• Title/Summary/Keyword: Insulators

Search Result 652, Processing Time 0.029 seconds

Artificial contaminated test method and leakage current characteristics of EHV insulators (송전용 애자의 인공오손시험 기법과 누설전류 특성)

  • Choi, In-Huyk;Jung, Yoon-Hwan;Choi, Jang-Hyun;Lee, Dong-Il
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.05a
    • /
    • pp.386-391
    • /
    • 2004
  • To find out the reason of accident by being stained of insulators, this paper researched and analyzed the result of electrical characteristic test and field test of EHV insulator through artificial contaminated method. The best way to evaluate contaminated level of insulator surface is getting a contamination data by regional groups continually. But it is needed a lot of time and manpower. To overcome those difficulties, this research introduced ESDD(equivalent salt deposit density) measurement method which is adapted to the international codes of IEC and compared the relation between experimental test results which contaminated insulators by going through stain procedure and electrical measurement results.

  • PDF

The Characteristics of Artificial Contamination of Distribution Polymer Insulators Used for Outdoor Insulation (옥외에서 사용되는 배전용 폴리머애자의 인공오손 특성)

  • 이병성;한재홍;김찬영;한상옥
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.11a
    • /
    • pp.595-597
    • /
    • 2000
  • Poymeric insulators using in an heavy contamination area are easily attached to contaminants such as salt and by-products of industrial processes. To understand its effect on contaminants adhered to these insulators, we manufactured slurry mixed by some kaolin and salt as artificial contaminated solution. And then put samples in its slurry, for about one minute. And these samples are dried in natural condition for 6 days. We measured the degree of contaminant, AC leakage current for these contaminated samples.

  • PDF

Effects of UV and Ozone on the Weathershed for Polymer Insulators (폴리머애자 갓 재료에 미치는 자외선 및 오존의 영향)

  • 이병성;한재홍;한용희;한상옥;윤여숭
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1999.11a
    • /
    • pp.63-66
    • /
    • 1999
  • The effects of UV and ozone on the weathershed materials for 5 polymer insulators were investigated. This study was carried by material characterizations such as surface microstructure, thermal property, chemical structure and contact angle. The aged specimens are compared with new ones. In case of UV, the chalking of fillers and cracking of surface were increased with the increase of UV radiation time. In case of ozone, aged specimens are not different from new ones. From this study, It can be concluded that UV has more effect on the surface properties of weathershed materials than ozone.

  • PDF

Evaluation of Artificially Contaminated Suspension Insulators for Transmission (송전용 현수애자의 인공오손 평가)

  • Kim, Chan Young;Choi, In-Hyuk;Hong, Dong-Suk;Kim, Beom-Soo
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.08a
    • /
    • pp.123-127
    • /
    • 2002
  • This paper presented the results of evaluation of artificially contaminated suspension insulators for transmission lines. The suspension insulators were contaminated with kaolin and clay which were included various amount of natural salt. The degree of contamination were evaluated by measuring equivalent salt deposit density(ESDD). Then, the leakage currents were measured as a function of applied voltage, degree of contamination, humidity.

  • PDF

Study on Thermal Stress of Porcelain Insulator for T/L (송전용 자기애자의 열충격 특성 연구)

  • Han, Se-Won;Cho, Han-Goo;Choi, In-Hyuk;Lee, Dong-Ill
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2006.06a
    • /
    • pp.208-209
    • /
    • 2006
  • This study presents the thermal stress characteristics of TL porcelain insulators(healthy and ageing) by the accelerating thermal mechanical ageing test with forced temperature gradient. The test temperature gradient is $95^{\circ}C(-35{\sim}60^{\circ}C)$, it was focused to high temperature thermal stress as compared with IEC 60575 standard. There was no a discrimination in the case of healthy aluminous porcelain insulators, dissimilarly in crystoballite insulators according to this test method. It was indicated that the long tenn reliability by thermal stress was conformed reasonably through the conventional accelerating ageing test methods.

  • PDF

Analyses of Leakage Current of Transmission Insulator as a Function of Environmental Condition (환경에 따른 송전용 애자의 누설전류 분석)

  • Choi, In-Hyuk;Lee, Dong-Il;Kim, Chan-Young
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.07b
    • /
    • pp.1166-1170
    • /
    • 2004
  • The leakage currents of transmission insulator were investigated as a function of environmental conditions, such as temperature, humidity, and rainfall. The insulators were artificially contaminated with insoluble yellow soil and kaolin which helped salt to stick on the surface of insulator. The insulators contaminated with the grade of B, C, and D were installed in the KoChang Testing Center. The leakage currents were measured and compared with non-contaminated insulators. The results indicated that the most important factor affecting leakage current was humidity. After heavy rain, the artificially contaminated salt was dissolved, resulting in similar characteristics between with and without contamination

  • PDF

Evaluation on the radio influence voltage of ${7^1/2}$ pin type domestic insulators (국산 핀애자의 라디오 방해 전압(RIV) 평가)

  • 양배덕
    • 전기의세계
    • /
    • v.25 no.6
    • /
    • pp.65-68
    • /
    • 1976
  • For the RIV characteristics test of power apparatus, an indoor measuring system of radio influence voltage was set up and by means of this measuring unit SIV characteristics on the 7$^{1}$2/" pin-type domestic insulators were examined. According to the test data, RIV values of all the test pieces exceeded the maximum permissible level at 10kV applied voltage. The electrical resistivity of domestic semi-conductive glaze as good as importedone but un-uniformity of coating is turned out to be a main cause of failure.lure.

  • PDF

Status Assessment of Composite Insulators for Outdoor HV Applications

  • Gorur, R.S.
    • Electrical & Electronic Materials
    • /
    • v.11 no.10
    • /
    • pp.6-12
    • /
    • 1998
  • An attempt has been made to summarize the research and development on the topic of assessing the status of composite Insulators used for outdoor power delivery. Advances made in the evaluation of the electrical performance are discussed. The findings are applicable to other composite insultaing systems, as well. Aspects that have been understood well enough to be of practical use, and those needing further research are outlined.

  • PDF

A Study on the Effects of Metallic Barriers on Surface Discharge and It's Application to Insulators and Bushings (연면방전에 미치는 도전층의 영향 및 그 애자, 투관에의 응용에 관한 연구)

  • 정성계
    • 전기의세계
    • /
    • v.19 no.2
    • /
    • pp.1-5
    • /
    • 1970
  • According to the previous studies which was done by the author, the flashover voltage was found to be increased considerably if some metallic barriere are inserted into the flashover discharge path. This paper shows that the flashover voltage in suspension insulators and bushings is raised up by the application of metallic barrier effect on surface discharge. Using moderate metallic barrier configulation the flash over voltage can be raised up by the amount of about 15% compared to that of the convensional type of suspension insulatiors and bushings.

  • PDF

A Review on the Development of Hold Clamp for Feeder Distribution Line (급전분기선 지지 크램프 개발에 대한 검토)

  • Park, Weon-Chan;Lee, Jae-Bong;Oh, Sung-Hyo;Park, Jong-Hak
    • Proceedings of the KSR Conference
    • /
    • 2010.06a
    • /
    • pp.1898-1903
    • /
    • 2010
  • The hold clamp which is for holding feeder distribution line in direct current can be lengthened its span of life by inserting insulators(EDPM rubber) through improving its function such as preventing damage from temperature change and electric corrosion. This paper reviews the development background, design, manufacture and performance assessment of the hold clamp inserting insulators to prevent circulating current.

  • PDF