown Properties of the Interface between Epoxy/EPDM with Variation of the Spread Oil)

  • 배덕권;정일형;오재한;박우현;이기식;김충혁;이준웅
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제49권8호
    • /
    • pp.445-450
    • /
    • 2000
  • Many successful developments and microscopic studies have been made on the high quality insulating materials. However, a little attention have given to the macroscopic interface in HV(High Voltage) insulating systems. In this study, AC interfacial breakdown strength and V-t characteristic of the interface between Epoxy/EPDM(ethylene propylene diene terpolymer) are investigated. Electrode system is designed to reduce the charges from electrodes and to have the tangential potentials along the interface between Epoxy/EPDM by FEM(finite elements method). The AC breakdown strength is observed when HV is given to the interface. It is shown that AC interfacial breakdown strength is improved by increasing interfacial pressure and oiling. In particular, it was saturated at certain interfacial pressure level. V-t characteristic is able to extend to the life time of the interface between Epoxy/EPDM. Oiling also plays a good roll in prolongation of the life time.

  • PDF

에폭시/고무 거시계면에서 장시간 절연파괴전압에 대한 연구 (Study on the Long Time Breakdown Voltage in the Macro Interface between Epoxy and Rubber)

  • 박우현;이기식
    • 한국전기전자재료학회논문지
    • /
    • 제15권11호
    • /
    • pp.1003-1008
    • /
    • 2002
  • In this paper, the estimation of lifetime with the various conditions of the interface between toughened epoxy and rubber which are consisting materials of underground power delivery system has been studied. After the measurement of the short time AC interfacial breakdown strength on macro interfaces at room temperature, the breakdown time at several voltages were measured under the constant voltages lower than the short time breakdown voltage. The long time breakdown voltage was calculated by using Inverse Power Law. Two types of interfaces was studied. One was the interface between toughened epoxy and EPDM(Ethylene Prorylene Diene Terpolymer). The other was the interface between toughened epoxy and silicon rubber. Interfacial pressure and roughness of interfaces was determined through the characteristic of short time AC interfacial breakdown strength. Oil condition was no oiled, low viscosity oiled and high viscosity oiled. High viscosity oiled interface between Toughened epoxy and silicon rubber had the best lifetime exponent, 20.69. and the breakdown voltage of this interface after 30 years was evaluated 19.27㎸.

Epoxy/EPDM 이종절연물의 계면조건에 따른 계면절연파괴특성의 분석 및 시뮬레이션에 관한 연구 (A study on the analysis and simulation of interfacial breakdown properties with interfacial condition in Epoxy/EPDM)

  • 정인재;박성민;김영식;김상걸;장인범;김용주;이준응
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1998년도 추계학술대회 논문집
    • /
    • pp.227-230
    • /
    • 1998
  • The interfacial breakdown between two internal dielectric surfaces represents one of the major causes of failure for power cable joint. In order to better understand this phenomenon, breakdown experiments were performed for each interfacial condition at Epoxt/EPDM interface found in cable. The specimen were Epoxy resin and EPDM generally used in cable joint. The interface conditions were three parts. First condition was the pressure of interface, we used the value of 1, 2, 3, 4, 5[kg/cm$^2$]. For the second condition, the sanding condition was treated with sand paper #220, #600, #1200. Finally, we observed the breakdown according to the presence of silicon oil at the interface.

  • PDF

XLPE/EPDM laminate의 첨가제에 따른 전하분포특성 (Interfacial Breakdown Characteristics in XLPE/EPDM Laminate as a function of Additives)

  • 남진호;서광석
    • 한국항해항만학회:학술대회논문집
    • /
    • 한국항해항만학회 2000년도 추계학술대회논문집
    • /
    • pp.77-80
    • /
    • 2000
  • In order to determine what influences the interfacial charge in EPDM/XLPE laminates, We used PEA (pulsed electroacoustic) method. Interfacial properties such as space charge accumulation and breakdown strength in crosslinked polyethylene (XLPE)/ethylene-propylene-diene monomer (EPDM) laminates were investigated. Interfacial charge develops when the EPDM is laminated with XLPE. It showed the positive polarity same as the simulation in case on intercase of EPDM/XLPE. In case of coupling agent added silicone oil, as increasing the content of coupling agent, the interfacial charge decreased. Details of the results are given and their origins discussed.

  • PDF

XLPE/EPDM laminate의 첨가제에 따른 전하분포특성 (Interfacial Breakdown Characteristics in XLPE/EPDM Laminate as a function of Additives)

  • 남진호;서광석
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 추계학술대회 논문집
    • /
    • pp.77-80
    • /
    • 2000
  • In order to determine what influences the interfacial charge in EPDM/XLPE laminates, We used PEA (pulsed electroacoustic) method. Interfacial properties such as space charge accumulation and breakdown strength in crosslinked polyethylene (XLPE)/ethylene-propylene-diene monomer (EPDM) laminates were investigated. Interfacial charge develops when the EPDM is laminated with XLPE. It showed the positive polarity same as the simulation in case on intercase of EPDM/XLPE. In case of coupling agent added silicone oil, as increasing the content of coupling agent, the interfacial charge decreased. Details of the results are given and their origins discussed.

  • PDF

여러 종류의 에폭시/이종무기물 혼합 콤포지트의 전기적 교류 절연파괴 특성 (Electrical AC Insulation Breakdown Characteristics of Various Epoxy / Heterogeneous Inorganic Mixed Composite)

  • 박재준
    • 전기학회논문지
    • /
    • 제67권11호
    • /
    • pp.1463-1470
    • /
    • 2018
  • In this study, 20 types of samples were prepared by mixing different kinds of inorganic materials to develop insulation materials for epoxy - based GIS substation equipment used under high voltage environmentally friendly insulation gas. One of the electrical characteristics, AC insulation breakdown experiment was performed. As mixing ratio of mixed heterogeneous inorganic materials, the dielectric breakdown strength was increased with increasing filler ratio of micro silica, micro silica : micro Alumina, 1:9, 3:7, 5:5, 7:3, 9:1, and decreased as the filling amount of micro alumina increased. The AC insulation breakdown characteristics were the best when the composition ratio was 9:1. The higher the content of silica, the better the interfacial properties, and the larger the alumina content ratio, the worse the interfacial properties.

Epoxy/EPDM계면의 최적처리 조건과 수명 예측 (The Optiomun Treatment Conditions an the Estimation of Life in the Interface between Epoxy/EPDM)

  • 오재한;배덕권;최운식;이경섭
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 C
    • /
    • pp.1978-1980
    • /
    • 2000
  • Because the interfaces between two different materials are the weak-link in the underground power transmission systems, they affects the stability of insulation systems. In this paper, Epoxy/EPDM interface is selected and investigated the optimum condition by variation of interfacial conditions such as roughness of surface, spreading of oils, interfacial pressure and temperature. The breakdown times under the constant voltage below the breakdown voltage were also gamed. The breakdown voltage at the after laying time equivalent to is calculated by the V-t characteristic and the inverse power law. When this is done. the characteristic life exponent n is used and the long time breakdown voltage can be evaluated.

  • PDF

Toughened Epoxy/Rubber계면의 교류 절연파괴 현상에 관한 연구 (Study on the AC Interfacial Breakdown Prosperities in the Interface between Toughened Epoxy and Rubber)

  • 김태형;배덕권;이동규;정일형;김충혁;이홍표;이준웅
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 하계학술대회 논문집
    • /
    • pp.771-774
    • /
    • 2000
  • Recently, complex insulation method is used in insulation system for underground power delivery devices. Considering the interfaces which affect stability of insulation system, By modeling interface between Epoxy and Rubber, AC interfacial breakdown properties with variation of many conditions to influence on electrical properties were investigated. In this paper, toughened Epoxy and Silicone rubber were used for materials to make interface .

  • PDF

V-t 특성 분석에 의한 고체 거시계면의 수명 평가 (Prediction of Life-Time on the Macroscopic Interface between Solid Materials with Analysis of V-t Characteristics)

  • 오재한;이경섭;배덕권;김충혁;이준웅
    • 한국전기전자재료학회논문지
    • /
    • 제13권7호
    • /
    • pp.607-611
    • /
    • 2000
  • The characteristics on the interface between Epoxy and EPDM which are materials of the underground insulation systems of power delivery have studied. The breakdown strength of specimens are observed by applying high AC voltage at the room temperature. The breakdown times under the constant voltage below the breakdown voltage were gained. As constant voltage is applied the breakdown time is proportion to the breakdown strength. The life exponent n is gained by inverse power law and the long breakdown life time can be evaluated. AC breakdown strength and life time is improved by oiling to the interface. When the low viscosity oil is spread interface has the highest life time.

  • PDF

XLPE/EPDM의 계면처리조건에 따른 절연파괴 특성 (Breakdown Characteritics of XLPE/EPDM on the Treatment Condition of the Interfacial layer)

  • 한성구;조정형;이창종;박양범;박강식;한상옥
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1996년도 추계학술대회 논문집
    • /
    • pp.230-233
    • /
    • 1996
  • In this paper, We intended to evaluate characteristics of XLPE/EPDM interface which exists in the cable joint. Because the fault was mainly occurred in this interface. We investigated breakdown characteristics of XLPE/EPDM double layered insulator as a funtion of temperature, pressure, annealing time, kinds of jointmaterial. It was shown that breakdown strength of XLPE/EPDM insulators is higher that of XLPE/XLPE or EPDM/EPDM

  • PDF